Ziegler 3410 User manual

Ziegler mfm 3410Ziegler mfm 3410
Digital Multifunction Instrument
the user
Digital Volts, Amps & Frequency Indicator
Password Protection
Set Up Screens
3.2.5 Demand Reset
4.4 Auxiliary Supply
Connection Diagrams
The Instrument is a panel mounted 96x 96mm DIN Quadratic Digital
metering system for the measurement& display of basic electrical parameters like
AC Voltage, AC Current, Frequency, kVA, Ampere Demand and kVA Demand.
The instrument integrates accurate measurement technology (All
Voltage& Current measurements are True RMS upto 15th Harmonic) with3 line4
The instrument can be configured and
programmed at site for the following: PT
Primary, CT Primary, CT Secondary (5A or 1A)
The front panel has two push buttons through
may scroll through the
available measurement readings, reset the
demand readings and configure the product.
Units of measurement
Volts
Amps
Hz
kVA
AD
kVAD
Max AD
Max kVAD
Single Phase(1-PH)
& Operatin g Inst ructio ns
Measurement Reading Screens
3.2.1 Potential Transformer Primary value
3.2.2 Current Transformer Primary value
3.2.3 Current Transformer Secondary value
3.2.4 Demand Integration Time
EMC Installation Requirements
Case Dimensions and Panel Cut-out
4.6 Earth/ Ground Connections
1. Introduction
digits Ultra high brightness LED display.
which
Measure d Parameters
System Voltage
System Current
Frequency
System Apparent Power
Total System Current Demand
Total System kVA Demand
Maximum Total System Current Demand
Maximum Total System kVA Demand
TABL E 1:
Installati on
Section Conten ts
1. Introduction
2.
5.
3. Programming
3.1
3.2
4. Installation
4.1
4.2
4.3 Wiring
4.5 Fusing
6. Specification
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max k VAD
Up
Down
15000500_Rev_A/09/09 E1.R0
3. Programming
The following sections comprise step by step procedures for configuring the
instrument for individual user requirements.
To access the set-up screens press and hold the“
Key simultaneously for5 seconds. This will take the User into the Password
Protection Entry Stage (Section 3.1).
3.1. Passwor d Protection
Screen 3 : Apparent Power,
kVA demand and Max. kVA demand
Password protection can be enabled to prevent unauthorised access to set-up
Down” and “ Up”
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
SysV
SysA
Hz
x1000
Sy s k VA
x1000
AD
kVAD
x1000
Ma x AD
Ma x k VAD
2. MeasurementRead ing Screens
Screen 1: System screen
(System Voltage, System Current,
Frequency)
screens, by default password protection is not enabled.
Password protection is enabled by selectinga four digit number other than 0000,
setting a password of 0000 disables the password protection.
In normal operation the user is presented with one of the measurement reading
screens out of available screens. These screens may be scrolled through one ata
time in incremental order by pressing the “ Up key” and in decremental order
by pressing “ Down key”.
Enter Password, prompt for first digit.
(* Denotes that decimal point will be flashing).
Press the “ Down” key to scroll the value of the first digit
from0 through to 9, the value will wrap from 9 round to 0.
Press the “ Up” key to advance to Up digit.
In the special case where the Password is “0000” pressing
the “ Up” key when prompted for the first digit will
advance to the “Password Confirmed” screen.
Enter Password, first digit entered, prompt for second digit.
(* Denotes that decimal point will be flashing).
Press the “ Down” key to scroll the value of the second
digit from 0 through to 9, the value will wrap from9 round
to 0.
Press the “ Up” key to advance to Up digit.
SysV
SysA
Hz
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
SysV
SysA
Hz
x1000
Sy s k VA
x1000
AD
kVAD
x1000
Ma x AD
Ma x k VAD
Screen 2 : Ampere Demand
Max Ampere Demand
www.ziegler-instruments.com 1|6

Max AD
Max kVAD
Enter Password, fourth digit entered, awaiting
verification of the password.
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
New / Change Password
(*Decimal point indicates that this will be flashing).
Pressing the “ Down” key will scroll the value of the
first digit from0 through to 9, the value will wrap from9
round to 0.
Pressing the “ Up” key to advances the operation to
the Up digit and sets the first digit, in this case to “2”
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
Passwor d Incorr ect.
The unit has not accepted the
Password entered.
Pressing the" Down" key will return to
the Enter Password stage.
Pressing the “ Up” key exits the
Password menu and returns operation
to the measurement reading mode.
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
Password confirmed.
Pressing “ Down” key will advance to the “New/
change Password” entry stage.
Pressing the “ Up” key will advance to the Set up
screen. (See section 3.2).
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
Enter Password, third digit entered, prompt for fourth
digit.
(* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the fourth
digit from0 through to 9, the value will wrap from9
round to 0.
Press the “ Up” key to advance to verification of the
password.
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
Enter Password, second digit entered, prompt for third
digit.
(* Denotes that decimal point will be flashing).
Use the “ Down” key to scroll the value of the third
digit from0 through to 9, the value will wrap from9
round to 0.
Press the “ Up” key to advance to Up digit.
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
New/ Change Password, first digit entered, prompting for
second digit. (*Decimal point indicates that this will be
flashing).
Pressing the “ Down” key will scroll the value of the
second digit from0 through to 9, the value will wrap from
9 round to 0.
Pressing the “ Up” key advances the operation to the
Up digit and sets the second digit, in this case to “1”
SysV
SysA
Hz
x1000
Neutr alA
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
New/ Change Password, second digit entered,
prompting for third digit. (*decimal point indicates that
this will be flashing).
Pressing the “ Down” key will scroll the value of the
third digit from0 through to 9, the value will wrap from9
round to 0.
Pressing the “ Up” key advances the operation to
the Up digit and sets the third digit, in this case to “5”
3.2 Set Up Screens
3.2.1. Potential Transformer
The nominal full scale voltage which will be displayed as the Line to Neutral. This screen enables
the user to display the line to neutral voltage inclusive of any transformer ratios, the values displayed
represent the voltage in kilovolts (note the x1000 enunciator).
Primary Value
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
New Password confirmed.
Pressing the “ Down” key will return to the
“New/Change Password”.
Pressing the “ Up” key will advances to the Set up
screen.(see section 3.2).
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
New/ Change Password, third digit entered, prompting
for fourth digit. (* denotes that decimal point will be
flashing).
Pressing the “ Down” key will scroll the value of the
fourth digit from0 through to 9, the value will wrap from
9 round to 0.
Pressing the “ Up” key advances the operation to
the “New Password Confirmed” and sets the fourth digit,
in this case to “3”.
Pressing the “ Up” key accepts the present value
and advances to the “Current Transformer Primary
Value edit” menu. (See Section 3.2.2)
Pressing the “ Down” key will enter the “Potential
Transformer Primary Value Edit” mode.
Initially the “multiplier must be selected, pressing the“
Down” key will move the decimal point position to the
right until it reaches### .# after which it will return to
#.## #.
Pressing the “ Up” key accepts the present
multiplier (decimal point position) and advances to the
“Potential Transformer Digit Edit” mode.
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
www.ziegler-instruments.com 2|6

Note : the flashing decimal point indicates the cursor position, a steady decimal point will be present
to identify the scaling of the number until the cursor position coincides with the steady decimal point
When the least significant digit has been set pressing the “ Up” key will advance to the
Screen showing display of 0.120 kV i.e. 120 Volts indicating steady decimal point and cursor
The nominal Full Scale Current that will be displayed as the Line currents. This screen enables the
user to display the Line currents inclusive of any transformer ratios, the values displayed represent
Pressing the “ Up” key accepts the present value and advances to the Current Transformer
the presently displayed Potential Transformer Primary
Value together with the Current Transformer Primary
Value, previously set, would result in a maximum power
of greater than 360 MVA in which case the digit range
Pressing the “ Up” key accepts the present value
at the cursor position and advances the cursor to the
(* Denotes that decimal point will be flashing).
Potential Transformer Primary Value Confirmation
This screen will only appear following an edit of the
Potential Transformer Primary Value.
If the scaling is not correct, pressing the “ Down”
key will return to the “Potential Transformer Primary
Value Edit” stage with the digits flashing indicating
that the multiplier (decimal point position) should be
Pressing the “ Up” key sets the displayed value
and will advance to the Current Transformer Primary
Transformer Primary Value Edit” mode. This will scroll the
value of the most significant digit from 0 through to 9,
unless the presently displayed Current Transformer
Primary Value together with the Potential Transformer
Primary Value results ina maximum power of greater
than 360 MVA in which case the digit range will be
restricted, the value will wrap. Example: If primary value
of PT is set as 400kV (max value) then primary value of
Current is restricted to 0208A.
Pressing the “ Up” key will advance to the Up less
significant digit. (* Denotes that decimal point will be
Pressing the “ Down” key will enter the “Current
The “Maximum Power” restriction fo 360 MVA refers to 120% of nominal current and 120% of
When the least significant digit had been set, pressing the “ Up” key will advance to the
The minimum value allowed is 1, the value will be forced to 1 if the display contains zero when the
Current Transformer Primary Value Confirmation.
This screen will only appear following an edit of the
If the scaling is not correct, Pressing the “ Down” key
Edit
stage with the most significant digit highlighted (associated
decimal point flashing) and the bottom line of the display
Pressing the “ Up” key sets the displayed value and
will advance to the “Current Transformer Secondary Value
Edit” menu. (See section 3.2.3).
Current
Current Transformer Primary Value ”
Up less significant digit.
Value (See section 3.2.2.)
position. At this stage the decimal point will flash.
“Potential Transformer Primary Value Confirmation” stage.
flashing at the “hundreds of volts” position.
3.2.2. Curren t Prima ry ValueTransformer
Secondary Value (See section 3.2.3)
will be restricted.
selected.
flashing).
nominal voltage, i.e, 250 MVA nominal system power.
“Current Transformer Primary Value Confirmation” stage.
.
will return to the“
will be blanked.
Transformer Primary Value
for 4W
x1000
AD
kVAD
x1000
MaxAD
Max kVAD
x10 00
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
x1000
Sys kVA
x1000
AD
kVAD
x1000
MaxAD
Max kVAD
x1000
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
the Current in Amps.
“ Up” key is pressed.
Note: 0.120 kV i.e. 120V L-N
120V fpr 3W
L-L
SysV
SysA
Hz
SysV
SysA
Hz
SysV
SysA
Hz
SysA
Hz
Sys kVA
SysV
x1000
the most significant digit from 0 through to9 unless
Pressing the “ Down” key will scroll the value of
Potential Transformer Digit Edit
CT Secondary value confirmation
This screen will only appears following an edit of CT
secondary value.
If secondary value shown is not correct, pressing the
Down key will return to CT secondary edit stage by
blanking the bottom line of the display.
Pressing “ Up” key sets the displayed value and
will advance to Demand Integration time Edit menu.
(See section 3.2.4)
This screen is used to set the secondary value for
Current Transformer. Secondary value “5” for 5A or
“1” for 1A can be selected. Pressing “ Up” key
accepts the present value and advances to the
Demand Integration Time edit menu (See section
3.2.4).
Pressing the “ Down” key will enter the CT
Secondary value edit mode and scroll the value
through the values available.
Pressing the “ Up” key will advance to the CT
Secondary value confirmation.
3.2.4. Demand Integrati on Time
This screen is used to set the time taken for maximum demand readings. The value displayed
represents time in minutes. Integration periods of 8, 15, 20 or 30 minutes can be selected.
Pressing “ Up” key accepts the presents value
and advances to the “Demand Reset” menu. (See
section 3.2.5).
Pressing the “ Down” key will enter the “Demand
Integration Time Edit” mode and scroll the value
through the values available.
Pressing the “ Up” key advances to the “Demand
Integration Time Confirmation” menu.
As the unit advances to the Up screen the unit
demands are reset.
Demand Integration Time Confirmation.
This screen will only appear following an edit of the
Demand Integration Time.
If the time shown is not correct, pressing the“
Down” key will return to the “Demand Integration
Time Edit” stage by blanking the bottom line of the
display.
Pressing “ Up” key sets the displayed value and
will advance to the “Demand Reset” menu. (See
section 3.2.5)
SysV
SysA
Hz
SysV
SysA
Hz
SysV
SysA
Hz
SysV
SysA
Hz
x1000
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
x1000
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
x1000
Sys kVA
x1000
AD
kVAD
x1000
MaxAD
Max kVAD
x1000
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
Seco nd ary Value3.2.3. Cur rent Transf ormer
www.ziegler-instruments.com 3|6

The following screens allow the user to reset the Demand and Maximum Demand readings.
Note: Resetting the Demand will automatically reset the Maximum Demands (MaxAD and MaxkVAD).
Reset (None)
Pressing “ Up” key returns the product to
measurement reading screens.
Pressing the “ Down” key will enter the “Reset
Parameter Select” mode and scroll the “value”
through the parameters None and d wrapping back
to None.
Pressing the “ Up” key will not reset demand and
return to measurement reading screens.
Reset parameters select, (Reset Demands)
The user has scrolled through to the “d” (Demands)
value.
Pressing the “ Up” key will select the value and
advance to the “Reset Demands Confirmation” Mode.
Reset Demands Confirmation.
Pressing the “ Down” key will re-enter the “Reset
Parameter Select mode.
Pressing the “ Up” key resets the Demand
readings and returns the product to measurement
reading screens.
SysV
SysA
Hz
SysV
SysA
Hz
SysV
SysA
Hz
4. Install ation
Mountin g is by fou r side clam ps,slid e th e sid e clamp s throug h side
slot ti ll side clam p gets firm ly locke d in a groov e (Refer fig.) Considera tion
shoul d be give n to the space require d behin d the ins trumen t to allo w for bends
in the connectio n cables.
As the front of the enclosure conforms to IP54 it is protected from water spray
from all directions, additional protection to the panel may be obtained by the
use of an optional panel gasket. The terminals at the rear of the product
should be protected from liquids.
The instrument should be mounted in a reasonably stable ambient
temperature and where the operating temperature is within the range
0
-10 to 55 C. Vibration should be kept to a minimum and the product should
not be mounted where it will be subjected to excessive direct sunlight.
SLIDE IN THIS DIRECTION AND LOCK
PANEL
Front
2.
Vol tage s dang erous to human lif e are pres ent at som e of the term inal
co nnectio ns of this unit . En sure that all su pplie s are de -energise d before
att emptin g any conne cti on or disco nnecti on.
3.
Thes e prod ucts do not ha ve interna l fus es th erefor e externa l fuses must
be used to ens ure safe ty und er faul t condi tio ns.
4.1 EMC Installa tion
This product has been designed to meet the certification of the EU directives
when installed to a good code of practice for EMC in industrial environments,
e.g.
1. Screened output and low signal input leads or have provision for fitting
RF suppression components, such as ferrite absorbers, line filters etc., in
the event that RF fields cause problems.
Note:I t is good practice to install sensitive electronic instruments that are
performing critical functions, in EMC enclosures that protect against electrical
interference which could cause a disturbance in function.
2. Avoid routing leads alongside cables and products that are, or could be,a
source of interference.
3. To protect the product against permanent damage, surge transients must
be limited to 2kV pk. It is good EMC practice to suppress differential
surges to 2kV at the source. The unit has been designed to automatically
recover in the event of a high level of transients. In extreme
circumstances it may be necessary to temporarily disconnect the
auxiliary supply fora period of greater than5 seconds to restore correct
operation.
4. ESD precautions must be taken at all times when handling this product.
4.2 Case Dime nsion
The Current inputs of these products are designed for connection in to
systems via Current Transformers only, where one side is grounded.
4.4 Auxilia ry Sup ply
Meter should ideally be powered from a dedicated supply, however
it may be powered from the signal source, provided the source remains within
the limits of the chosen auxiliary voltage.
3.78”
96mm
FRONT DISPLAY
AREA
3.78”
96mm
4.3 Wiring
Input connections are made directly to screw-type terminals with indirect
wire pressure. Numbering is clearly marked in the plastic moulding. Choice of
cable should meet local regulations. Terminal for both Current and Voltage
inputs will accept upto 3mm x 2 diameter cables.
2
x1000
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
x10 00
Sys kVA
x1000
AD
kVAD
x1000
Ma x AD
Max kVAD
x10 00
Sys kVA
x1000
AD
kVAD
x1000
Max AD
Max kVAD
Note: It is reco mmended to use wir e wit h lug for
connectio n wit h mete r.
Requirements
and Panel Cut Out
3.15”
80mm
MAX PANEL THICKNESS 0.18”,5mm
PANEL CUTOUT
3.62”
92mm
3.62”
92mm
a qualifi ed engi neer, abi din g by any local regula tio ns.
In th e intere st of safet y and fu nct ional ity this pro duc t mus t be installe d by
1.
Caution
3.2.5. Demand Reset
www.ziegler-instruments.com 4|6

Disp lay
3 line 4 digits . Digit height 11mm
Approx.1 second
LED
Update
Controls
Two push buttonsUser Interface
Standards
IEC 61326
10V/m min-Level 3 industrial low level
electromagnetic radiation environment
IEC 61000-4-3.
IEC 61010-1 , Year 2001
EMC Immunity
Safety
Isolat ion
2.2 kV RMS 50 Hz for1 minute
between all electrical circuits
Dielectric voltage withstand
test between circuits and
accessible surfaces
Std. Values upto 4kA (1 or 5 Amp secondaries)
+20%/ -15 % of Rated Value
Hz
It is recommended that all voltage lines are fitted with1 amp HRC fuses.
For safety reasons, CT secondary connections should be grounded in
1-PHASE 2-WIRE UNBALANCED LOAD
DIGITAL METERING SYSTEM
58
11 1 34679
13 14
LN
AUX
SUPPLY
P1 S1
L
O
A
D
to 277VL-N
120% of Rated Value
Rated Value
application repeated 10times
at 10s intervals)
approx. perphase
1A / 5A AC rms programmable at site
Rated Value
approx. perphase
20 x (1s application repeatedRated Value
5 times at5 min. intervals)
5 .. 120% of Rated Value
5 .. 120% of Rated Value
40 .. 70 Hz
Accuracy
Voltage
Current
+ 0.5% of range( 50 .... 100% of Rated Value)
+0.5% of range ( 10 .... 100% of Rated Value)
Frequency 0.15% of mid frequency
System Apparent power (VA)
Temperature Coefficient 0
0.025% / C for Voltage( 50 ... 120% of Rated Value)
+ 0.5% of range ( 10 .... 100% of Rated Value)
0
(For range of use 0...50 C)Rated Value
Error change due to variation of an
influence quantity.
2* Error allowed for the reference
condition applied in the test.
Referenc e condition s for Accuracy
0
23 C 2C+
50 or 60 Hz 2%+
Sinusoidal (distortion factor 0.005)
Rated Value 1%+
Reference temperature
Input frequency
Input waveform
Auxiliary supply voltage
Auxiliary supply frequency
Nomina l rang e of use of influenc e quantitie s for measurands
50 .. 120% of Rated Value
10 .. 120% of Rated Value
Rated Value +1 0%
0
0to 50C
Rated Value 10%+
Rated Value +1 0%
Voltage
Current
Input frequency
Temperature
Auxiliary supply voltage
Auxiliary supply frequency
0
Rated Value 1%+
0
0.05% /C for Current( 10 ... 120% of Rated Value)
SystemCTprimaryvalues
Auxiliary
Standard nominal a.c.supply 110V AC
voltages
a.c.supplyvoltagetolerance
a.c.supplyfrequ ency range 45to66
a.c.supplyburden 4VA
4.5 Fusing
4.6 Earth/Gro und Connections
accordance with local regulations.
5 Connection Diagrams
2
L1
L2
L3
N
6. Specification
Syst em
Single Phase
Inpu ts
Nominal inputvoltage
Maxconti nuous input
voltage
Maxshortdurati on input
voltage
Nominal inputvoltageburden
57.7V L-N
2x
(1s
0.2VA
Nominal inputcurrent
Maxconti nuous inputcurrent 120%of
Nominal inputcurre nt burden 0.6VA
Max sho rt duratio n curren t input
Operatin g Measurin g Ranges
Voltage
Current
Frequency
230V AC
380V AC
www.ziegler-instruments.com 5|6

Environmental
0
-10 to 55 C
0
-20 to +65 C
0..90%RH
3 minute(minimum)
15g in 3 planes
10 .. 55 Hz, 0.15mm amplitude
IP 54 as per IEC 60529
Operating temperature
Storage temperature
Relative humidity
Warm up time
Shock
Vibration
Enclosure (front only)
Enclosure
96mm x 96mm DIN Quadratic
Polycarbonate Housing,
<80mm
0.620 kg Approx.
Style
Material
Terminals
Depth
Weight
Screw-type terminals
Self extinguish & non dripping as per UL 94 V-0
www.ziegler-instruments.com 6|6
ZIEGLER INSTRUMENTS
Schnepfenreuther Weg 6, D-90425 Nürnberg, Germany.
(+49)(911) 38 492 45
TEL.
(+49)(911) 32 26 212
FAX.
www.ziegler-instruments.com
E-MAIL
WEBSITE
in
Germany
made
Table of contents
Other Ziegler Measuring Instrument manuals