3Assembly
3.1 Assembly
The TMP tripping device MS 220 DA - MCB 220 PTC Thermistor Option B is intended to be used in Danfoss Automation Drives series VLT®. PTC-thermistor
sensors are connected directly to the terminals T1, T2. The lines of Safe Stop T37 and Logic Out are to be routed separately.
Attention: Routed lines must keep enough distance to sensor lines and other mainstream lines.
3.2 Putting into Operation
After installation and before first operation, the correct function of the TMP tripping device has to be tested by simulation of the sensor resistance at
terminals T1, T2.
This test must also be done after modifications in the installation.
This test can additionally be done with maintenance services:
Short circuit test: resistance 20 Ωin parallel to sensor terminals T1, T2
Line interruption test: disconnect sensor line at terminal T1 or T2
Temperature test: increase resistance 50…1500 Ωup to 4000 Ω
The tripping function will be displayed on the drive display and must be reseted manually.
Please notice the admissible ambient conditions > Technical data.
Atteention! The TMP tripping device MS 220 DA was designed for Class A. The use of this product in home applications can cause radio
frequency distortions.
3.3 Maintenance and Repair
The devices are maintenance-free. Only the manufacturer may accomplish repairs. We recommend an examination within the regular maintenance periods
of the plant, in which the equipment is installed.
3.4 Warranty
The guarantee presupposes the observance of this Operating Instruction (safety and start-up instructions).
3.5 Safety Integrity Level (EN 61508)
The safety function of the safety equipment
• achieves SIL 1 within a proof test interval of 3 years
• achieves SIL 2 within a proof test interval of 2 years.
The safety function fulfils the recommendations of category 2 according ISO 13849-1:1999 (EN 954-1:1996). More safety-related parameters -> Technical
data
3.6 Troubleshooting
• The resistance within the sensor circuit must have a value 50 Ω< R < 1500 Ω. The voltage at terminals T1, T2 must be < 2.5 VDC when PTC-
thermistor sensors are connected and the temperature is below TNF.
• The TMP tripping device must shut down when the sensor circuit is open. The voltage at terminals T1, T2 must be < 9 VDC.
Motor Protection MS 220 DA 3 Assembly
MG33V102 - VLT®is a regisered Danfoss trademark
7