Absolute Process Instruments APD 1431 User manual

RTD or Thermistor Input, Factory Configured
Specify temperature range in °F or °C and sensor type
Minimum span: 100°F (55°C) or consult factory
RTD types: Specify type listed below and if 2, 3, or 4 wire
For others provide resistance at 0°C and curve
100 Ω0.00385 DIN
100 Ω0.003916
100 Ω 0.00392
10 ΩCu
1000 ΩNi-Fe
120 ΩNi
RTD leadwire compensation: < ±0.05% of
span per 1 Ωchange in leadwire resistance
Thermistors: Specify type listed below. For other sensor types
provide temperature-resistance chart.
44004/44033 2.252 kΩat 25°C
44005/44030 3.000 kΩat 25°C
44007/44034 5.000 kΩat 25°C
44006/44031 10.00 kΩat 25°C
44008/44032 30.00 kΩat 25°C
YSI 400 2.252 kΩat 25°C
Spectrum 1003k 1 kΩ
Isolation
Power to input isolation: 1200 V
Common mode protection: 600 VACpor 600 VDC
LoopTracker
Variable brightness LED indicates input level and status
APD 1401 Relay Output
Single setpoint dual DPST contact sets, field configurable
2 Form A (NO) and 2 Form B (NC) contact sets (8 terminals)
May be field wired for Form C operation
One set point, 12 turn potentiometer, 0-100% of span
One reset point, 12 turn potentiometer, 0-100% of span
Factory configured alarm
Standard: HI alarm, non-latching, normal acting
APD 1421, APD 1431 Relay Output
2 independent setpoint DPST contact sets, field configurable
SP 1: Form A (NO) and Form B (NC) contacts (4 terminals)
SP 2: Form A (NO) and Form B (NC) contacts (4 terminals)
May be field wired for Form C operation
Two set points, two 12 turn potentiometers, 0-100% span
Two reset points, two 12 turn potentiometers, 0-100% span
Factory configured alarm
APD 1220: HI/LO alarm, non-latching, normal acting
APD 1230: Band alarm (both alarms trip if outside LO and
HI trip points), non-latching, normal acting
Relay Contact
Ratings
8 A max @ 240 VAC
resistive load.
External contact
protection such as
an RC snubber is
recommended for
inductive loads.
Response Time
300 milliseconds typical
Output Test/Reset Button
Front button or external contact closure toggles relays to
opposite state when pressed.
Resets relay if latching relay option is ordered
RTD/Thermistor Input Alarm Trips, Isolated, Factory Configured APD 1401, APD 1421, APD 1431
Input: 2 or 3 Wire RTD
Output: Two 8 Amp SPDT Relays
OFactory Set Input Type and Temperature Range
OAdjustable Trip and Reset Potentiometers
OInput LoopTracker®and Alarm Status LEDs
OFull 1200 V Isolation
OAlarm Test, Optional Latching Reset Button
ORTD Leadwire Compensation
QProcess Limit Alarm
QMonitor, Heaters, Refrigerators, Ovens
QProcess Signal Over or Under Alarms
Applications
Switching Current (A)
Switching Voltage (V)
0 3 5 10 30 50 100 300 500
8
5
3
1
0.5
0.3
0.1
AC inductive load
(cos f= 0.4) AC resistive
load
DC inductive load
(L/R = 7 ms)
DC resistive
load
© 08-19
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
AABSOLUTEBSOLUTE PPROCESSROCESS IINSTRUMENTSNSTRUMENTS
Description
The APD 14x1 series accepts an RTD or thermistor tempera-
ture input and provide a visual alarm indication and alarm
relay contact outputs.
The input type, range, and alarm types are factory configured.
The input can be configured for most RTDs or thermistors.
Front-accessible potentiometers are used to adjust alarm trip
and reset point(s).
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies
in intensity with changes in the process input signal.
A red/green bicolor alarm status LED (two on the APD 1420)
visually indicate alarm status.
These LEDs provide a quick visual picture of your process
at all times.
Output Test / Unlatch
API's exclusive Output Test button can be used to verify the
alarm and system operation and also provides the additional
function of unlatching the alarm when the latching option has
been ordered.
The output test button greatly aids in saving time during initial
startup and/or troubleshooting.
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than 0.04% of span per °C
Dimensions
0.89" W x 4.62" H x 4.81" D (22.5 x 117 x 122 mm)
Height includes connectors
Housing and Connectors
IP 40, requires installation in panel or enclosure
For use in Pollution Degree 2 Environment
Mount vertically to a 35 mm DIN rail
Four 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 2 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 2 W maximum
Quick Link: api-usa.com/1000
Input: 2, 3, or 4 Wire RTD or Thermistor New Microprocessor-Based Versions
Output: Two 8 Amp DPST Relays
See Wiring
Diagrams on
Next Page
Free Factory
I/O Setup!
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
Made in USA
Quick Link: api-usa.com/1400
Applications Link
api-usa.com/apps
Pb Lead
Free
Universal
Power
Alarm Status LED
Input Loop-
Tracker LED
Alarm Test
Function
Adjustable
Trip and Reset
Points
Two 8 Amp DPST
Alarm Relays
Custom Input
Ranges
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Model Input Standard Alarm Configuration Power
APD 1401 Factory ranged, specify
sensor type
°F or °C temperature
range
Options if required
HI alarm, single setpoint, dual DPST relays
non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1401 D 9-30 VDC or 10-32 VAC
APD 1421 HI/LO alarms, 2 setpoints, 2 DPST relays
non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1421 D 9-30 VDC or 10-32 VAC
APD 1431 Band alarm, 2 setpoints, 2 DPST relays
non-latching, normal acting
85-265 VAC or 60-300 VDC
APD 1431 D 9-30 VDC or 10-32 VAC
Options—add to end of model number
LAPD 1401 with LO trip. Alarm trips on decreasing signal.
HH APD 1421 with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL APD 1421 with LO/LO trip. Alarms trip at their respec-
tive trip points on decreasing signal.
LH APD 1421 with LO/HI trip. Alarm 1 trips on decreasing
signal. Alarm 2 trips on increasing signal.
IB APD 1431 with Inverse Band alarm. Both alarms trip if
signal is between LO and HI trip points.
HT Latching alarm with push button reset
HP Latching alarm with power-off reset. Module power
must be turned off to reset alarms
RReverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
UConformal coating for moisture resistance
Accessory—order as separate line item
API BP4 Spare removable 4 terminal plug, black

Precautions
WARNING! All wiring must be performed by a qualified electri-
cian or instrumentation engineer. See diagram for terminal des-
ignations and wiring examples. Consult factory for assistance.
WARNING! Avoid shock hazards! Turn signal input, output,
and power off before connecting or disconnecting wiring, or
removing or installing module.
Précautions
ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de
câblage. Consulter l'usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal
d'entrée, le signal de sortie et l'alimentation électrique avant
de connecter ou de déconnecter le câblage, ou de retirer ou
d'installer le module.
Electrical Connections
See wiring diagrams. Observe input connections. If the output
does not function, check all wiring and polarity.
*Do not make any connections to unused terminals or use
them as wiring junctions for external devices. This may cause
permanent damage to the module!
Input
The sensor type and input range is factory pre-configured (at
24°C ±1°C) and do not require adjustment. See the model/
serial number label for sensor type, temperature range and
options. The temperature sensor input is connected as shown
in the wiring diagrams.
Alarm Types
High Alarm (default, H, or HH): The alarm relay changes state
when the temperature exceeds the trip point. The relay resets
when the temperature drops below the reset point. For a high
alarm, the trip point is above the reset point.
Low Alarm (L or LL): The alarm relay changes state when the
temperature goes below the trip point. The relay resets when
the temperature exceeds the reset point. For a low alarm the
trip point is below the reset point.
HT: Latching alarm with push button reset
HP: Latching alarm with power-off reset. Module power must
be turned off to reset alarms
R: Reverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
Relay Output Terminals
See wiring diagrams for connections. APD modules do not
provide power to the relay contacts. Inductive loads (motors,
solenoids, contactors, etc.) will greatly shorten relay contact
life unless an appropriate RC snubber is installed.
The APD 1401 operates two sets of relays in unison with a
single setpoint. The dual DPST contact sets are in a Form C
configuration.
The APD 1421 and APD 1431 operate two sets of relays inde-
pendently, each with its own setpoint. The dual DPST contact
sets are in a Form C configuration.
Module Power
Check model/serial number label for module operating volt-
age to make sure it matches available power.
When using DC power, either polarity is acceptable, but
for consistency with similar API products, positive (+) can
be wired to terminal 13 and negative (–) can be wired to
terminal 16.
Mounting To a DIN Rail
Install module vertically on a 35 mm DIN rail in a protective
enclosure away from heat sources. Do not block air flow. Al-
low 1" (25 mm) above and below housing vents for air cir-
culation.
1. Tilt front of module downward and clip the lower mount
with spring clips to the bottom edge of DIN rail.
2. Push front of module upward until upper mount snaps into
place.
Removal From a DIN Rail
1. Push up on the bottom back of the module.
2. Tilt front of module downward to release upper mount
from top edge of DIN rail.
3. The module can now be removed from the DIN rail.
Relay Operation
Relay operation is factory configured. See model/serial num-
ber label for relay configuration option codes.
Set Point
This multi-turn potentiometer (one for each alarm on the APD
1421 and APD 1431) allows the operator to adjust the level at
which the alarm is activated. This control is adjustable from 0
to 100% of the input range.
Reset Point
This multi-turn potentiometer (one for each alarm on the APD
1421 and APD 1431) allows the operator to adjust the level at
which the alarm resets. This control is adjustable from 0 to
100% of the input range.
Sufficient deadband (difference between trip and reset point)
should be used to prevent chattering of the relays or false
trips when the process signal is unstable or changes rapidly.
Adjustments
Set the signal source to a reference that represents the de-
sired set point.
Adjust the set point potentiometer to the point at which the
relay changes state from a non-alarm to an alarm condition.
Set the signal source to a reference that represents the
desired reset point.
Adjust the reset point potentiometer to the point at which the
relay changes state from an alarm to a non-alarm condition.
Operate the signal source through the set and reset points to
confirm desired operation and adjust if necessary.
For the APD 1421 and APD 1431, repeat the above procedure
for the second alarm.
Output Test Function
When the front test button is depressed it will drive the relays
to their opposite state. When released, the relays will return
to their prior states.
This can be used as a diagnostic aid during initial start-up or
troubleshooting, or as a manual over-ride function. The Test
button also resets the relays on models with the HT option.
Operation
The green LoopTracker®input LED provides a visual indication
that a signal is being sensed by the input circuitry of the
module. It also indicates the input signal strength by changing
in intensity as the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as
the process changes, check the module power or signal input
wiring. Note that it may be difficult to see the LEDs under
bright lighting conditions.
The bicolor alarm LED provides a visual indication of the alarm
status. In all configurations, a green LED indicates a non-alarm
condition and a red LED indicates an alarm condition.
In the normal mode of operation, the relay coil is energized
in a non-alarm condition and de-energized in an alarm
condition. This will create an alarm condition if the module
loses power. For a normal acting, non-latching configuration,
the alarm will activate when the input signal exceeds the
setpoint (HI alarm) or falls below the setpoint (LO alarm),
then will automatically reset when the alarm condition no
longer exists.
For a reverse acting alarm, the relay coil is de-energized in a
non-alarm condition and energized in an alarm condition. The
alarm activates when the input signal exceeds the setpoint (HI
alarm) or falls below the setpoint (LO alarm), then automati-
cally resets when the alarm condition no longer exists.
For models with the latching relay option, it will be necessary
to push the Test button or remove power from the module to
reset the alarm, depending on the type of latching option. The
alarm will only reset if the alarm condition no longer exists.
Installation and Setup APD 1401, APD 1421, APD 1431
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
AABSOLUTEBSOLUTE PPROCESSROCESS IINSTRUMENTSNSTRUMENTS
API maintains a constant effort to upgrade and improve its products.
Specifications are subject to change without notice. See api-usa.com for
latest product information. Consult factory for your specific requirements.
WARNING: This product can expose you to chemicals includ-
ing nickel, which are known to the State of California to cause
cancer or birth defects or other reproductive harm. For more
information go to www.P65Warnings.ca.gov
* Do not make connections to unused terminals!
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
Input
Relay 1
Power
Relay 2 Wire terminal torque
0.5 Nm to 0.6 Nm
(4.4 to 5.3 in-lbs)
To maintain full isola-
tion avoid combining
power supplies in
common with input,
output, or unit power.
* Do not make
connections to
unused terminals!
3 Wire RTD Input
109 11 12
4 Wire RTD Input
109 11 12
2 Wire RTD or Thermistor Input
109 11 12
Module Power
AC or DC +
AC or DC –
1413 15 16 Cu 60/75°C
conductors
14 AWG
max.
Relay Wiring APD 1421, 1431
SP 1 Form A Form B
NO NO NC NC
21 3 4
65 7 8
SP 2 Form A Form B
NO NO NC NC
Jumper
2 & 3 for
Form C
operation
Jumper
6 & 7 for
Form C
operation
Relay Wiring APD 1401
SP 1 Form A Form B
NO NO NC NC
21 3 4
65 7 8
SP 1 Form A Form B
NO NO NC NC
Jumper
2 & 3 for
Form C
operation
Jumper
6 & 7 for
Form C
operation
This manual suits for next models
5
Other Absolute Process Instruments Security System manuals

Absolute Process Instruments
Absolute Process Instruments API 1080 G User manual

Absolute Process Instruments
Absolute Process Instruments Cecomp F16ADA User manual

Absolute Process Instruments
Absolute Process Instruments APD 1400 User manual

Absolute Process Instruments
Absolute Process Instruments API 1000 G User manual

Absolute Process Instruments
Absolute Process Instruments API 1005 G User manual

Absolute Process Instruments
Absolute Process Instruments API 1040 G Series User manual

Absolute Process Instruments
Absolute Process Instruments APD 1200 User manual