Ziton Z600 Series Assembly instructions

© 2014 UTC Fire & Security. All rights reserved. 1 / 2 P/N 501-1335ZE-1-06 • REV 06 • ISS 19FEB14
Z600 Series Conventional Detector
Installation Sheet
1
2
Description
Z600 Series Conventional Detector models are shown in
Table 1.
Table 1: Models
Number Description EN 54 temperature
classification
Z620-581-3P
Fixed temperature heat
detector,Polar white Class A (58ºC)
Z620-582-3P
Rate of rise heat detector, Polar
white Class A1R (58ºC)
Z620-771-3P High temperature heat detector,
Polar white Class B (77ºC)
Z630-3P Optical smoke detector, Polar
white N/A
Z630-3S30 Optical smoke detector, Polar
white, Chubb N/A
Figures
Figure 1: Position of the locking tab
Figure 2: Removing a locked detector
Installation
Note: No wiring is required between the detector and the base.
Refer to base datasheet for line wiring installation. The
installation should be in accordance with the requirements of
the authority having jurisdiction.
The detector attaches to compatible bases with a plug-and-
twist action.
To attach the detector to the mounting base:
1. Align the unit to the base, and then slowly turn until the
location pin on the detector base engages with the slot on
the detector moulding.
2 / 2 P/N 501-1335ZE-1-06 • REV 06 • ISS 19FEB14
2. Rotate the detector clockwise until it clicks into position.
The detector may be locked into the mounting base if
required. To do this, remove the locking tab (Figure 1)
before installation.
3. Prior to initial testing remove the yellow plastic dust cover
from the detector. (For all tests notify the proper
authorities that the fire alarm system is undergoing
maintenance and will be temporarily out of service).
4. To allow easy zone identification, an indent is provided on
the detector exterior for application of a zone number
label.
For head out continuity, a diode base must be used and zone
wiring must be terminated with a suitable end of line (EOL)
component. The choice of EOL is dependant on the control
panel used (refer to control panel documentation). For control
panels with a head out facility, an active end of line unit must
be used.
To remove a locked detector:
1. Insert a small screwdriver into the locking tab slot as
shown in Figure 2.
2. Press the screwdriver to disengage the lock, and then
rotate the detector anticlockwise to remove it.
Maintenance
Maintenance should be planned in accordance with the
requirements of the authority having jurisdiction.
Specifications
Operating voltage
Z620-581-3P
Z620-582-3P
Z620-771-3P
Z630-3P, Z630-3S30
12 to 30 VDC
12 to 30 VDC
12 to 30 VDC
15 to 30 VDC
Current
Quiescent
Alarm
<60 µA at 24 VDC
50 mA max. (limited by panel)
Monitoring
Overall
Base
Diode base
Indication
Continuously self-checking
Open and short circuit by
end of line resistor
Open and short circuit, and head out
continuity with suitable end of line
(EOL) component.
Alarm LED (red)
Area coverage
Z620-581-3P
Z620-582-3P
Z620-771-3P
Z630-3P, Z630-3S30
50m², subject to local codes
50m², subject to local codes
50m², subject to local codes
100m², subject to local codes
Compatibility Compatible 24 VDC conventional
systems
Compatible mounting bases Z6-BS1P, Polar white
Z6-BS5P, Polar white
Mounting Plugs into surface base
Environmental
Application
Temperature range
Relative humidity
Storage temperature
IP rating
Z620-581-3P
Z620-582-3P
Z620-771-3P
Z630-3P, Z630-3S30
Indoor use
−20 to 15ºC above temp rating
20 to 95%, noncondensing
−20 to +70°C
IP55
IP55
IP55
IP32
Mechanical details
Material
Dimensions (Ø × H )
Height
Weight
Z620-581-3P
Z620-582-3P
Z620-771-3P
Z630-3P, Z630-3S30
Moulded ABS
106 x 52 mm (excluding base)
60 mm (from ceiling with surface –
mount base)
105 g (excluding base)
105 g (excluding base)
105 g (excluding base)
100 g (excluding base)
Regulatory information
This section includes both regulatory information and a summary on
the declared performance according to the Construction Products
Regulation 305/2011. For detailed information refer to the product
Declaration of Performance.
Certification
Certification body 0370
Declaration of
Performance number
Z620-581-3P
Z620-582-3P
Z620-771-3P
Z630-3P, Z630-3S30
360-4211-0599
360-4211-0899
360-4211-0699
360-4211-0799
Year of first CE marking 05
Product Identification Z620-581-3P, Z620-582-3P, Z620-771-3P
Z630-3P, Z630-3S30
Intended use See DoP point 3
Essential characteristics See DoP point 9
Manufacturer Gulf Security Technology Co.,Ltd
80, Changjiang East Road,
QETDZ, Qinhuangdao,
Hebei Province, China 066004
Authorized EU manufacturing
representative:
UTC Fire & Security B.V. Kelvinstraat 7,
6003 DH Weert, Netherlands
European Union directives 1999/5/EC (R&TTE directive): Hereby, UTC
Fire & Security declares that this device is in
compliance with the essential requirements
and other relevant provisions of Directive
1999/5/EC.
2002/96/EC (WEEE directive): Products
marked with this symbol cannot be disposed
of as unsorted municipal waste in the
European Union. For proper recycling,
return
this product to your local supplier upon the
purchase of equivalent new equipment, or
dispose of it at designated collection points.
For more information see:
www.recyclethis.info.
Contact information
For contact information, see www.utcfssecurityproducts.eu.

This manual suits for next models

5

Other Ziton Security Sensor manuals

Ziton ZP7BMR-50 User manual

Ziton

Ziton ZP7BMR-50 User manual

Ziton ZP700 Series Assembly instructions

Ziton

Ziton ZP700 Series Assembly instructions

Ziton ZR432-2P User manual

Ziton

Ziton ZR432-2P User manual

Ziton ZR432-2P Assembly instructions

Ziton

Ziton ZR432-2P Assembly instructions

Ziton ZP700 Series Assembly instructions

Ziton

Ziton ZP700 Series Assembly instructions

Popular Security Sensor manuals by other brands

PCB Piezotronics 1203-15A Installation and operating manual

PCB Piezotronics

PCB Piezotronics 1203-15A Installation and operating manual

UTL UTLCD1 instruction manual

UTL

UTL UTLCD1 instruction manual

Santacary i2 user manual

Santacary

Santacary i2 user manual

LEGRAND 845 06 manual

LEGRAND

LEGRAND 845 06 manual

DSC LC-100-PI installation manual

DSC

DSC LC-100-PI installation manual

CAMP Matik instruction manual

CAMP

CAMP Matik instruction manual

Gordon Ellis Prima quick start guide

Gordon Ellis

Gordon Ellis Prima quick start guide

Fluke Amprobe UAT-620 Technical data

Fluke

Fluke Amprobe UAT-620 Technical data

Solutions UWT NivoGuide 8100 Technical Information/Instruction manual

Solutions

Solutions UWT NivoGuide 8100 Technical Information/Instruction manual

Bircher Reglomat Herkules 2 Translation of the original operation instruction

Bircher Reglomat

Bircher Reglomat Herkules 2 Translation of the original operation instruction

GTE ADICOS HOTSPOT-1000 operating manual

GTE

GTE ADICOS HOTSPOT-1000 operating manual

General Monitors FL4000H quick start guide

General Monitors

General Monitors FL4000H quick start guide

tams elektronik WRM-4 manual

tams elektronik

tams elektronik WRM-4 manual

STEINEL IS 3180 installation instructions

STEINEL

STEINEL IS 3180 installation instructions

Omron K8AC-H Series manual

Omron

Omron K8AC-H Series manual

Emerson Rosemount 975 Series Reference manual

Emerson

Emerson Rosemount 975 Series Reference manual

Nice Mhouse MAD3 Instructions for installation

Nice

Nice Mhouse MAD3 Instructions for installation

Bacharach H-10 PRO instruction manual

Bacharach

Bacharach H-10 PRO instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.