
14
The data recorded in the registers of the relay
can be used both to analyze an earth-fault situ-
ation and to study the behaviour of the protec-
tion equipment.
Register 1 stores the maximum measured neu-
tral current of the relay as a multiple of the rated
current of the energizing input used. If the relay
operates, the current measured at the moment
of operation is memorized. A new relay opera-
tion erases the previous value from the register
and updates the register contents. The register is
also erased and updated whenever the measured
current exceeds the currently recorded value.
The level of the neutral current value recorded
in a fault situation shows the degree of develop-
ment of the earth fault. The data of register 1
also show how close the relay’s start current is to
the actual fault current value.
Correspondingly the ratio between the set start
current and the current values during normal
operation can be determined by reading the
normal current values via the display of the relay.
The number of times the different stages have
started, registers 2 and 3, provides information
on the occurrence of earth-faults and informa-
tion on the distribution of earth-faults in respect
of the fault resistance. Frequent starts may be a
sign of an imminent earth-fault or some kind of
disturbance apt to cause an earth-fault.
Registers 4 and 5 show the duration of the latest
start situation of the stages, expressed in per cent
of the set operate time or, at inverse time opera-
tion the calculated operate time. Any new start
resets the counter, which restarts from zero. If
the stage operates, the register value will be 100.
The registers 4 and 5 give information on the
duration of an earth-fault, or, if a final trip has
been performed, the safety margin of the grad-
ing times of the selective protection. If, for
instance, the value of register 4 of the busbar
earth-fault relay operating as feeder back-up
protection is 75 when the earth-fault relay of the
feeder has operated, the safety margin between
the primary protection and the back-up protec-
tion is 25%.
The registers 1...5 are reset either by pressing the
STEP and RESET push-buttons simultaneously
or with a command, V102, over the SPA bus.
Recorded data
and fault analysis
Testing, both primary and secondary, should
always be performed in accordance with na-
tional regulations and instructions.
The protection relay incorporates an IRF func-
tion that continuously monitors the internal
state of the relay and produces an alarm signal on
the detection of a fault. According to the manu-
facturer’s recommendations the relay should be
submitted to secondary testing at five years’
intervals. These tests should include the entire
protection chain from the instrument trans-
formers to the circuit breakers.
The secondary testing described in this manual
is based on the relay’s setting values during
normal operation. If necessary, the secondary
testing can be extended by testing the protection
stages throughout their setting ranges.
As switch positions and setting values have to be
altered during the test procedure the correct
positions of switches and the setting values of
the relay during normal operation conditions
have to be recorded, for instance, on the refer-
ence card accompanying the relay.
To enable secondary injection testing the relay
has to be disconnected, either through discon-
nectable terminal blocks or a test plug fitted on
the relay.
DANGER!
Do not open the secondary circuit of a cur-
rent transformer under any phases of the
testing, if the primary circuit is live. The high
voltage produced by an open CT secondary
circuit could be lethal and may damage in-
struments and insulation.
When auxiliary voltage is connected to the
protection relay, the relay performs a self-testing
program, which does not includes the matching
transformers and the contacts of the output
relays. The operational condition of the relay is
tested by means of ordinary relay test equipment
and such a test also includes the matching trans-
formers, the output relays and the accuracy of
the operate values.
Equipment required for testing:
- adjustable voltage transformer 0...260 V, 1 A
- current transformer
- ammeter, accuracy ±0.5%
- stop watch or counter for time measurement
- dc voltage source
- switches and indicator lamps
- supply and pilot wires
- calibrated multimeter
Secondary
injection testing