Ziton ZP755V Assembly instructions

© 2022 Carrier. All rights reserved. 1 / 4 P/N 501-1782ZE-1-09 • ISS 30MAY22
ZP755V Addressable Visual Indicator
Installation Sheet
Description
The ZP755V is an addressable visual indicator designed for
use in Ziton addressable fire detection and alarm systems. The
visual indicator provides visual warnings from a single,
addressable, loop-wired unit.
Note: The visual indicator of this product does not comply with
EN 54-23 and must not be used in fire alarm installations
where fire notification beacons are required.
The visual indicator includes an address-setting switch and a
pair of jumpers to select the operating power — from the
addressable loop or an external supply. See Table 1 for a list
of models.
Table 1: Models
Model
number Description
ZP755V
-W
ZP755V
-P
Visual indicator, White
Visual indicator, Polar white
ZP7
-SSB-W
ZP7
-SSB-P
Base, White
Base, Polar white
Installation
To install the visual indicator;
1. Wire the base
2. Set the operating power
3. Set the address
4. Set the device mode
5. Mount the visual indicator onto the base
The details of each step are given below.
Wiring the base
Connect loop wiring for the base as shown in Figure 1. There
is no wiring between the visual indicator and base. The base is
supplied separately.
Figure 1: Loop wiring for the plug-in base
1. Ext. 24 VDC+ IN/OUT
4
. Ext. 24 VDC ground IN/OUT
5. Loop+ IN/OUT
7. Shield
8. Loop− IN/OUT
Setting the operating power
The visual indicator includes a pair of power selection jumpers,
J1 and J2. To select the source of the sounder operating
power, position the jumpers as shown in Figure 2.
Figure 2: Power selection jumper configuration
1.
Loop powered 2. External 24 VDC
Note: When using an external power supply, use only one that
is CE and EN 54-4 compliant to power all the visual indicators
on the same loop.
98 01
4
7
8
1
5
24V
0V
EXT
POWERED
24V
0V
EXT
POWERED
EXT
POWERED
LINE
POWERED
LINE
POWERED

2 / 4 P/N 501-1782ZE-1-09 • ISS 30MAY22
Setting the address
The visual indicator includes an eight-segment DIP switch
(SW1). Switch SW1-1 though SW1-7 are used to assign device
addresses. Each switch segment has a decimal value as
shown in Figure 3. The address is the sum of all the switch
segments (SW1-1 though SW1-7) in the ON position. The
switch may be set to represent any address from 1 to 127.
For example, to select a device address of 007, set SW1-1,
SW1-2, and SW1-3 to the ON position and the remaining
switch segments to the OFF position.
Figure 3: Address switch setting
1. Device mode
Setting the device mode
SW1-8 selects whether the visual indicator operates as a
stand-alone visual indicator or in ZP755 sounder emulation
mode as described in Table 1. Refer to Figure 3.
Table 1: SW1-8 mode selection switch
Mode
SW1-8 Output Signal Requirement
ZP755V
OFF Stand-alone
visual indicator
This setting is not
currently supported
Z
P755
emulation
ON ZP755 sounder ZP3 panel
Mounting the visual indicator onto the base
Align the addressable visual indicator to the plug-in base. Push
up, and then turn the visual indicator until it clicks into place.
Push the visual indicator up once more to engage.
Note: To prevent unauthorized removal, a plastic breakout tab
is provided in the addressable visual indicator housing. Once
the breakout tab is removed, the sensor can only be released
by use of a small flat screwdriver.
Visual indicators per loop
The visual indicator can be powered directly from the loop. Use
Figure 4, in conjunction with Table 2, to determine the quantity
of detectors and visual indicators that can be connected to a
two-core shielded loop.
Figure 4: Visual indicators per loop
A. Cable length panel to first visual indicator
B.
Cable length first to last visual indicator
C.
Cable length last visual indicator to panel
1. Detectors and visual indicators
Table 2: Maximum detectors and visual indicators per loop
A
B C Quantity allowed [1]
10 m
980 m 10 m 60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
100 m
800 m 100 m 60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
200 m
600 m 200 m 60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
300 m
400 m 300 m 60 detectors and 60 visual
indicators
80 detectors and 40 visual
indicators
[1] Using a two-core shielded loop of 1000 meters cable size 1.5 mm²
ON
1234567
OFF
ON
DIPSWITCH
1 2 4 8 16 32 64
8
1
2 8
416
32
64 1

P/N 501-1782ZE-1-09 • ISS 30MAY22 3 / 4
Specifications
Operating voltage
External supply
Loop supply, ZP protocol
18 to 30 VDC
19.5 to 20.5 V pulsed, max. 4 V line loss
Current
(line powered)
Quiescent (RMS)
Alarm (RMS)
Alarm maximum start of
flash
400 μA
2.5 mA
9 mA
Current (
externally powered)
Quiescent (RMS)
Alarm (RMS)
Maximum number
350 μA
360 μA
60 per 1 km loop (subject to cable
size and visual indicator spacing)
Light output
Equivalent to 1J xenon element
Strobe f
requency Flash rate 1.1 seconds
Monitoring
ZP loop
Operating power level tested
continuously
Addressing method
8-segment DIP switch
Mounting
Surface with stand-alone visual
indicator base
Wiring
Two-core shielded loop
Construction
Material
Colour
Weight
Dimensions (Ø × D)
Moulded thermoplastic
White, polar white
95 g
106 × 49 mm
Environmental
Operating temperature
Storage temperature
Relative humidity
−10 to +60°C
−20 to +70°C
10 to 95% noncondensing
Regulatory information
C
onformity
Manufacturer
Carrier Safety System (Hebei) Co. Ltd.,
80 Changjiang East Road, QETDZ,
Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing
representative:
Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
Netherlands.
2012/19/EU (WEEE Directive): Products
marked with this symbol cannot be
disposed of as unsorted municipal waste
in the European Union. For proper
recycling, return this product to your local
supplier upon the purchase of equivalent
new equipment, or dispose of it at
designated collection points. For more
information see: recyclethis.info.
Contact information and product
documentation
For contact information or to download the latest product
documentation, visit firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND
INSTALLATION BY QUALIFIED PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY
ASSURANCE THAT ANY PERSON OR ENTITY BUYING ITS
PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR
“AUTHORIZED RESELLER”, IS PROPERLY TRAINED OR
EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers
and product safety information, please check
https://firesecurityproducts.com/policy/product
-
warning/
or scan the QR code:

4 / 4 P/N 501-1782ZE-1-09 • ISS 30MAY22
This manual suits for next models
4
Other Ziton Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

Lippert
Lippert Tire Linc OEM INSTALLATION MANUAL

Felix Instruments
Felix Instruments F-750 Operation manual

Medical International Research
Medical International Research spirodoc user manual

PSI
PSI Polypen Aqua Instruction guide

Camille Bauer
Camille Bauer SINEAX AM1000 Device handbook

Schaller
Schaller humimeter BLL operating manual