ABB VFD-GATEWAY User manual

—
ABB MOTION DRIVES US - CONNECTIVITY
VFD-GATEWAY
EtherNet/IP™ to Modbus RTU gateway User Manual

LVD-EOMU02U-EN REVB 04/2022
—
VFD-GATEWAY EtherNet/IP™
User Manual
Table of contents

LVD-EOMU02U-EN REVB 04/2022
—
Contents
4 1. Safety instructions
5-9 2. Installation
10–26 3. Setup
27-28 4. Troubleshooting
29-31 5. Appendix

LVD-EOMU02U-EN REVB 04/2022
—
1. Safety instructions
WARNING! Obey these instructions. If you ignore them, injury or death, or damage to the
equipment can occur.
• If you are not a qualified electrician, do not do installation or maintenance work.
• Disconnect the drive, converter or inverter from all possible power sources. After you have disconnected the
drive, converter or inverter, always wait for 5 minutes to let the intermediate circuit capacitors discharge
before you continue.
• Disconnect all dangerous voltages connected to other control signal connectors in reach. For example, it is
possible that 120/230 V AC is connected from outside to a relay output of the drive, converter or inverter.
• Always use a multimeter to make sure that there are no parts under voltage in reach. The impedance of the
multimeter must be at least 1 Mohm.
VFD-GATEWAY devices and equipment are sensitive to electrostatic discharge, which can cause internal damage
and affect normal operation.
Observe the following rules when handling the VFD-GATEWAY:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wrist strap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• If available, use a static-safe workstation.
• When not in use, store the equipment in appropriate static-safe packaging.
VFD-GATEWAY
Ensure the VFD-GATEWAY is grounded.
• The ground (switch cabinet earthing, PE) is supplied both by the mains connection (or 24 V supply voltage) and
via the DIN rail (if mounted).
• The DIN rail must be connected to the ground before the device is subjected to any power. The ground may be
removed only if it is certain that no more power is being supplied to the control system.

LVD-EOMU02U-EN REVB 04/2022
—
2. Installation
Contents of this chapter
2.1 Mounting the VFD-GATEWAY
DIN rail according to DIN EN 50022 35 mm, depth 7.5 mm or 15 mm:
Mounting with screws M3 (see Appendix for hole fixing dimensions):
Fastening torque 1.2 Nm

LVD-EOMU02U-EN REVB 04/2022
2.2 Power supply connection and requirements
ABB 1SVR427041R0000, CP-D 24/0.42
CAUTION!
Safety Extra Low Voltage (SELV) and Protective Extra Low Voltage (PELV)
2.3 Ethernet interface
Connect your Ethernet interface via the VFD-GATEWAY RJ45 jack
Note: EtherNet cable not included. The network cable must be CAT5 or higher, and type UTP, FTP or STP.
The maximum length for an Ethernet segment on twisted pair media is 100 meters.
The VFD-GATEWAY supports twisted pair as the physical media in a star topology. All twisted pair media between the
Ethernet node and the switch or router must be shorter than 100 meters, including media within patch panels.
LED Color Off On Flashing
-
-

LVD-EOMU02U-EN REVB 04/2022
2.4 Modbus RTU Interface and wiring
1. 2 LEDs for communication state display (TxD and RxD)
2. 2 LEDs for termination state display
3. Allocation of signal name
4. 5-pin terminal block for communication interface
Status LEDs:
The Modbus-RTU can be connected to up to 5 ABB drives via the following connections:
Terminating resistors
120 Ω ¼ W is required at both line ends of the Modbus-RTU network
Ω

LVD-EOMU02U-EN REVB 04/2022
Disabling terminating resistors
If the gateway needs to be installed in the middle of the Modbus network, the resistor on the gateway needs to be
turned off. To do this the Modbus module on the gateway needs to be removed using the following instructions.
Ensure the VFD-GATEWAY is turned off.
Press the tab on the side of the module and pull up on the module to remove it from the VFD-GATEWAY:
After it is removed, turn the top dip-switches off. They are currently in the on position from the factory.
Flip the switches to the left for OFF (towards the ABB logo) and reinstall.

LVD-EOMU02U-EN REVB 04/2022
Modbus-RTU cable requirements
Make sure you use cable with the following specification for reliable Modbus-RTU performance.
Use shielded twisted-pair cable with a twisted pair for data and a wire or another pair for signal ground (nominal
impedance 100 to 165 ohm, for example Belden 9842) for the wiring. For best immunity, ABB recommends high quality
cable. Keep the cable as short as possible.
Avoid unnecessary loops and parallel runs near power cables such as motor cables.
BUS Cable
Ω
ΩΩΩ

LVD-EOMU02U-EN REVB 04/2022
—
3. Setup
Contents of this chapter
3.1 Drive Setup
3.2 Data mapping examples for ACS355
Drive Supported data words
Drive Parameter Example for ACS355
Setup parameters
ACS355 typical parameters
READ from VFD
WRITE to VFD
ACS355 must be power cycled for changes to take effect

LVD-EOMU02U-EN REVB 04/2022
3.3 Setup, data mapping and typical parameters for ACS380, ACH/Q/S580
Drive Parameter Example for ACS380, ACQ/S580
Setup parameters
Note: You MUST set 58.06 to refresh settings after all parameters in group 58 are set.
ACS380, ACQ/S580 typical parameters
READ from VFD
Write to VFD

LVD-EOMU02U-EN REVB 04/2022
3.4 Setup, data mapping and typical parameters for ACS880, DCS880
Drive Parameter Example for ACS880, DCS880
Setup parameters
ACS880 typical parameters
READ from VFD
Write to VFD
Note: You MUST set 58.06 to refresh settings after all parameters in group 58 are set.

LVD-EOMU02U-EN REVB 04/2022
3.5 Setup, data mapping and typical parameters for ACH580 and ACH580 E-Clipse bypass
ACH580 ACH580 E-Clipse
Drive Parameter ACH580 E-Clipse
Setup parameters
Note: You MUST set 58.06 to refresh settings after all parameters in group 58 are set.
Note: ACH580 E-Clipse power must be cycled for changes to take effect
ACH580 E-Clipse typical parameters
READ from VFD
WRITE to VFD
Drive Parameter Example for ACH580
Setup parameters
ACH580 typical parameters
READ from VFD
Write to VFD

LVD-EOMU02U-EN REVB 04/2022
3.6 ABB Drives control profile
only
Control Word sequence:
To Run Drive:
To Stop Drive:
•
•
Speed Scaling ACS380, ACH/S/Q580, ACS880, DCS880 and ACH580 E-Clips:
Speed Scaling ACS355:
ABB Drives profile Control Word Bit structure
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0Reset
1
ABB Drives profile Status Word Bit structure
Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
1
Enable
At

LVD-EOMU02U-EN REVB 04/2022
3.7 Ethernet configuration settings
3.8 Ethernet/IP scanner setup
Assembly Instance Size

LVD-EOMU02U-EN REVB 04/2022
Note: Use either EDS File or Generic module DO NOT USE BOTH

LVD-EOMU02U-EN REVB 04/2022
-
MUST
Note: Use either EDS File or Generic module DO NOT USE BOTH

LVD-EOMU02U-EN REVB 04/2022

LVD-EOMU02U-EN REVB 04/2022

LVD-EOMU02U-EN REVB 04/2022
3.9 Configuring the VFD-GATEWAY Web browser interface
Table of contents
Other ABB Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

Alfalaval
Alfalaval Pharma-line S 1 instruction manual

Ice Qube
Ice Qube IQ700HE Operation and installation manual

Harmonic Drive
Harmonic Drive HFUS-2A Series engineering data

Isotech
Isotech OCEANUS-6 Series User & maintenance manual

Unitrol
Unitrol PO-22 instruction manual

Entrematic
Entrematic Ditec VALHLLOK installation manual

Alfalaval
Alfalaval LeviMag instruction manual

C.R. Laurence
C.R. Laurence CRL 290 Series Assembly instructions

Burger & Brown
Burger & Brown SMARTFLOW FasTie installation instructions

Power Fist
Power Fist 8873341 quick start guide

TAS
TAS 3006 plus user manual

EGAmaster
EGAmaster ROSCAMATIC 100-4 operating instructions