MOD9200LON Transceiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000695
Middleton, Wisconsin 53562 Page 2 of 33
www.workaci.com (888) 967-5224
License Agreement for Automation Components, Inc. Software
IMPORTANT-READ THESE TERMS CAREFULLY BEFORE INSTALLING THIS SOFTWARE.
THESE TERMS AND CONDITIONS ESTABLISH A CONTRACT BETWEEN YOU INDIVIDUALLY IF YOU ARE AGREEING TO IT IN YOUR OWN CAPACITY, OR IF
YOU ARE AUTHORIZED TO AGREE ON BEHALF OF YOUR COMPANY OR ANOTHER ORGANIZATION, BETWEEN THE ENTITIY FOR WHOSE BENEFIT YOU
ACT (“YOU”), AND ACI. BY OPENING THE SEALED CD ROM PACKAGE IN THIS MANUAL, YOU ACKNOWLEDGE THAT YOU HAVE READ THIS LICENSE
AGREEMENT, THAT YOU UNDERSTAND IT, AND THAT YOU AGREE TO BE BOUND BY ITS TERMS. IF YOU DO NOT AGREE TO THE TERMS AND
CONDITIONS OF THIS LICENSE AGREEMENT OR IF YOU DO NOT UNDERSTAND THEM, PROMPTLY RETURN THE UNOPENED PACKAGE AND ALL
ACCOMPANYING ITEMS TO ACI FOR A FULL REFUND.
1. Grant of License for Registered Users
ACI grants you a non-exclusive, non-transferable license to use the software program with which this license is distributed (the "Product"), including any documentation files
accompanying the Product ("Documentation") on any single computer. You may use the Product on a second computer so long as only one (1) is used at a time.
2. Backup Copy
You may make one backup copy of the Product. You may use it only to reinstall the Product.
3. Ownership
You have no ownership rights in the Product. Rather, you have a license to use the Product as long as this License Agreement remains in full force and e_ect. Ownership of the
Product, Documentation and all intellectual property rights therein shall remain at all times with ACI. Any use of the Product by any other person, business, corporation,
government organization or any other entity is strictly forbidden and is a violation of this License Agreement. You may not make more copies of the Product than speci_ed in this
agreement or allowed by applicable law, despite this limitation; publish the Product for others to copy; or rent, lease or lend the Product.
4. Copyright
The Product and Documentation contain material that is protected by United States Copyright Law as well as other intellectual property law and international treaty provisions. All
rights not granted to you herein are expressly reserved by ACI. You may not remove any proprietary notice of ACI from any copy of the Product or Documentation.
5. Restrictions
You may not publish, display, disclose, rent, lease, modify, loan, distribute, or create derivative works based on the Product or any part thereof. You may not reverse engineer,
decompile, translate, adapt, or disassemble the Product, nor shall you attempt to create the source code from the object code for the Product. You may not transmit the Product over
any network or between any devices, although you may use the Product to make such transmissions of other materials. You may access the Product from only one computer at a
time.
6. Limited Warranty
ACI WARRANTS THAT THE PRODUCT WILL OPERATE SUBSTANTIALLY IN ACCORDANCE WITH THE THEN CURRENT DOCUMENTATION. SHOULD THE
PRODUCT NOT SO OPERATE, YOUR EXCLUSIVE REMEDY, AND ACI'S SOLE OBLIGATION UNDER THIS WARRANTY, SHALL BE, AT ACI'S SOLE
DISCRETION, CORRECTION OF THE DEFECT OR REFUND OF LICENSE FEES PAID BY YOU FOR THE PERIOD DURING WHICH THE DEFECT WAS NOT
CORRECTED AND MATERIALLY AFFECTED THE OPERATION OF THE PRODUCT. ANY USE BY YOU OF THE PRODUCT IS AT YOUR OWN RISK. THIS
LIMITED WARRANTY IS THE ONLY WARRANTY PROVIDED BY ACI REGARDING THE PRODUCT. EXCEPT FOR THE LIMITED WARRANTY ABOVE, THE
PRODUCT IS PROVIDED "AS IS." TO THE MAXIMUM EXTENT PERMITTED BY LAW, ACI DISCLAIMS ALL OTHER WARRANTIES OF ANY KIND, EITHER
EXPRESSED OR IMPLIED, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE. ACI DOES NOT WARRANT THAT THE FUNCTIONS CONTAINED IN THE PRODUCT WILL MEET ANY REQUIREMENTS OR NEEDS YOU MAY
HAVE, OR THAT THE PRODUCT WILL OPERATE ERROR FREE, OR IN AN UNINTERRUPTED FASHION, OR THAT ANY DEFECTS OR ERRORS IN THE
PRODUCT WILL BE CORRECTED, OR THAT THE PRODUCT IS COMPATIBLE WITH ANY PARTICULAR PLATFORM. SOME JURISDICTIONS DO NOT ALLOW
THE WAIVER OR EXCLUSION OF IMPLIED WARRANTIES SO THEY MAY NOT APPLY TO YOU.
7. Limitation of Liability
IN NO EVENT WILL ACI BE LIABLE TO YOU OR ANY THIRD PARTY FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES (INCLUDING, WITHOUT
LIMITATION, INDIRECT, SPECIAL, PUNITIVE, OR EXEMPLARY DAMAGES FOR LOSS OF BUSINESS, LOSS OF PROFITS, BUSINESS INTERRUPTION, OR LOSS
OF BUSINESS INFORMATION) ARISING OUT OF THE USE OF OR INABILITY TO USE THE PROGRAM, OR FOR ANY CLAIM BY ANY OTHER PARTY, EVEN IF
ACI HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. ACI’S AGGREGATE LIABILITY WITH RESPECT TO ITS OBLIGATIONS UNDER THIS
AGREEMENT OR OTHERWISE WITH RESPECT TO THE PRODUCT AND DOCUMENTATION OR OTHERWISE SHALL NOT EXCEED THE AMOUNT OF THE
LICENSE FEE PAID BY YOU FOR THE PRODUCT AND DOCUMENTATION. BECAUSE SOME STATES/COUNTRIES DO NOT ALLOW THE EXCLUSION OR
LIMITATION OF LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES, THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
8. Export Restrictions
THIS LICENSE AGREEMENT IS EXPRESSLY MADE SUBJECT TO ANY LAWS, REGULATIONS, ORDERS, OR OTHER RESTRICTIONS ON THE EXPORT FROM
THE UNITED STATES OF AMERICA OF THE PRODUCT OR INFORMATION ABOUT SUCH PRODUCT WHICH MAY BE IMPOSED FROM TIME TO TIME BY THE
GOVERNMENT OF THE UNITED STATES OF AMERICA. YOU SHALL NOT EXPORT THE PRODUCT, DOCUMENTATION, OR INFORMATION ABOUT THE
PRODUCT AND DOCUMENTATION WITHOUT CONSENT OF ACI AND COMPLIANCE WITH SUCH LAWS, REGULATIONS, ORDERS, OR OTHER
RESTRICTIONS.
9. Termination
This License Agreement is e_ective until it is terminated. You may terminate this License Agreement at any time by destroying or returning to ACI all copies of the Product and
Documentation in your possession or under your control. ACI may terminate this License Agreement for any reason, including, but not limited to, if ACI _nds that you have
violated any of the terms of this License Agreement. Upon noti_cation of termination, you agree to destroy or return to ACI all copies of the Product and Documentation and to
certify in writing that all known copies, including backup copies, have been destroyed. All provisions relating to con_dentiality, proprietary rights, and non-disclosure shall survive
the termination of this Product License Agreement. Additionally, it is understood that termination of this Agreement will not e_ect a refund of any license fees paid or owed to
ACI.
10. General
This License Agreement shall be construed, interpreted and governed by the laws of the State of Wisconsin without regard to con_icts of law provisions thereof. The exclusive
forum for any disputes arising out of or relating to this License Agreement shall be an appropriate federal or state court sitting in the State of Wisconsin, USA. This License
Agreement shall constitute the entire Agreement between the parties hereto. Any waiver or modi_cation of this License Agreement shall only be e_ective if it is in writing and
signed by both parties hereto. If any part of this License Agreement is found invalid or unenforceable by a court of competent jurisdiction, the remainder of this License Agreement
shall be interpreted so as to reasonably e_ect the intention of the parties.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 3 of 33
www.workaci.com (888) 967-5224
Table of Contents
I. Introduction................................................................................................................................4
a. ACI MOD9200 Transceiver System ..................................................................................4
II. LON Transceiver Installation & Network Setup ...................................................................5
a. Transceiver Installation......................................................................................................5
b. Network Setup for Transceiver Configuration.................................................................6
c. Setting A New IP Address...................................................................................................6
d. Manually Resetting The Factory Default IP Address......................................................7
III. Configuration Software...........................................................................................................8
a. Configuration Software Description..................................................................................8
b. System Requirements..........................................................................................................8
c. Configuration Software Installation..................................................................................8
d. Creating A MOD9200 Configuration File.........................................................................9
e. Input Register Configuration...........................................................................................10
f. Digital Output (Coil) Register Configuration................................................................15
g. Analog Output (Holding) Register Configuration..........................................................17
h. Setting the Mesh Network ID for the repeater/router devices......................................20
i. Miscellaneous Menu..........................................................................................................20
j. Configuring The Transceiver For Internal Network.....................................................22
k. Sending The Configuration File To The MOD9200.......................................................24
l. Activating The Config File................................................................................................26
IV. Data Acquisition.....................................................................................................................27
a. LONWORKS Protocol......................................................................................................27
b. MOD9200LON LonWorks Transceiver Parameters.....................................................27
•The Input Registers.......................................................................................................28
•The Digital Output (Coil) Registers.............................................................................28
•The Analog Output (Holding) Registers......................................................................28
•The Alarm Registers......................................................................................................29
V. Quick Setup Instructions ........................................................................................................30
a. Configuration of the MOD9200LON...............................................................................30
b. Installing the FTT-10 Network.........................................................................................31
APPENDIX A ................................................................................................................................32
Available MOD9200LON models..............................................................................................32

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 4 of 33
www.workaci.com (888) 967-5224
I. Introduction
MOD9000LON
Wireless Transceiver
The ACI MOD9000LON LonWorks® network transceiver
utilizes reliable Spread Spectrum Radio technology. When used
with other ACI wireless sensors the system can transmit remote
sensor readings, and status/alarm indications to a centralized
networked monitoring station or controller without the need for
extensive wiring. The MOD9000LON is compatible with any
control panels or automation systems that utilize the LonWorks®
communication protocol.
a. ACI MOD9200 Transceiver System
•MOD9200LON Network Transceiver
•Receives input from up to 50 remote wireless sensor modules and/or wireless
output modules (RD2402 & RD2432) per Transceiver
•ACI signal repeater/router RR2552 can be used to extend the wireless
sensor transmission distance if needed
•FTT-10 (Free Topology Twisted Pair) phyical network connection
•MOD9200 Configuration Software
RepeaterIncreases
Transmission Distance, if
needed
Wireless Remote Digital/Analog
Input Modules& Energy Totalizer
Wireless OutsideAir
Temperature &
Humidity
Wireless Wall Temp. & Humidity
Sensor
Wireless Immersion &
Remote Sensors
LON FTT Network
MOD9200LON
LonWorks® Transceivers
Sub-SystemOverview
Wireless Digital
&Analog Outputs
Wireless Digital
(Relay) Outputs

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 5 of 33
www.workaci.com (888) 967-5224
II. LON Transceiver Installation & Network Setup
a. Transceiver Installation
•Choose a location close to the LonWorks® network connection awat from the ground.
•Mount the Transceiver on the wall using four #8 screws.
•24 VAC Input (500 mA nominal) - Connect 24VAC 60 Hz (no secondary ground) to the
input terminals using 20 AWG wire as shown in the product data sheet.
Figure 1
•FTT-10 - Use 20 or 22 gauge shielded twisted pair wire to connect the
Transceiver(Terminals “A” & “B”) to the LonWorks network (See Figure 1). The
connection of the FTT-10 network is not polarity sensitive and the designation (+) and (-)
on the board is not relevant in this case. There are two sets of terminal “A” & “B”. The
second set of terminals can be used to extend the FTT-10 network (if needed).
Default
IP
Jumper
TCP/IP
Connection (J2)
Connection
(J1)
24 VAC
Input
RS485
Terminals

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 6 of 33
www.workaci.com (888) 967-5224
b. Network Setup for Transceiver Configuration
•A network connection using a crossover cable is required during the initial setup of the
Transceiver for transporting the Transceiver Configuration File via FTP.
•Connect the MOD9200 Transceiver (J2) to a 10/100Base-T Ethernet network or use a
crossover cable to connect directly to the PC.
•Apply 24 VAC 60 Hz power to the MOD9200 Transceiver.
c. Setting A New IP Address
•The MOD9200 is shipped from the factory with an IP address of 192.168.0.1 and a
subnet mask of 255.255.255.0 .
Note: To initially connect to the Transceiver the networked PC must have a static IP
address in the form of 192.168.0.X where X is > 2 with a subnet mask of
255.255.255.0.
•The IP Address can be changed by changing the IP Address in the Transceiver Config
File. Open either an existing config file or a new config file using the ACI Programmer
Software.
•Click on Settings > TCP/IP Transport.
•Enter the new IP Address and Subnet Mask and click OK. The new IP Address will take
affect when the Config File is downloaded to the Transceiver. Please note the “Router
Setup-Webserver Only” window is not used by the MOD9200.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 7 of 33
www.workaci.com (888) 967-5224
•Our recommendation is not to change the default factory IP address of the transceiver,
since the Ethernet connection is used to configure the transceiver only and will not be
required when the LON network is up and running.
•Router Setup – Webserver Only – NOT USED.
d. Manually Resetting The Factory Default IP Address
•The Transceiver can manually be reset to the default IP Address by moving the jumper
(J6) from “Norm” to “Init”.
•Turn off the power to the Transceiver and move the jumper from “Norm” to “Init”. Turn
on power and the Transceiver can be communicated with using the Factory Default IP
Address 192.168.0.1 Subnet Mask 255.255.255.0. The Config File is no longer active
while the jumper is in the “Init” position . A new Config File can be downloaded to the
Transceiver if desired.
•To reactivate the Config File - turn off the power to the Transceiver and move the
jumper back to “Norm”. Turn the power back on and the Config File will become
active. The Transceiver will have the IP Address that was set in the Config File.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 8 of 33
www.workaci.com (888) 967-5224
III. Configuration Software
a. Configuration Software Description
•The data registers of the Transceiver need to be configured prior to use.
The configuration program “Trs Programmer.exe” can be found on CD ROM in
packaging, or can be downloaded from our website ‘www.workaci.com’. The download
instructions are included in the shipping document of the MOD9200 Transceiver. The
software will be used to configure the 3 different type of data registers as follows:
- Assign the Input Register function – Analog or Discrete
- Assign wireless Digital Output (Coil) Register function
- Assign wireless Analog Output (Holding) Register function
- Assign the register address
- Assign the Wireless Sensor ID and transmission channel
- Assign the data type
•The MOD9200LON Transceiver is pre-defined with fixed configurations. Please refer
to Appendix A for configuration map and details of different transceiver models.
b. System Requirements
•PC (Notebook or desktop) with Windows 98, XP, Vista, Windows 7, or Windows 8
•Ethernet connection
•10 MB of hard drive memory available
c. Configuration Software Installation
•Extract (or unzip) the Trs Programmer zip file and click start the ‘setup.exe’ program to
install the program. Follow the on screen instructions to complete the installation.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 9 of 33
www.workaci.com (888) 967-5224
d. Creating A MOD9200 Configuration File
•To create a new MOD9200 configuration file open the Trs Programmer by clicking on
Start > Programs > Trs Programmer 6.XX.
•To open a new configuration table Click on File > New Transceiver Config File. A blank
configuration table will open.
•The default startup is the Input Register configuration table and System Setup page.
•By clicking the “RegisterBank” tab, you can go to the Digital Output (Coil) register
configuration table or Analog Output (Holding) Register configuration table.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 10 of 33
www.workaci.com (888) 967-5224
e. Input Register Configuration
•Each row of the configuration table is a unique data register having eight special attributes.
REG
FUNCTION
--
Identifies the function of the register – Analog or
Digital (Discrete) Note: If selecting the Digital
(Discrete) function, be sure to set the appropriate
Digital Capture Time (Page 15)
REG ADDRESS
--
Assigns the address of the data register (0 to 99).
GROUP NAME
--
Assigns a group name to the data register (not used
by LON). Multiple data registers can have the
same group name. This is useful for monitoring
and data logging programs.
POINT NAME
--
Assigns a unique name to the data register to help
identify the location of the sensor/transmitter (Not
used by LON). Multiple point names can have the
same group name.
TRANSMITTER
ID
--
Assigns a wireless sensor/transmitter address to
the data register. Each wireless sensor is factory
configured with a unique hexadecimal address.
TRANS CHAN
--
Assigns a wireless sensor/transmitter data channel
to the data register. A wireless sensor/transmitter
may have up to four (4) analog channels and (4)
digital status/alarm channels.
DATA
FORMAT
LOG
--
--
Assigns the data type to the register – temperature
(RTD or Thermistor 20K), analog voltage, totalizer
or humidity. This register is left blank if the REG
FUNCTION is Digital (Discrete).
Not used for MOD9200LON

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 11 of 33
www.workaci.com (888) 967-5224
•First we will assign the REG FUNCTION by clicking in the REG FUNCTION cell to
open a drop down menu. Select the appropriate function.
•Use the mouse to move to the next column to assign the REG ADDRESS by clicking in
the cell. Before entering register addresses, ensure the “RegisterEntry” AutoSet is turned
off as shown:
•The data registers of the MOD9200 should be assigned non-consecutively based on
the network variable maps in Appendix A. User can assign specific data registers
needed and skip to the next applicable data register using the Trs Programmer software
setup tool.
•Refer to Appendix A for REG ADDRESS to specific MO9200LON model. Either
scroll to the appropriate address using the scroll bar or type the address in the cell and the
drop down menu will automatically scroll to that address.
Enter the Register address in the REG ADDRESS window and press down to enter.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 12 of 33
www.workaci.com (888) 967-5224
•Again use the mouse to move to the next column. Enter a GROUP NAME for the data
set by typing the group name in the cell.
Enter the name in the cell by using the mouse to click on the next column.
Note: DO NOT use commas or semicolons in the Group Name.
•Enter a POINT NAME for the data point by typing the name in the cell.
Enter the name in the cell by using the mouse to click on the next column.
Note: DO NOT use commas or semicolons in the Point Name.
•Assign a sensor/transmitter to the data register by clicking in the TRANSMITTER ID
cell to open a drop down menu. Use the scroll bar to scroll to the correct address or
automatically scroll to the address by typing the hexadecimal address in the cell. To
select the address, click on the appropriate ID in the drop down menu. Each ACI
transmitter is factory configured with a unique ID – refer to the sensor product data sheet
for the location of the transmitter ID.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 13 of 33
www.workaci.com (888) 967-5224
•Assign the appropriate sensor transmission channel to the data register by clicking in the
cell to open a drop down menu. Click on the appropriate transmission channel (01 to 04)
to select.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 14 of 33
www.workaci.com (888) 967-5224
The active transmission channels are factory configured as follows:
Device
Analog CH-01
Analog CH-02
Digital CH-01
WT2630A
Space Temp
(Therm 20K)
WT2630B
Space Temp
(Therm 20K)
SetPoint
(Analog)
Override (Discrete)
See page 15 to set the
Digital Capture Time
WT2630C
Space Temp
(Therm 20K)
Override (Discrete)
See page 15 to set the
Digital Capture Time
WH2630A
Humidity
WH2630B
Space Temp
(Therm 20K)
Humidity
OA2630A
Outdoor Temp
(Therm 20K)
Outdoor
Humidity
OST2630A
Outdoor Temp
(Therm 20K)
DT2630A
Duct Temperature
(Therm 20K)
DT2650A
Ave Temperature
(Therm 20K)
DH2630A
Duct Humidity
DH2630B
Duct Temperature
(Therm 20K)
Duct Humidity
FT2630A
Fluid Temperature
(Therm 20K)
RT2630A,B,C
See Device Label for Analog (4) and Digital (4) Configuration
RT2620A
See Device Label for Digital (4) Configuration
RT2602B
Digital (2) Inputs
SST2630A
Temperature (Therm 20K)
SST5630AE
Temperature (RTD 1K)
•Select the appropriate DATA FORMAT value by clicking in the cell to open a drop down
menu.
•To create a new data register row click on Row > Append. Continue to do this for each
row/data register that needs to be configured.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 15 of 33
www.workaci.com (888) 967-5224
•The completed configuration example for an office building is as follows:
•The columns may be resized by placing the cursor over one side of the column. When
the cursor changes to two arrows, hold down the left mouse button and drag the side of
the column to resize it.
f. Digital Output (Coil) Register Configuration
•Select the Digital Output (Coil) Register table by clicking the “RegisterBank” tab.
•First we will assign the REG ADDRESS by clicking in the cell. Before entering register
addresses, ensure the “RegisterEntry” AutoSet is turned off as shown:
•Enter the Register address in the REG ADDRESS window. The valid range is 0 to 49.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 16 of 33
www.workaci.com (888) 967-5224
•Again use the mouse to move to the next column. Enter a GROUP NAME, if desired, for
the data set by typing the group name in the cell.
Enter the name in the cell by using the mouse to click on the next column.
Note: DO NOT use commas or semicolons in the Group Name.
•Enter a POINT NAME, if desired, for the data point by typing the name in the cell. Enter
the name in the cell by using the mouse to click on the next column.
Note: DO NOT use commas or semicolons in the Point Name.
•Assign a sensor/transmitter to the data register by clicking in the TRANSMITTER ID
cell to open a drop down menu. This is the device ID of the remote output devices
(RD2402 & RD2432). Use the scroll bar to scroll to the correct address or automatically
scroll to the address by typing the hexadecimal address in the cell. To select the address
click on the appropriate ID in the drop down menu.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 17 of 33
www.workaci.com (888) 967-5224
•Assign the appropriate digital or relay output “TRANS CHAN” to the data register by
clicking in the cell to open a drop down menu. Click on the appropriate transmission
channel (01 to 04) to select.
•The active transmission channels or output number are factory set as follows:
Device
Digital
Analog
RD2402
1 to 2 for relay
#1 and relay #2
NA
Wireless relay
output module
RD2432
1 to 4 for relay
#1 to relay #4
1 to 4 for
analog output
1 to 4
Wireless digital &
analog output
module
g. Analog Output (Holding) Register Configuration
•Select the Analog Output (Holding) Register table by clicking the “RegisterBank” tab.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 18 of 33
www.workaci.com (888) 967-5224
•First we will assign the REG ADDRESS by clicking in the cell. Before entering register
addresses, ensure the “RegisterEntry” AutoSet is turned off as shown:
•Enter the Register address in the REG ADDRESS window. The valid range is 0 to 49.
•Again use the mouse to move to the next column. Enter a GROUP NAME, if desired, for
the data set by typing the group name in the cell.
Enter the name in the cell by using the mouse to click on the next column.
Note: DO NOT use commas or semicolons in the Group Name.
•Enter a POINT NAME, if desired, for the data point by typing the name in the cell. Enter
the name in the cell by using the mouse to click on the next column.
Note: DO NOT use commas or semicolons in the Point Name.

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 19 of 33
www.workaci.com (888) 967-5224
•Assign a sensor/transmitter to the data register by clicking in the TRANSMITTER ID
cell to open a drop down menu. This is the device ID of the remote output devices
(RD2432). Use the scroll bar to scroll to the correct address or automatically scroll to the
address by typing the hexadecimal address in the cell. To select the address click on the
appropriate ID in the drop down menu.
•Assign the appropriate digital or relay output “TRANS CHAN” to the data register by
clicking in the cell to open a drop down menu. Click on the appropriate transmission
channel (01 to 04) to select.
•The active transmission channels or output number are factory set as follows:
Device
Digital
Analog
RD2402
1 to 2 for relay
#1 and relay #2
NA
Wireless relay
output module
RD2432
1 to 4 for relay
#1 to relay #4
1 to 4 for
analog output
1 to 4
Wireless digital &
analog output
module

MOD9000LON Receiver Installation & Configuration
AUTOMATION COMPONENTS, INC Version : 1.0
2305 Pleasant View Road I0000675
Middleton, Wisconsin 53562 Page 20 of 33
www.workaci.com (888) 967-5224
h. Setting the Mesh Network ID for the repeater/router devices
•The mesh network ID of the MOD9200 Gateway can be set to specific network # from 1
to 64. The MOD9200 functions as a network coordinator. Any repeater/router that has
the same network ID will be able to communicate and channel sensor information to the
MOD9200
i. Miscellaneous Menu
•The transmitter timeout interval, default temperature degrees (C/F), and Digital Input
Capture Time are set globally for all sensors using the Miscellaneous Dialog Screen.
•Click on Settings > Miscellaneous
•Set the transmitter transmission timeout interval (requires a minimum of 30 min.) by
clicking in the Transmitter Timeout cell to open a drop down menu. Use the scroll bar to
scroll down to the appropriate value (1 to 60 min.) or type the value in the cell to
automatically scroll to the appropriate value. This will be used to generate an error
message if the transmitter fails to transmit in the specified time interval.
Other manuals for MOD9200LON LONWORKS
1
Table of contents
Other aci Transceiver manuals
Popular Transceiver manuals by other brands

Radiocrafts
Radiocrafts Tinymesh RC11 -TM Series manual

VHF Engineering
VHF Engineering HT 144B Manual guide

Dittel
Dittel FSG 40S manual

Kenwood
Kenwood TS-950S Digital instruction manual

Enforcement Technology Group
Enforcement Technology Group WRAPS Operation manual

Kenwood
Kenwood TR-851A instruction manual