
12
Ratings, fuses and typical power cables
1) Typical motor power with no overload capacity (nominal use). The kilowatt ratings apply to most IEC 4-pole motors. The
horsepower ratings apply to most NEMA 4-pole motors.
2) For IEC installations, ABB recommends aR fuses. See hardware manual for guidelines in selecting between aR and gG
fuses, and for additional fuse alternatives.
3) The recommended branch protection fuses must be used to maintain the IEC/EN/UL 61800-5-1 and CSA C22.2 No. 274
certifications. Refer to note 6 for circuit breaker protection.
4) IEC 61439-1:The drive is suitable for use on a circuit capable of delivering not more than 65 kA when protected by the
fuses given in this table.
5) UL 61800-5-1, CSA C22.2 No. 274: The drive is suitable for use on a circuit capable of delivering not more than 100 kA
symmetrical amperes (rms) at 600 V maximum when protected by the ABB recommended fuses.
6) Refer to
Alternate Fuses, MMPs and Circuit Breakers for ABB Drives
(3AXD50000645015 [English]) for additional UL fuses
and circuit breakers that can be used as branch circuit protection.
7) Class J, CC, and CF fuses are also allowed at the same nominal current and voltage ratings.
8)IEC 61800-9-2: Typical drive losses when it operates at 90% of the nominal output frequency and 100% of the nominal
output current.
9) IEC Installations: The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
on top of the other, ambient temperature 30 °C, PVC insulation, surface temperature 70 °C (EN 60204-1 and IEC 60364-5-
52/2001). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
10) NEC Installations: The cable sizing is based on NEC Table 310-15 for copper wires, 75 °C (167 °F) wire insulation at 40 °C
(104 °F) ambient temperature. Not more than three current-carrying conductors in raceway or cable or earth (directly
buried). For other conditions, size the cables according to local safety regulations, appropriate input voltage and the load
current of the drive.
- FA81 Safe torque off 1 loss The Safe torque off circuit 1 is broken.
- FA82 Safe torque off 2 loss The Safe torque off circuit 2 is broken.
ACS880
-01-… Frame
size
Nominal ratings Fuses3) Typical power cable Typical
power loss 8)
Input
current
Output
current
Motor
power1)
gG fuse4)
(DIN 43620)
aR fuse2)4)
(DIN 43620)
UL class
T5)6)7) Copper
I
1
I
2
P
nABB type Bussmann type mm2 9) AWG 10) W
AAkWhp
U
n= 3-phase 230 V
04A6-2 R1 4.6 4.6 0.75 1.0 OFAF000H6 170M1559 JJS-15 3×1.5 14 61
06A6-2 R1 6.6 6.6 1.1 1.5 OFAF000H10 170M1559 JJS-15 3×1.5 14 88
07A5-2 R1 7.5 7.5 1.5 2.0 OFAF000H16 170M1559 JJS-15 3×1.5 14 100
10A6-2 R1 10.6 10.6 2.2 3.0 OFAF000H16 170M1560 JJS-20 3×1.5 14 152
16A8-2 R2 16.8 16.8 4.0 5.0 OFAF000H25 170M1561 JJS-25 3×6 10 216
24A3-2 R2 24.3 24.3 5.5 7.5 OFAF000H40 170M1563 JJS-35 3×6 8 372
031A-2 R3 31.0 31.0 7.5 10 OFAF000H50 170M1565 JJS-50 3×10 8 364
046A-2 R4 46 46 11 11 OFAF000H63 170M1566 JJS-80 3×16 6 551
061A-2 R4 61 61 15 20 OFAF000H80 170M1568 JJS-80 3×25 4 811
075A-2 R5 75 75 18.5 25 OFAF000H100 170M3815 JJS-110 3×35 3 955
087A-2 R5 87 87 22 30 OFAF00H125 170M3816 JJS-110 3×35 2 1177
115A-2 R6 115 115 30 40 OFAF00H160 170M3817 JJS-150 3×50 1/0 1378
145A-2 R6 145 145 37 50 OFAF0H200 170M3817 JJS-200 3×95 3/0 1946
170A-2 R7 170 170 45 60 OFAF0H250 170M5809 JJS-250 3×120 4/0 1986
206A-2 R7 206 206 55 75 OFAF1H315 170M5810 JJS-300 2×150 300 MCM 2660
274A-2 R8 274 274 75 100 OFAF2H400 170M5810 JJS-400 2×(3×95) 2×2/0 3472
U
n= 3-phase 400 V
02A4-3 R1 2.4 2.4 0.75 - OFAF000H4 170M1561 - 3×1.5 - 47
03A3-3 R1 3.3 3.3 1.1 - OFAF000H6 170M1561 - 3×1.5 - 55
04A0-3 R1 4.0 4.0 1.5 - OFAF000H6 170M1561 - 3×1.5 - 63
05A6-3 R1 5.6 5.6 2.2 - OFAF000H10 170M1561 - 3×1.5 - 81
07A2-3 R1 8.0 8.0 3.0 - OFAF000H10 170M1561 - 3×1.5 - 115
09A4-3 R1 10.0 10.0 4.0 - OFAF000H16 170M1561 - 3×1.5 - 149
12A6-3 R1 12.9 12.9 5.5 - OFAF000H16 170M1561 - 3×1.5 - 217
017A-3 R2 17.0 17.0 7.5 - OFAF000H25 170M1563 - 3×6 - 239
025A-3 R2 25.0 25.0 11.0 - OFAF000H32 170M1563 - 3×6 - 411
032A-3 R3 32.0 32.0 15.0 - OFAF000H40 170M1565 - 3×10 - 406
038A-3 R3 38.0 38.0 18.5 - OFAF000H50 170M1565 - 3×10 - 519
045A-3 R4 45.0 45.0 22.0 - OFAF000H63 170M1566 - 3×16 - 533
061A-3 R4 61 61 30 - OFAF000H80 170M1567 - 3×25 - 820
072A-3 R5 72 72 37 - OFAF000H100 170M1568 - 3×35 - 865
087A-3 R5 87 87 45 - OFAF000H100 170M1569 - 3×35 - 1157
105A-3 R6 105 105 55 - OFAF00H125 170M3817 - 3×50 - 1228
145A-3 R6 145 145 75 - OFAF00H160 170M3817 - 3×95 - 1965
169A-3 R7 169 169 90 - OFAF0H250 170M5809 - 3×120 - 2049
206A-3 R7 206 206 110 - OFAF1H315 170M5810 - 3×150 - 2812
246A-3 R8 246 246 132 - OFAF1H355 170M5812 - 2×(3×70) - 3049
Warning Fault Aux. code Description