Absolute Process Instruments API 1005 G User manual

Input: 4-20 mADC
Output: One 8 Amp DPDT Relay or Two 8 Amp SPDT Relays
O4-20 mA Input with Loop Supply
OField Adjustable Setpoints
OPlug-In Design for Fast Installation
OInput LoopTracker®and Alarm Status LEDs
OAlarm Test, Optional Reset Button
QProcess Limit Backup Alarm
QTank Level Alarm
QProcess Signal Over, Under, Out-of-Range Alarm
Model Input Standard Alarm Configuration Power
API 1005 G
Factory ranged
4-20 mA
Single setpoint one DPDT relay
HI alarm, non-latching, normal acting
115 VAC
API 1005 G A230 230 VAC
API 1005 G P 85-265 VAC or 60-300 VDC
API 1005 G D 9-30 VDC
API 1025 G
Factory ranged
4-20 mA
2 setpoints, 2 SPDT relays
HI/LO alarms, non-latching, normal acting
115 VAC
API 1025 G A230 230 VAC
API 1025 G P 85-265 VAC or 60-300 VDC
API 1025 G D 9-30 VDC
4-20 mA Input
Factory configured 4-20 mADC, sourcing
Input Impedance and Burden
Current: 50 Ωtypical
Voltage burden: 1.25 VDC at 20 mA current input
Isolation and Input Protection
750 VACpor 750 VDC common mode protection
Input isolated from power supply
Input Loop Power Supply
18 VDC unregulated, 25 mADC, <1.5 Vp-p ripple
LoopTracker
Variable brightness LED indicates input loop level and status
API 1005 G Relay Output
Two SPDT form C contact sets operating in unison as one
DPDT contact set
One setpoint, 12 turn potentiometer, 0-100% of span
Factory configured alarm type
Standard: HI alarm, non-latching, normal acting
Options: LO alarm, latching, reverse acting
API 1025 G Relay Output
Two independent SPDT form C contact sets
Two setpoints, two 12 turn potentiometers, 0-100% of span
Factory configured alarm action
Internal jumpers for HI/LO, LO/LO, HI/HI, LO/HI
Standard: HI/LO alarm, non-latching, normal acting
Options: LO/LO, HI/HI, LO/HI alarms, latching, reverse acting
Relay Contact Rating
8 A @ 240 VAC resistive load or 30 VDC resistive load
5 A @ 240 VAC inductive load (cos f = 0.4)
3.5 A @ 30 VDC inductive load (L/R = 7ms)
See graph on other side for relay load ratings
Caution: Do not exceed socket voltage rating
Use an RC snubber for inductive loads
Deadband
Alarm trip/reset window is symmetrical about the setpoint
API 1005 G 1.0 to 100% of span, 12 turn potentiometer.
API 1025 G Fixed at 1% of span, standard
API 1025 G A Adjustable deadbands, 1.0 to 100% of span,
1 turn potentiometer for each setpoint
Output Test/Reset Button
Toggles relay(s) to opposite state when pressed
Resets latching relay with HT option, available on 1005 G only
Response Time
70 milliseconds typical
Ambient Temperature Range and Stability
–10°C to +60°C operating ambient
Better than 0.02% of span per °C stability
Housing and Sockets
IP 40, requires installation in panel or enclosure
API 011 or API 011 FS socket
Socket mounts to 35 mm DIN rail or can be surface mounted
Power
Standard: 115 VAC ±10%, 50/60 Hz, 2.5 W max.
Poption: 85-265 VAC 50/60 Hz, 60-300 VDC, 2.5 W typ.
A230 option: 230 VAC ±10%, 50/60 Hz, 2.5 W max.
Doption: 9-30 VDC, 2.5 W typical
Options—add to end of model number
L1005 G with LO trip. Alarm trips on decreasing signal.
HT 1005 G latching alarm with push button reset
HP 1005 G latching alarm with power-off reset
Module power must be turned off to reset alarms
HH 1025 G with HI/HI trip. Alarms trip at their respective
trip points on increasing signal.
LL 1025 G with LO/LO trip. Alarms trip at their respective
trip points on decreasing signal.
A1025 G with adjustable deadbands
RReverse-acting alarms. Relay coils energized in an alarm
condition. No alarm condition with module power off.
UConformal coating for moisture resistance
Accessories—order as a separate line item
API 011 11-pin socket, DIN rail or surface mount
API 011 FS 11-pin finger safe socket, DIN rail or surface mount
API CLP1 Module hold-down spring for high vibration or
mobile applications
4-20 mA Input Alarm Trips with Loop Supply API 1005 G, API 1025 G
Applications
Description
The API 1005 G and API 1025 G are factory configured for a
4-20 mA current input and provides alarm contact outputs.
The 4-20 mA input provides power to the input loop via a
built-in 18 VDC loop power supply that can be used to power a
loop-powered transmitter or other passive input device. Heavy
duty relay contacts allow directl control of high capacity loads.
The API 1005 G provides a single setpoint adjustment and
DPDT relay contacts. The alarm output can be factory config-
ured for HI or LO operation, non-latching or latching, normal
or reverse acting. Top-accessible potentiometers are used to
adjust the alarm setpoint and deadband.
The API 1025 G contains two independent setpoints with two
SPDT relay contact outputs. The alarm output can be factory
configured for HI/HI, HI/LO, LO/HI or LO/LO operation, normal
acting or reverse acting. Top-accessible potentiometers are
used to adjust each alarm setpoint. Deadband is fixed at 1% of
span. Adjustable deadbands are optional.
LoopTracker and Alarm Status LEDs
API exclusive features include a LoopTracker LED that varies in
intensity with changes in the process input signal.
A red/green bi-color alarm status LED (two on the API 1025
G) visually indicate alarm status. These LEDs provide a quick
visual picture of your process at all times.
Output Test/Unlatch
API’s exclusive functional test button can be used to verify the
alarm and system operation. The output test button greatly
aids in saving time during initial startup and/or troubleshooting.
The HT latching option provides the additional function of
unlatching the alarm when the reset button is pressed. The
alarm will reset if the alarm condition not longer exists.
API 1025 G P 001 001
115 VAC
Your Required Input
Your Alarm Configuration
2.75"
Free Factory
I/O Setup!
Quick Link
api-usa.com/1005
API 1005 G
Variable Brightness Input LED
Bi-Color Relay LED
Deadband Adjustment
Setpoint Adjustment
Output Test Button
Reset w. HT Option
2.38"
1.75"
API 1025 G
AOption Deadband Adjustments
2.38"
1.75"
Variable Brightness Input LED
Bi-Color Relay 2 LED
Bi-Color Relay 1 LED
Setpoint 2 Adjustment
Setpoint 1 Adjustment
Output Test Button
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
HHHHH
HHHHHH
Made in USA
Hot Swappable
Plug-In Design
API 011
300 V Rating
API 011 FS
300 V Rating API CLP1
© 08-19
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
ABSOLUTE PROCESS INSTRUMENTS
Installation and Setup API 1005 G, API 1025 G
Precautions
WARNING! All wiring must be performed by a qualified electrician
or instrumentation engineer. See diagram for terminal designa-
tions and wiring examples. Consult factory for assistance.
WARNING! Avoid shock hazards! Turn signal input, output, and
power off before connecting or disconnecting wiring, or remov-
ing or installing module.
Précautions
ATTENTION! Tout le câblage doit être effectué par un élec-
tricien ou ingénieur en instrumentation qualifié. Voir le dia-
gramme pour désignations des bornes et des exemples de
câblage. Consulter l’usine pour assistance.
ATTENTION! Éviter les risques de choc! Fermez le signal
d’entrée, le signal de sortie et l’alimentation électrique avant
de connecter ou de déconnecter le câblage, ou de retirer ou
d’installer le module.
Alarm Configuration
API 1005 G relay operation is factory configured. The default
configuration is HI alarm normal acting. See model/serial num-
ber label for non-standard relay configuration options.
API 1025 G relay operation is factory configured, but internal
jumpers can be used to modify the alarm type as follows.
1. Unplug the module from the socket.
2. Remove the 4 screws from the module bottom and remove
the plastic case.
3. Unplug the circuit board with the test button from the base.
4. Note location of jumper block at top left of circuit board next
to test button. See diagram at right.
5. Place jumpers as indicated for desired alarm operation.
The standard HI/LO setting is with one jumper across the
two top pins or with no jumper at all. Never place a jumper
across the two bottom pins!
6. Replace board, cover, and screws.
Socket and Mounting
Install module in a protective panel or enclosure. Allow space
around module for air flow. Use API 011 or API 011 FS socket.
See specifications for maximum allowable socket voltages. The
socket clips to a standard 35 mm DIN rail or can be mounted to
a flat surface.
Input
The 4-20 mA input is factory configured and calibrated (at
24°C ±1°C), and does not require adjustment. See the model/
serial number label for input type, range, and options. See wir-
ing diagram for connections. Polarity must be observed. The
module provides 18 VDC unregulated power to the input loop.
Relay Output
See wiring diagram for connections. The module does not
provide power to the relay contacts.
Inductive loads (motors, solenoids, contactors, etc.) will greatly
shorten relay contact life unless an appropriate RC snubber
is installed.
Module Power
Check model/serial number label for module operating voltage
to make sure it matches available power.
When using DC power, polarity must be observed. The positive
(+) must be wired to terminal 1 and negative (–) must be wired
to terminal 3.
Setpoint
This multi-turn potentiometer (one for each setpoint on the API
1025 G) allows the operator to adjust the level at which the
alarm is activated. This control is adjustable from 0 to 100%
of the input range.
Deadband
The API 1005 G deadband potentiometer allows the alarm trip/
reset window to be adjusted symmetrically about the setpoint
from 1 to 100% of the span.
The deadband is fixed at 1% of span on the API 1025 G. The API
1025 G A with adjustable deadband option allows deadbands
to be adjusted symmetrically about each setpoint from 1 to
100% of the span.
Deadband allows the operator to fine tune the point at which
the alarm trips and resets. The deadband is typically used to
prevent chattering of the relays or false trips when the process
signal is unstable or changes rapidly.
Adjustments
To calibrate the alarm section, set the deadband control to the
minimum (counterclockwise). The deadband will be 1.0% of
input span in this case.
Set the signal source to a reference that represents the desired
trip point.
Adjust the setpoint control to the point at which the relay
changes state from a non-alarm to an alarm condition.
If a larger amount of deadband is desired turn the deadband
potentiometer clockwise. The deadband is symmetrical about
the setpoint; both transition points will change as deadband
is increased.
Alternately set the setpoint and deadband until the desired trip/
reset points are set.
Output Test Function
The functional test button toggles the alarm status independent
of the input when depressed. It verifies the alarm and system
operation. When released, the relays will return to their prior
states. This can be used as a diagnostic aid during initial start-
up or troubleshooting.
The API 1005 G with the HT latching alarm option, the test
button provides the additional function of unlatching the alarm
relays provide the alarm condition no longer exists.
Operation
The green LoopTracker®input LED provides a visual indication
that a signal is being sensed by the input circuitry of the mod-
ule. It also indicates the input signal strength by changing in
intensity as the process changes from minimum to maximum.
If the LED fails to illuminate, or fails to change in intensity as
the process changes, check the module power or signal input
wiring. Note that it may be difficult to see the LEDs under bright
lighting conditions.
The bi-color alarm LED provides a visual indication of the alarm
status. In all configurations, a green LED indicates a non-alarm
condition and a red LED indicates an alarm condition.
NOTE: Although the API 1005 G has a pair of relays, these
relays will energize and de-energize in unison.
The API 1025 G will accommodate independent relay operations.
High Alarm (Default, H, or HH)
The alarm relay changes state when the input exceeds the
deadband trip point. The relay resets when the input drops
below the deadband reset point unless the module has a
latching relay option. For a high alarm, the trip point is above
the reset point.
Low Alarm (L or LL)
The alarm relay changes state when the input goes below the
deadband trip point. The relay resets when the input exceeds
the deadband reset point unless the module has a latching relay
option. For a low alarm, the trip point is below the reset point.
HT Option (API 1005 G Only)
The module has a latching alarm with a push button reset. The
Test button or powering the module off can be used to reset the
alarm provided the alarm condition no longer exists.
HP Option (API 1005 G Only)
The module has a latching alarm with a power-off reset.
Module power must be turned off to reset alarms. The alarm
will reset provided the alarm condition no longer exists.
Normal Acting Alarms (Standard)
Normal acting alarms energize the relay coils in a non-alarm
condition and de-energize them in an alarm condition. This will
create an alarm condition if the module loses power.
Reverse Acting Alarms (R Option)
Reverse-acting alarms energize the relay coils in an alarm con-
dition and de-energize them in a non-alarm condition. There is
no alarm condition with module power off.
API 1025 G Alarm States with Normal Action HI/LO Alarms
No Alarm
GREEN Relay 1
8NC
7Com.
6NO
Relay 2
11 NC
10 Com.
9NO
GREEN GREEN
Relay 1
8NC
7Com.
6NO
Relay 2
11 NC
10 Com.
9NO
RED
HI Alarm LO Alarm
GREEN Relay 1
8NC
7Com.
6NO
Relay 2
11 NC
10 Com.
9NO
RED
Setpoint 1 = HI
Setpoint 2 = LO
(Standard)
API 1025 G
Setpoint 1 = HI
Setpoint 2 = HI
API 1025 G
Setpoint 1 = LO
Setpoint 2 = LO
API 1025 G
Setpoint 1 = LO
Setpoint 2 = HI
API 1025 G
API 1025 G Internal Alarm Configuration Jumpers
Switching Current (A)
Switching Voltage (V)
0 3 5 10 30 50 100 300 500
8
5
3
1
0.5
0.3
0.1
AC inductive load
(cos f= 0.4) AC resistive
load
DC inductive load
(L/R = 7 ms)
DC resistive
load
Relay Contact Ratings
API 1005 G Alarm States with Normal Action HI Alarm
Relay 1
8NC
7Common
6NO
Relay 2
11 NC
10 Common
9NO
GREEN
No Alarm
OFF
RED
Power Off
HI Alarm
Relay 1
8NC
7Common
6NO
Relay 2
11 NC
10 Common
9NO
api-usa.com
1220 American Way Libertyville, IL 60048
Phone: 800-942-0315 Fax: 800-949-7502
ABSOLUTE PROCESS INSTRUMENTS
API maintains a constant effort to upgrade and improve its products.
Specifications are subject to change without notice. See api-usa.com for
latest product information. Consult factory for your specific requirements.
WARNING: This product can expose you to chemicals includ-
ing lead and nickel, which are known to the State of California
to cause cancer or birth defects or other reproductive harm.
For more information go to www.P65Warnings.ca.gov
32111109
87654
(–) (+)
AC or
DC–
AC or
DC+
Contact Set 1
NC C NO
Module power
Socket
top view
Key down
when panel
mounting
NO C NC
Contact Set 2
See
api-usa.com/accessories
for socket information
and dimensions
Passive
4-20 mA
Device
NO = Normally Open
C = Common
NC = Normally Closed
(+)
18 VDC
* Do not make connections to
unused terminals!
To maintain
full isolation
avoid com-
bining power
supplies in
common
with input,
output, or
unit power.

This manual suits for next models

7

Other Absolute Process Instruments Security System manuals

Absolute Process Instruments APD 1400 User manual

Absolute Process Instruments

Absolute Process Instruments APD 1400 User manual

Absolute Process Instruments API 1080 G User manual

Absolute Process Instruments

Absolute Process Instruments API 1080 G User manual

Absolute Process Instruments APD 1431 User manual

Absolute Process Instruments

Absolute Process Instruments APD 1431 User manual

Absolute Process Instruments API 1000 G User manual

Absolute Process Instruments

Absolute Process Instruments API 1000 G User manual

Absolute Process Instruments API 1040 G Series User manual

Absolute Process Instruments

Absolute Process Instruments API 1040 G Series User manual

Absolute Process Instruments APD 1200 User manual

Absolute Process Instruments

Absolute Process Instruments APD 1200 User manual

Absolute Process Instruments Cecomp F16ADA User manual

Absolute Process Instruments

Absolute Process Instruments Cecomp F16ADA User manual

Popular Security System manuals by other brands

Siemens milltronics MFA 4P instruction manual

Siemens

Siemens milltronics MFA 4P instruction manual

urmet domus 1068 Installation and programming manual

urmet domus

urmet domus 1068 Installation and programming manual

GE Simon XTi installation guide

GE

GE Simon XTi installation guide

Indexa MA03 instructions

Indexa

Indexa MA03 instructions

New Cosmos USA DeNova Detect 807NIT user manual

New Cosmos USA

New Cosmos USA DeNova Detect 807NIT user manual

INSTEON 2420M user manual

INSTEON

INSTEON 2420M user manual

SuperSail Marine Alarm installation manual

SuperSail

SuperSail Marine Alarm installation manual

jacarta SP8 Test guide

jacarta

jacarta SP8 Test guide

King Pigeon S110 user manual

King Pigeon

King Pigeon S110 user manual

Smiths detection eqo operating instructions

Smiths detection

Smiths detection eqo operating instructions

SecEng SED-900 installation instructions

SecEng

SecEng SED-900 installation instructions

MediaShop M35445 instruction manual

MediaShop

MediaShop M35445 instruction manual

teko Astra-321 user guide

teko

teko Astra-321 user guide

Tyco DSC GS2055 installation manual

Tyco

Tyco DSC GS2055 installation manual

Sonic Alert HomeAware HA360MK Quick Reference and Installation Guide

Sonic Alert

Sonic Alert HomeAware HA360MK Quick Reference and Installation Guide

Paradox K656 Touch Sense quick start

Paradox

Paradox K656 Touch Sense quick start

Q-See QS218-411 Quick installation guide

Q-See

Q-See QS218-411 Quick installation guide

HIK VISION DS-19A Series manual

HIK VISION

HIK VISION DS-19A Series manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.