WISE-S100 Startup Manual 3
•Inthecongurationsection,userscangetmoreinformationandsetupthesensor.
-Mode:Enablethisfunctiontodetectblinkingfrequencywithinamaximumof3.3Hz.
-Delay Time: Onlyeectiveinon/o/blinkmodewhichisthedefaultsetting.
2 Secs Default:
Lightonoro>2secs=deviceonoro.
Lightonando<2secs=blinking.
Forexample,whenthedelaytimeissetto2seconds,itmeansthesensorsdeterminethelightshouldlastforatleast2
secondsinONorOFFmodeandduringthose2seconds,itwillbeBLINKING.
-Filter: Sensorsamplingrateis0.1sbydefault.
Thisfunctionensuresachangeofstateandavoidsnoisewhenthefunctionisenabled.
-Reading Illumination option: EnablethisfunctiontogettheLuxvalueofthesensor.
-Normal Status: Tosupportbetterpowersavingmode,pleasetickthenormalstatusofthelighttower.
Forexample,thelightisusuallyon,pleaseticknormalon.
-Low Illumination Limited Value:Lux<xmeansDark
-High Illumination Limited Value: Lux>xmeansLight
-Fast Blink Frequency Threshold:Frequency≥xmeansFastBlinking
Note: Tips for better accuracy
Please enable Lux reading rst.
Record the Lux value when the lights are on.
Lux(on)/2+100:HighIlluminationLimitValue.
Lux(on)/2-100:LowIlluminationLimitValue.
For example, when the lux is 1000, it is suggested to set the high illumination limit value at 600.
(This varies based on real case example)