sigfox ANALOG PWR - Guide utilisateur / User guide version V2.0.0
61
Page of 86
2.2.5 TEST Mode
This mode allows the user to perform tests of the product more quickly by reducing the time scales of the produc-
tion mode and modifying the behaviour of the LEDs.
It is obtained by positioning register S306 at the value 2 in the COMMAND mode. Once out of the command
mode,theproductreturnstothepreviouslydenedapplicationbehaviourbutwiththefollowingchanges:
- register S300: the periodicity of the Keep Alive frame is expressed in groups of twenty seconds instead
of tens of minutes. Hence in test mode when register 300 = 144, the Keep Alive frame is no longer sent every
144x10min=1440 minutes or 24h but every 144x20s=2880 seconds or 48 minutes.
- register S301: the periodicity of the sending of data (periodic mode) is expressed in groups of twenty
seconds instead of tens of minutes. Hence in test mode when register 301 = 1, the data frame is no longer sent
every 10min but every 20 seconds.
- In the event mode with transmission on threshold overrun the monitoring period of inspection by the
sensors, normally 10 minutes is now, in TEST mode, set to 100 seconds.
-TheLEDSalsohavedierentbehaviour,allowingavisualfeedbacktotheuserintheeventoftransmis-
sion and reception of frames (see paragraph 2.3 for more details).
A complete list of the registers can be found in paragraph 3.4.
E.g.:
Register Value encoding Value Result
S306 Decimal 2 The product is in TEST mode
S300 Decimal 72 The Keep Alive frame is sent every:
72x20=1440s = 24 minutes
S301 Decimal 6 Periodic mode with a period of 6x20 =
120s = 2 minutes
2.3. Operation of the LEDs
Mode LED red state LED green state
Transmission of frame (TEST mode
only) ON during the transmission cycle
Reception of frame (TEST mode
only) ON during the reception of a down-
link frame
Product in Park mode OFF OFF
Magnet detection process (1 to 6
seconds) OFF ON from detection of the magnet
up to a maximum of 1 second
Product start (after detection of
the magnet) OFF Rapidashing6cycles,100msON
/ 100 ms OFF
Switching to the Command mode Continuously lit Continuously lit
Battery level low Flashing (0.5s ON every 60s)
Product faulty (return to factory) Fixed ON
Product in production mode (TEST
mode only) 50ms ON / 50 s OFF 50ms ON / 50 s OFF (just before
the red LED)
Product in REPLI mode Flashing (100ms ON / 100ms OFF) x
2 every 5s