www.advancedco.com2
These instructions cover the installation, replacement and configuration of the AX-CTY module.
The AX-CTY is a module providing connection of Advanced Axis
AX
panels to a Local Energy Masterbox. The AX-CTY
module connects to any dedicated notification appliance circuit of an Axis
AX
panel installation (AX-LPD/AX-NAC
module or SLC loop NAC module).
Caution: Before installing or removing any module, remove all sources of power (AC and Battery).
Installing & Replacing the AX-CTY Module:
Installation:
Remove the AX-CTY module from its shipping package. Place in a standard electrical back box and wire to a
dedicated NAC circuit and Local Energy Masterbox.
Note: The AX-CTY module can be placed inside a standard electrical box with or without the AX-NACM (SLC
loop module).
Replacement:
Replacement is as simple as disconnecting the flying-leads of the AX-CTY module, that connect it to the dedicated
NAC circuit and Local Energy Masterbox, and reconnecting the removed field wiring to the new AX-CTY module.
AX-CTY Module Wiring:
The Red and Black flying- leads get wired to a dedicated notification appliance circuit (NAC), + and - respectively.
The two White flying-leads get wired to the Local Energy Masterbox trip coil (orange wires).
The NAC circuit must be programmed to activate on general alarm and be non-silenceable.
POWER LIMITED – Connect to power limited circuits only.
Wire range – 18-12 AWG
AX-CTY Module Specification
Operating Voltage 18 – 28 VDC
Operating Current
Quiescent
Alarm
0 mA
0.5 A (max.) for
1
/
2
second
Operating Temperature 32-120°F (0-48°C)
Environment Indoor, Dry
Humidity 10-95% (non-condensing)
Dimensions
1
/
2
”H x 1”W x 8
1
/
2
”L (includes wire length)
Weight 0.8 oz
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice
Doc Number: 682-150 AFS
Revision: 1