ABB XT201M3H/DALI Manual

XT201M3H/DALI
Technical Specifications
1 of 4
4 of 4
Operation
IP Rating
Function
Lumen output
Power Supply
Power Consumption
Temperature
Luminaire Class
Photometric
: Maintained and Non maintained
: IP20
: DALI with AUTO test
: 150lm (CREE XT-E)
: 220-240VAC, 50/60 Hz
: Max. 5.5W
: 0°C-25°C
: Class II
Note: We reserve the right to make technical changes
or modify the contents of this document without prior
notice. With regard to purchase orders and/or contracts,
the agreed particularsshall prevail. ABB does not accept
any responsibility whatsoever for potential errors or
possible lack of information in this document.
We reserve all rights in this document and in the subject
matter and illustrations contained therein.
Any reproduction, disclosure to third parties or utilisation
of its contents - in whole or in parts -is forbidden without
prior written consent of ABB.
Copyright © 2020 ABB
All rights reserved
Instruction Leaflet
Model Number
Explanations
Maintained
Luminaire
Switched Maintained
Luminaire
Non-maintained
Luminaire
Emergency mode
Failure-Battery
Charge
Input
Voltage
220-240V~
50/60HZ
Charge
Duration
Discharge
Duration Battery Power
Consumption
Ni-Mh
3.6V 2.6Ah CREE XT-E
LED Lumen
ouput
LED INDICATION STATUS COMMENTARY
Permanent Green
Everything Working Correctly
Fast Flashing Green Function Test in Progress
(0.1 Sec ON - 0.1 sec OFF)
Slow Flashing Green
(1 sec ON-1 sec OFF) Duration Test In Progress
Permanent Yellow Load Failure
Slow Flashing Yellow Battery Failure
(1 sec ON-1 sec OFF)
(0.1 sec ON-0.1 sec OFF) Charging Failure
DC Mode
Green and Yellow OFF
Open Circuit/Short Circuit/LED Failure
Battery Failed Duration or Function Test
Battery is Defective/Wrong Battery Voltage
Incorrect Charging Current
Battery Operation(Emergency Mode)
Fast Flashing Yellow
OK
150 lm
5.5 W
3 h
24 h
TECHNICAL INFORMATION
XT201M3H/DALI
IP
20
D
ABB BV
C/O Thomas & Betts European Centre
Boulevard Millenium 8
B – 7110 Houdeng-Goegnies
Belgium
UK Contact
Telephone +44 (0) 113 281 0600
Sales +44 (0) 113 281 0610
Fax +44 (0) 113 281 0601
Email LV[email protected]
Deutschland Kontakt:
Busch-Jaeger Elektro
Ein Unternehmen der ABB Gruppe
Freisenbergerstrasse 2
58513 Lüdenscheid
Zentraler Vertriebsservice
Tel: +49 (0)2351 956 1600
Fax: +49 (0)2351 956 1700
Website: solutions.abb/led-sicherheitsbeleuchtung
Other countries:
For more information, please reach
out to our ABB local contact center.
Find out on: new.abb.com/contact-centers

INSTALLATION
3 of 4
2 of 4
MOUNTING SPACING
WIRING INSTRUCTION
GENERAL INFORMATION
LED Emergency down light for both open area and escape routes.
Product has polycarbonate housed LED light source with low power consumption giving extended
battery life.
PRECAUTIONS
Carefully read this instruction leafet before installing or using the luminaire.
This leafet provides important information about the correct installation, use, maintenance and
disposal of this product. Please observe the following guidelines:
1. Installation must be in accordance with European installation requirements HD 60364 and
additional local regulations.
2. This product may not be modified in any way what so ever or used for a purpose or in an
environment other than for which it is designed. Failing to observe these guidelines will invalidate
the warranty and the CE-compliance of this product.
3. The luminaire is suitable for indoor use only
4. Before installing the luminaire, the supply must be isolated.
5.The luminaire should be connected to the voltage equivalent to that indicated on the type label
SERVICE & OPERATION
Normal Operation: The green indicator light on face plate stays on. The LED will go out if the mains
supply fails, the internal charger malfunctions, or the unit is in test mode.
Battery: Sealed Ni-Cad or Ni-Mh rechargeable battery pack. Battery should be replaced when the
required duration is no longer achieved. To avoid any damage to the fixture and ensure its
performance,the battery should be replaced with same brand and type.
Test Switch: Press the test switch button, LED indicator will go out and the sign will be illuminate
from its battery pack.
WARNING:
The luminaire must, under no circumstances, be covered with insulating material or similar material
only
Commissioning Test Behaviour
Initial connection of the mains supply will initiate a commissioning sequence where the battery will
remain on charge and test for an uninterrupted 60 hours. Any interruption of the mains supply during
this period will reset the counter to zero.
The sequence is : to charge for 24hours. Having fully charged the battery, then execute a duration test.
Upon successful completion of the duration test, the gear will perform another full charge period of
24hours. After this period, it is suggested to perform a function test and then check for successful
completion of the function and duration tests.
Therefore, after initial mains power on, it is best to leave the gear alone for 60 hours to allow the gear
to complete its pre-programmed commissioning testing. During the 60 hour period, any attempt
to have the gear perform a function or duration test will simply result in the requested test being
'pended'. Following the commissioning test it will then perform whatever tests are pended. Meaning
that if you had pressed "start duration test", at the end of commissioning, the gear will perform
another duration test and another subsequent charge period before normal operations could be
resumed.
Gear Behaviour After Battery Change (meaning Disconnect / Reconnect battery)
After changing the battery, the gear will perform a complete commissioning sequence, as described
above, irrespective of the condition of the battery.
Function test
A 5 second functional test is carried out at nominally 1 week interval.
Duration test
The gear switches to battery supply with mains supply off, and runs until the batteries can no longer
supply the lamp
The length of time to run out is recorded in memory.
A pass result indicates the battery powered the fitting and lamp for the rated period of this fitting.
A full rated duration test is carried out nominally at 52 weeks intervals.
In DALI mode, the start of the regular duration and function tests, is initiated by the attached controller.
If the DALI controller is not available, the gear will revert to its automated settings.
Maintained or Non-Maintained wiring. ACEM wiring(switchable maintained).
Connect L, N and remove jumper cable and
connect switched line between SL and L
terminal.
Maintained (default operation):
Connect L, N and leave jumper cable connected.
Non-maintained:
Connect L, N and remove jumper cable.
• Even escape routes
• Emergency lighting factor: 1.00
• Minimum illuminance on centre line: 1.00 lx
• Minimum illuminance on half of escape route
width: 0.50 lx
• Diversity on the centre line max. 40 : 1
• Width of escape route: 2.00 m
Xb
Ya
Yb
Xa
The spacing table is based on the following
parameters:
MF 1.00 MF 0.8
h(m) Xa Xb Yb Ya Xa Xb Yb Ya
2.5 3.80 9.33 5.84 2.44 3.56 8.71 5.38 2.34
3 4.08 10.00 6.16 2.73 3.77 9.35 5.87 2.60
3.5 4.26 10.64 6.73 2.97 3.90 9.98 6.48 2.80
4 4.38 11.24 7.35 3.16 3.99 10.4 7.02 2.94
Other ABB Light Fixture manuals
Popular Light Fixture manuals by other brands

California Accent Lighting
California Accent Lighting lipLEDs LLED8350-UC installation instructions

Creamsource
Creamsource Vortex 8 manual

Chauvet
Chauvet eclipse user manual

Philips
Philips VL72 installation instructions

Trio
Trio JASMIN quick start guide

Cooper Lighting
Cooper Lighting all-pro mst27920les instruction manual