manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Ziton
  6. •
  7. Marine Equipment
  8. •
  9. Ziton ZP755W-2R Assembly instructions

Ziton ZP755W-2R Assembly instructions

© 2014 UTC Fire & Security. All rights reserved. 1 / 4 P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14
ZP755W-2R Addressable Weatherproof Sounder
Installation Sheet
Description
The ZP755W-2R is an addressable, weatherproof sounder,
designed for use on Ziton addressable fire detection and alarm
systems. The sounder is rated for outdoor, wet applications. It
provides audible warnings from a single, addressable, loop-
wired unit.
The device includes a volume control, an address-setting
switch, programmable tone settings, and a pair of jumpers to
select the operating power — from the analogue addressable
loop or an external supply.
Installation
To install the device follow these general steps.
1. Wire the PCB.
2. Set the operating power.
3. Set the address.
4. Set the operating mode.
5. Set the tone.
6. Set the volume.
7. Mount the sounder.
The details of each step are given below.
Wiring the PCB
Connect the loop wiring and the optional external power cables
to the terminals on the PCB as shown Figure 1.
Figure 1: Connecting the wiring
3072-013072-01
24 VOLTS 0 VOLTS SCREEN (+VE LOOP)(_VE LOOP)
1
12
3
4
5
1. PCB
2. Six-way terminal connector
3. Header socket
4. Connect to sounder
5. External power
Setting the operating power
The sounder includes a pair of power selection jumpers, J1
and J2. To select the source of the sounder operating power,
position the jumpers as shown in Figure 2.
Figure 2: Power selection jumper configuration
J1 J1J2 J2
21
1. Loop powered 2. External 24 VDC
Note: When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the sounders on the
same loop.
Setting the address
The sounder includes a seven-segment DIP switch (SW1) for
assigning device addresses. Each switch segment has a
decimal value as shown in Figure 3. The address is the sum of
all the switch segments in the ON position. The switch is used
to set the device address in binary code. The switch may be
set to represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
2 of 4 P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14
Figure 3: Address switch setting
Mode and tone settings
The sounder includes a seven-segment DIP switch (SW2)
used to select operating mode, device mode, and tone. See
Figure 4.
Figure 4: Mode of operation switch settings
1
2
34
5
1. Power selection jumpers
2. SW2 configuration switch
3. Tone setting
4. Device mode
5. Operating mode
Setting the operating mode
The device operates as a dedicated (stand-alone) sounder with
its own unique loop address when SW2-7 is set to ON.
To configure operation as a stand-alone sounder:
1. Set SW2-7 to ON.
2. Navigate to the following menu to tag the sounders as
SAB:
ZP3 Panel Menu/Setup/Sounders/SAB/Add SAB
The Planner can also be used.
3. To map an alert-to-evac function, make the first input type
a fast flash input.
The sounder will sound the alert tone in response to a fast
flash input or an evac tone when the input configured as
steady is triggered, overriding the alert tone.
Setting the device mode
SW2-6 selects whether the loop sounder operates in ZP755
mode or in ZP754 emulation mode as described in Table 1.
Table 1: SW2-6 mode selection switch
Mode SW2-6 Output signal Requirement
ZP755 OFF User-selectable two-
tone operation and
full monitoring
ZP3 software
v1.18 or later
ZP754
emulation
ON Two fixed tones ZP5 panels or
ZP3 panels with
legacy software
Setting the tone
Two different tones can be programmed to operate from the
panel. In ZP755 mode these tones are selected using SW2-1,
SW2-2, and SW2-3. Refer to Table 2.
Note: In the ZP panel I/O mapping menu, outputs are
programmed as "steady" or "flashing." The link to the table
below is as follows:
• Tone A = Panel setting "fast flash/slow flash.”
• Tone B = Panel setting "steady.”
© 2014 UTC Fire & Security. All rights reserved. 3 / 4 P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14
Table 2: Tone settings
SW2-6 device mode
switch setting Device mode SW2 switch setting
-1 -2 -3 Mapping input type
Fast flash Steady
Tone type
Tone A primary/alert Tone B secondary/evac
OFF ZP755 0 Intermittent Continuous
OFF ZP755 1 Continuous Intermittent
OFF ZP755 2 Continuous Two-tone
OFF ZP755 3 Two-tone Continuous
OFF ZP755 4 Two-tone Intermittent
OFF ZP755 5 Intermittent Two-tone
OFF ZP755 6 Not used
ON ZP754 7 Intermittent Continuous
Setting the volume
The sounder has a volume control potentiometer to adjust the
volume. Refer to Figure 5.
WARNING: To conform to EN 54 Part 3 sound output levels,
the volume control pot must be set to the full clockwise
position. If the volume is adjusted for any reason, it must be
returned to the full clockwise position.
Figure 5: Volume control
1
2
3
3050-01
123
4
1. Tone Select
2. SW2-6 on
3. SW2-6 off
4. Volume control
Mounting the sounder
To mount the sounder:
1. Insert four M4 × 25 mm screws through the PCB mounting
holes, and then secure to the backbox surface. See
Figure 6.
2. Install the sound output assembly into the backbox, and
then secure using mounting screws.
Figure 6: Mounting
3064-01
1
2
3
4
1. M4 × 25 mm screws
2. Mounting screws
3. Sound output assembly
4. PCB
Sounders per loop
The sounder can be powered directly from the loop of a ZP3
panel. Use Table 3, in conjunction with Figure 7, to determine
the quantity of detectors and sounders that can be connected
to a two-core shielded loop.
Figure 7: Detector/sounders per loop
4 of 4 P/N 501-1786ZE-1-08 • REV 08 • ISS 30JAN14
A. Cable length panel to first sounder
B. Cable length first to last sounder
C. Cable length last sounder to panel
1. Detectors and Sounders
Table 3: Maximum detectors and sounders per loop
A B C Quantity allowed [1]
10 m 980 m 10 m 50 detectors and 50 sounders
63 detectors and 42 sounder
100 m 800 m 100 m 45 detectors and 45 sounder
63 detectors and 40 sounder
200 m 600 m 200 m 40 detectors and 40 sounder
63 detectors and 37 sounder
300 m 400 m 300 m 37 detectors and 37 sounder
63 detectors and 35 sounder
[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm²
Specifications
Operating voltage
External supply
Loop supply, ZP protocol
18 to 30 VDC
19.5 to 20.5 V pulsed, max. 4 V line
loss
Current (line powered)
Quiescent (RMS)
Alarm (RMS)
Alarm (excluding device
address)
Alarm (at device address)
820 μA
6.4 mA
16.3 mA max. average
24.65 mA max.
Current (externally powered)
Quiescent (RMS)
Alarm (RMS)
Maximum number
470 μA
500 μA
50 per 1 km loop (subject to cable
size and sounder spacing)
Sound output
Tone 1
Tone 2
Tone 3
90 dBA (forward sound dispersion)
Continuous 980 Hz.
Intermittent 980 Hz. (0.5 sec on/off)
Two-tone warble, 980/670 Hz.
Sound distribution Narrow
CNPP anechoic sound levels See Figure 8
Monitoring
ZP loop
Sound output level
Open and short circuit fault
Self test facility
Compatibility Ziton analogue addressable systems
Addressing method 7-segment DIP switch
Mounting Surface
Wiring Two-core shielded loop
Construction
Material
Colour
Weight
Dimensions (Ø × D)
Moulded thermoplastic
Red
610 g
120 × 150 mm
Operating environment
Temperature
Relative humidity
−25 to +70°C
10 to 95%, noncondensing
Storage temperature −25 to +70°C
Figure 8: CNPP anechoic sound levels
165
O
105
O
75
O
45
O
15
O
135
O
dBA 70 75 80 8570758085
3507-01
ZP755W
90 90
Regulatory information
This section includes both regulatory information and a
summary on the declared performance according to the
Construction Products Regulation 305/2011. For detailed
information refer to the product Declaration of Performance.
Certification
Certification body 0370
Declaration of
Performance number
360-5201-0599
Year of first CE marking 14
Product Identification ZP755W-2R
Intended use See DoP point 3
Essential characteristics See DoP point 9
Manufacturer Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing
representative:
UTC Fire & Security B.V.
Kelvinstraat 7, 6003 DH Weert,
Netherlands
European Union directives 1999/5/EC (R&TTE directive): Hereby,
UTC Fire & Security declares that this
device is in compliance with the essential
requirements and other relevant
provisions of Directive 1999/5/EC.
2002/96/EC (WEEE directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.

Other Ziton Marine Equipment manuals

Ziton ZP755WV-2R Assembly instructions

Ziton

Ziton ZP755WV-2R Assembly instructions

Ziton ZP755HA-2P Assembly instructions

Ziton

Ziton ZP755HA-2P Assembly instructions

Ziton ZP755B-2 Assembly instructions

Ziton

Ziton ZP755B-2 Assembly instructions

Ziton ZP755HA-2 Assembly instructions

Ziton

Ziton ZP755HA-2 Assembly instructions

Ziton ZP755R-2 Assembly instructions

Ziton

Ziton ZP755R-2 Assembly instructions

Ziton ZP755W-2R Assembly instructions

Ziton

Ziton ZP755W-2R Assembly instructions

Ziton ZP755BV-4 Assembly instructions

Ziton

Ziton ZP755BV-4 Assembly instructions

Popular Marine Equipment manuals by other brands

COBHAM SAILOR MF 63 Series user manual

COBHAM

COBHAM SAILOR MF 63 Series user manual

Simrad Navico WP10 manual

Simrad

Simrad Navico WP10 manual

JRC JFC-180BB quick reference

JRC

JRC JFC-180BB quick reference

NKE 90-60-495 user manual

NKE

NKE 90-60-495 user manual

Simrad AP70 Operator's manual

Simrad

Simrad AP70 Operator's manual

Ventus BOW PRO B Series installation instructions

Ventus

Ventus BOW PRO B Series installation instructions

Danelec DM800 installation manual

Danelec

Danelec DM800 installation manual

BEKA BR385 instruction sheet

BEKA

BEKA BR385 instruction sheet

Taco Marine GS-312 Installation instruction guide

Taco Marine

Taco Marine GS-312 Installation instruction guide

ProFurl NC 32 installation manual

ProFurl

ProFurl NC 32 installation manual

Fusion Apollo 770 Quick start manual

Fusion

Fusion Apollo 770 Quick start manual

Navman S100 user manual

Navman

Navman S100 user manual

Xintex G-1BB-R Owner's Manual & Installation Instructions

Xintex

Xintex G-1BB-R Owner's Manual & Installation Instructions

Raymarine i60 wind Installation & operation instructions

Raymarine

Raymarine i60 wind Installation & operation instructions

Furuno FCV-585 Operator's manual

Furuno

Furuno FCV-585 Operator's manual

Taco Marine Neptune III Installation instruction guide

Taco Marine

Taco Marine Neptune III Installation instruction guide

Dual MXDM66 Installation & owner's manual

Dual

Dual MXDM66 Installation & owner's manual

Furuno NAVpilot-711C installation manual

Furuno

Furuno NAVpilot-711C installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.