SPECIFICATIONS
• Power supply: 3 x 1.5 V batteries, type: AA
• Sensor design: electrochemical (approx. 10 years of service life)
• Stand-by input current: 35 uA
• Alarm mode input current: 85 mA
• Sound level: 85 dB
• Light alarm indication
• LCD with CO concentration readings and message output
• Carbon monoxide detection levels (ref. standard: PN-EN 50291-1:2010+A1:2012):
- 50 ppm (in up to 90 minutes)
- 100 ppm (in up to 40 minutes)
- 300 ppm (in up to 3 minutes)
• Additional Test Certicate for CO Detection Sensitivity
(300 ppm detected in less than 3 min), tested in a dedicated test chamber
• Ingress protection rating: IP 20
• Operating temperature: 0°C to +45°C
• Operating humidity: 0 to 90% RH
• Dimensions: 140 × 65 × 27 mm
1. INSTALLATION
• It is recommended that the device is installed by a qualied individual.
• Keep the product in a dry place away from sunlight. Protect the detector from damage in transport and while handling; damage may
reduce the service life. Do not use the detector if any damage is evident. It is recommended to have the product installed by a qualied
professional.
• Install the detector near locations extremely exposed to carbon monoxide concentrations developing from combustion of fuel, e.g. earth
gas, wood, or coal. To prevent false detection alarms, install the CO detector at least 2 m from all potential carbon monoxide emission
sources.
• Install the CO detector approx. 150 cm above the oor.
• To ensure optimum protection against CO hazards, install CO detectors in all rooms of prolonged inhabitation, especially bedrooms. Install
at least one CO detector per storey in multistorey buildings.
• Do not install CO detectors in ‘dead spaces’ (e.g. in recesses closed off by pieces of furniture or curtains, underneath the roof gable, etc.)
and wherever the detection performance will be reduced by currents of fresh air (e.g. near doors, windows, ventilation diffusers or air
fans). Do not install CO detectors in locations highly exposed to airborne dust, aerosols or household chemical which may cause irrepara-
ble failure of the detector.
Warranty Certicate
Reseller’s stamp and signature with date
Reseller’s stamp and signature with date
24-month commercial warranty granted by
ZAMEL Sp. z o.o.
1. ZAMEL Sp. z o.o. grants a 24-month warranty for the products it sells.
2. The warranty granted by ZAMEL Sp. z o.o. does not cover:
a) defects caused by transport, handling or other factors;
b) defects caused by improper installation or operation of the products manufactured ZAMEL Sp. z o.o.;
c) defectscausedbyanymodicationsoralterationsmadebytheBUYERoranythirdpartytothesoldproductsortothe
equipment required for the proper operation of the sold products;
d) defects caused by any force majeure event or another fortuitous event beyond any reasonable control of ZAMEL Sp. z o.o.
e) the power supply (batteries) included (if any) with the product as sold.
3. TheBUYERshallsubmitallwarrantyclaimsinwritingtotheoriginalresellerortoZAMELSp.zo.o.
4. ZAMEL Sp. z o.o. will examine each warranty claim as regulated by the applicable provisions of the Polish law.
5. If found valid by examination, the warranty claim will be processed by replacement of the defective product, its repair or a refund
of the price of purchase at the sole discretion of ZAMEL Sp. z o.o.
6. Thiswarrantyisonlyeffectiveonthefollowingterritories:RepublicofPoland.
7. NorightsoftheBUYERarisingfromthestatutoryorregulatorylawsconcerningimpliedwarrantyfordefectsofsoldgoodsare
limited, prejudiced or excluded by this warranty.
While an installed CO detector greatly improves indoor habitation safety, they are not 100% reliable in CO detection due
to the risks of detector failure, battery depletion and ambient effects. It is critical to periodically test the performance of
CO detectors (which is specied in this User Manual) and home heating equipment (including stoves, heaters, etc.) and
inspect all ventilation and ue gas exhaust systems for obstruction in the rooms monitored by CO detectors to minimise CO
concentrations that are hazardous to health and life.
Read the User Manual inside the packaging before installing the detector.
CTW-03_GB.indd 4-5
16.04.2020 07:41