EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
SDM630-MT V2
DIN Rail Smart Meter for Single and Three Phase Electrical Systems
Measures 4 Tariffs kWh/kvarh/time
and Kvarh, KW, Kvar, KVA, P, F, PF, dmd, V, A etc.
Bi-directional measurement IMP & EXP
Two pulse outputs
RS485 Modbus
Din rail mounting 35mm
100A direct connection
Better than Class 1 / B accuracy
USER MANUAL
2016 V1.1
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 1 -
Introduction
The SDM630-MT V2 is a multifunction meter that supports max 4 tariffs and 10 time segments,
the tariffs and segments can be set via RS485 communication. The unit measures and displays the
characteristics of single phase two wires (1p2w), three phase three wires (3p3w,) and three phase
four wires(3p4w) supplies, including voltage, frequency, current, power ,active and reactive
energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand
current can be measured over preset periods of up to 60 minutes. In order to measure energy,
the unit requires voltage and current inputs in addition to the supply required to power the
product.
SDM630-MT V2 supports max. 100A direct connection, saves the cost and avoid the trouble to
connect external CTs, giving the unit a cost-effective and easy operation. Built-in interfaces
provides pulse and RS485 Modbus RTU outputs. Configuration is password protected.
Unit Characteristics
The Unit can measure and display:
Line voltage and THD% (total harmonic distortion) of all phases
Line Frequency
Currents, Current demands and current THD% of all phases
Power, maximum power demand and power factor
Active energy imported and exported
Reactive energy imported and exported
The unit has password-protected set-up screens for:
Changing password
Supply system selection 1p2w, 3p3w,3p4w
Demand Interval Time(DIT)
Reset for demand measurements
Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
RS485 Serial–Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port.
Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant
of pulse output 2 for active energy is 400imp/kWh (unconfigurable), its width is fixed at 100ms.
The default constant of configurable pulse output 1 is 400imp/kWh, default pulse width is
100ms.The configurable pulse output 1 can be set from the set-up menu.
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 2 -
Start-up Screens
1
The first screen lights up all display
segments and can be used as a display
check
2
The second screen indicates the
firmware installed in the unit and its
build number.
3
The interface performs a self-test and
indicates the result if the test passes.
After a short delay, the screen will display active energy measurements.
Measurements
The buttons operate as follows:
1
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back” button.
2
Select the Frequency and Power factor display
screens
In Set-up Mode, this is the “Up” button
3
Select the Power display screens
In Set-up Mode, this is the “Down” button
4
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right” button
Voltage and Current
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 3 -
Each successive pressing of the button selects a new range:
1-1
Phase to neutral voltages(3p4w)
1-2
Phase to neutral voltages(3p3w)
2
Current on each phase
3-1
Phase to neutral voltage THD%(3p4w)
3-2
Phase to neutral voltage THD%(3p3w)
4
Current THD% for each phase
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 4 -
Frequency and Power factor and Demand
Each successive pressing of the button selects a new range:
1
Frequency and Power Factor (total)
2
Power Factor of each phase
3
Maximum Power Demand
4
Maximum Current Demand
Power
Each successive pressing of the button select a new range:
1
Instantaneous Active Power in kW
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 5 -
2
Instantaneous Reactive Power in kVAr
3
Instantaneous Volt-amps in KVA
4
Total kW, kVArh, kVA
Energy Measurements
Each successive pressing of the button selects a new range:
1-1
Imported active energy in kWh
1-2
Exported active energy in kWh
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 6 -
2-1
Tariff 1 Active energy
2-2
Tariff 2 Active energy
2-3
Tariff 3 active energy
2-4
Tariff 4 active energy
2-5
Total active energy in kWh
3-1
Imported reactive energy in kVArh
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 7 -
3-2
Exported reactive energy in kVArh
4-1
Tariff 1 reactive energy
4-2
Tariff 2 reactive energy
4-3
Tariff 3 reactive energy
4-4
Tariff 4 reactive energy
4-5
Total reactive energy in kVArh
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 8 -
5
Date
Year/month/day
Example:1st.Jan.2000
6
Time
Hour/minute/second
Example:00:02:16
Set-up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing. If an incorrect password is entered, the display will show: Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
Set-up Entry Methods
Some menu items, such as password, require a four-digit number entry while others, such as
supply system, require selection from a number of menu options.
Menu Option Selection
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 9 -
1) Use the and buttons to select the required item from the menu. Selection
does not roll over between bottom and top of list
2) Press to confirm your selection
3) If an item flashes, then it can be adjusted by the and buttons. If not, there
maybe a further layer.
4) Having selected an option from the current layer, press to confirm your selection.
The SET indicator will appear.
5) Having completed a parameter setting, press to return to a higher menu level. The
SET indicator will be removed and you will be able to use the and buttons for
further menu selection.
6) On completion of all set-up, press repeatedly until the measurement screen is
restored.
Number Entry Procedure
When setting up the unit, some screens require the entering of a number. In particular, on entry
to the setting up section, a password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1) The current digit to be set flashes and is set using the and buttons
2) Press to confirm each digit setting. The SET indicator appears after the last digit has
been set.
3) After setting the last digit, press to exit the number setting routine. The SET indicator
will be removed.
Change password
1
Use the and to
choose the change password option
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 10 -
2-1
Press the to enter the change
password routine. The new password
screen will appear with the first digit
flashing
2-2
Use and to set the
first digit and press to confirm
your selection. The next digit will flash.
2-3
Repeat the procedure for the remaining
three digits
2-4
After setting the last digit, SET will show.
Press to exit the number setting routine and return to the Set-up menu. SET will be
removed
DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for
maximum demand measurement. The options are: 0, 5, 8, 10, 15, 20, 30, 60 minutes
1
From the set-up menu, use and
buttons to select the DIT
option. The screen will show the
currently selected integration time.
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 11 -
2-1
Press to enter the selection
routine.
The current time interval will flash
2-2
Use and buttons to
select the time required.
2-3
Press to confirm the selection.
SET indicator will appear.
Press to exit the DIT selection routine and return to the menu.
Backlit set-up
1
The backlit lasting time is settable
Default lasting time is 60minutes
For example, if it’s set as 5, the backlit
will be off in 5minutes from the last
time operation on the meter.
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 12 -
2
Press to enter the selection
routine. The current time interval will
flash
The options can be:
0(always on),5,10,30,60,120minutes
Use and buttons to select the time required. Press to confirm the
set-up,
Supply System
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use
and buttons to select the
System option. The screen will show the
currently selected power supply.
2-1
Press to enter the selection
routine. The current selection will flash
2-2
Use and buttons to
select the required system option:
1P2(W),3P3(W) ,3P4(W)
2-3
Press to confirm the selection.
SET indicator will appear.
Press to exit the system selection routine and return to the menu. SET will disappear
and you will be returned to the main Set-up Menu
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 13 -
Pulse output
This option allows you to configure the pulse output 1. The output can be set to provide a pulse
for a defined amount of energy active or reactive.
Use this section to set up the pulse output for:
Total kWh/ Total kVArh
Import kWh/Export kWh
Import KVArh/Export KVArh
1
From the Set-up menu, use
and buttons to select the
Pulse output option.
2-1
Press to enter the selection
routine. The unit symbol will flash.
2-2
Use and buttons to
choose kWh or kVArh.
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
dFt/0.01/0.1/1/10/100kWh/kVArh.
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 14 -
(It shows 1 impulse = 10kWh/kVArh)
1
From the Set-up menu, use
and buttons to select the Pulse
Rate option.
2
Press to enter the selection
routine. The current setting will flash.
Note: When it’s dFt,
it means 2.5Wh/VArh
Use and buttons to choose pulse rate. On completion of the entry
procedure, press to confirm the setting and press to return to the main set
up menu.
Pulse Duration
The energy monitored can be active or reactive and the pulse width can be selected as
200, 100(default) or 60ms.
(It shows pulse width of 200ms)
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 15 -
1-1
From the Set-up menu, use
and buttons to select the
Pulse width option.
1-2
Press to enter the selection
routine. The current setting will flash.
Use and buttons to choose pulse width. On Completion of the entry
procedure, press to confirm the setting and press to return to the main set
up menu.
Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus
RTU, parameters are selected from Front panel.
RS485 Address
(The range is from 001 to 247)
1
From the Set-up menu, use and
buttons to select the Address ID
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 16 -
2-1
Press button to enter the
selection routine. The current setting will
be flashing.
2-2
Use and buttons to
choose Modbus Address(001 to 247)
On completion of the entry procedure, press button to confirm the setting and press
button to return the main set-up menu.
Baud Rate
1
From the Set-up menu, use and
buttons to select the Baud Rate
option.
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k,
38.4k
On completion of the entry procedure, press to confirm the setting and press
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 17 -
to return to the main set up menu.
Parity
1
From the Set-up menu, use and
buttons to select the Parity
option.
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Parity (EVEN / ODD / NONE)
On Completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Stop bits
1
From the Set-up menu, use and
buttons to select the Stop Bit
option.
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 18 -
2-1
Press to enter the selection
routine. The current setting will flash.
2-2
Use and buttons to
choose Stop Bit (2 or 1)
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
Note: Default is 1, and only when the parity is NONE that the stop bit can be changed to 2.
CLR
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use and
buttons to select the reset
option.
2
Press to enter the selection
routine. The MD will flash.
Press to confirm the setting and press to return to the main set up menu.
Specifications
Measured Parameters
The unit can monitor and display the following parameters of a single phase two wire(1p2w),
three phase three wire(3p3w) or four phase four wire(3p4w) supply.
EASTRON SDM630-MT V2 User Manual
Address: No.1369 Chengnan Road, Jiaxing, Zhejiang, 314001, China.
Tel: 0086-573-83698881/83698882 Fax: 0086-573-83698883 Web: www.eastron.com.cn
- 19 -
Voltage and Current
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies)
Voltages between phases 173 to 500V a.c. (3p supplies only)
Basic current (Ib): 10A
Max current : 100A
Min. Current: 5% of Ib
Starting current: 0.4% of Ib
Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies)
Percentage voltage THD% between phases (three phase supplies only)
Current THD% for each phase
Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Power 0 to 99999 W
Reactive Power 0 to 99999 VAr
Volt-amps 0 to 99999 VA
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for 3p4w supply only)
Energy Measurements
Imported active energy 0 to 999999.99 kWh
Exported active energy 0 to 999999.99 kWh
Imported reactive energy 0 to 999999.99 kVArh
Exported reactive energy 0 to 999999.99 kVArh
Total active energy 0 to 999999.99 kWh
Total reactive energy 0 to 999999.99 kVArh
Measured Inputs
Voltage inputs through 4-way fixed connector with 25mm²stranded wire capacity. single phase
two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) unbalanced. Line
frequency measured from L1 voltage or L3 voltage.
Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
Reactive power (VAr) ±1% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) ±1% of range maximum

Other Eastron Measuring Instrument manuals

Eastron SDM630-Mbus V2 User manual

Eastron

Eastron SDM630-Mbus V2 User manual

Eastron SDM320Y User manual

Eastron

Eastron SDM320Y User manual

Eastron SDM630-Mbus V2 User manual

Eastron

Eastron SDM630-Mbus V2 User manual

Eastron SDM72DM User manual

Eastron

Eastron SDM72DM User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM530-Modbus User manual

Eastron

Eastron SDM530-Modbus User manual

Eastron SMART X96-RC User manual

Eastron

Eastron SMART X96-RC User manual

Eastron SDM120 Series User manual

Eastron

Eastron SDM120 Series User manual

Eastron SDM630MCT-RC User manual

Eastron

Eastron SDM630MCT-RC User manual

Eastron SDM630MCT-RJV-333mV User manual

Eastron

Eastron SDM630MCT-RJV-333mV User manual

Eastron DCM230 User manual

Eastron

Eastron DCM230 User manual

Eastron SDM530D User manual

Eastron

Eastron SDM530D User manual

Eastron SDM220-MBUS User manual

Eastron

Eastron SDM220-MBUS User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Eastron SDM72DM User manual

Eastron

Eastron SDM72DM User manual

Eastron SDM630-Modbus MID V2 User manual

Eastron

Eastron SDM630-Modbus MID V2 User manual

Eastron SDM630-EV User manual

Eastron

Eastron SDM630-EV User manual

Eastron SDM630MCT-MOD-MID User manual

Eastron

Eastron SDM630MCT-MOD-MID User manual

Eastron SDM230-Modbus User manual

Eastron

Eastron SDM230-Modbus User manual

Eastron SDM230-LoRaWAN User manual

Eastron

Eastron SDM230-LoRaWAN User manual

Eastron SDM230 Series User manual

Eastron

Eastron SDM230 Series User manual

Eastron SDM120 Modbus User manual

Eastron

Eastron SDM120 Modbus User manual

Eastron SDM72CT-M User manual

Eastron

Eastron SDM72CT-M User manual

Eastron SDM630MCT-LoRaWAN User manual

Eastron

Eastron SDM630MCT-LoRaWAN User manual

Popular Measuring Instrument manuals by other brands

Sigma 980 Operating and maintenance manual

Sigma

Sigma 980 Operating and maintenance manual

SICK WTF9-3 operating instructions

SICK

SICK WTF9-3 operating instructions

Cannon CAV-2100 installation guide

Cannon

Cannon CAV-2100 installation guide

Hitachi UG 50Y instruction manual

Hitachi

Hitachi UG 50Y instruction manual

Levitronix LEVIFLOW LFSC-D Series user manual

Levitronix

Levitronix LEVIFLOW LFSC-D Series user manual

ETAS XETK-S16.0 user guide

ETAS

ETAS XETK-S16.0 user guide

Raycus RFL-C4000S-CE user guide

Raycus

Raycus RFL-C4000S-CE user guide

socomec COUNTIS E23 quick start

socomec

socomec COUNTIS E23 quick start

Stanley CL2i user manual

Stanley

Stanley CL2i user manual

Analog Devices ADXL180 iMEMS manual

Analog Devices

Analog Devices ADXL180 iMEMS manual

Komshine KPN-35 PON user manual

Komshine

Komshine KPN-35 PON user manual

Flexim FLUXUS F401 Operating	 instruction

Flexim

Flexim FLUXUS F401 Operating instruction

MEWOI 7800 user manual

MEWOI

MEWOI 7800 user manual

MULTISPAN PI 38 manual

MULTISPAN

MULTISPAN PI 38 manual

KROHNE OPTIWAVE 5200 C/F Handbook

KROHNE

KROHNE OPTIWAVE 5200 C/F Handbook

E Instruments BTU900 quick guide

E Instruments

E Instruments BTU900 quick guide

Hanna Instruments HI 93102 instruction manual

Hanna Instruments

Hanna Instruments HI 93102 instruction manual

KYORITSU KEW2040 instruction manual

KYORITSU

KYORITSU KEW2040 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.