Airbloc ACR User manual

ACR
RECESSED
AIRCURTAIN
ELECTRICALLY HEATED,
AMBIENT & LPHW
INSTALLATION AND OPERATING MANUAL
INDEX Section
General information ----------------------------------------------------------- 1
Dimensions ---------------------------------------------------------------------- 2
Technical Specification -------------------------------------------------------- 3
Wiring Details ------------------------------------------------------------------- 4
Installation Details -------------------------------------------------------------- 5
Servicing & Maintenance ----------------------------------------------------- 6
Spare Parts ---------------------------------------------------------------------- 7
Fault Finding -------------------------------------------------------------------- 8
Parts replacement ------------------------------------------------------------- 9
User Instructions --------------------------------------------------------------10
WARNINGS
1 This appliance must only be installed by a competent person in accordance with the requirements
of the Codes of Practice or the rules in force.
2 All external wiring MUST comply with the current IEE wiring regulations.
3 Warning this appliance must be earthed.
Instruction Manual.

2
Document Index.
1 Installation Requirements
1.1 Introduction
1.2 General
1.3 Electrical Supply
1.3.1 Electronic Controller
1.3.2 SmartElec2 Controller
1.4 Location
1.5 Clearance Distance
1.6 Health and Safety
1.7 Standards
2 Dimensions
2.1 ACR Air Curtain
2.2 Electronic Controller
2.3 Optional SmartElec2 Controller
3 Technical Specifications
3.1 Electrical Heated, Std Capacity 6&9kW 1P
3.2 Electrical Heated, Std Capacity 9-18kW
3.3 Electrical Heated, High Capacity 12-18kW
3.4 Ambient, Std Capacity
3.5 Ambient, High Capacity
3.6 LPHW, Std Capacity
3.7 LPHW, High Capacity
3.8 Electronic Controller
3.9 SmartElec2 Controller
4 Wiring Diagrams
4.1 Installer Wiring Electrically Heated 6&9kW 1P
4.2 Installer Wiring Electrically Heated 9&12kW
4.3 Installer Wiring Electrically Heated 18&24kW
4.4 Installer Wiring Ambient
4.5 Installer Wiring LPHW
4.6 Factory Wiring Electrically Heated 6&9kW 1P
4.7 Factory Wiring Electrically Heated 9&12kW
4.8 Factory Wiring Electrically Heated 18&24kW
4.9 Factory Wiring Ambient
4.10 Factory Wiring LPHW
4.11 Network Wiring Electronic Controller
4.12 Installer Wiring SmartElec2 Controller
4.13 Factory Wiring SmartElec2 Controller
4.14 Network Wiring SmartElec2 Controller
5 Installation Details
5.1 Mounting
5.2 Electrical Supply
5.3 Installation
5.4 Standard Controller
5.5 Option SmartElec2 Controller
5.6 LPHW only
5.7 Wiring
6 Servicing & Maintenance Instructions
7 Spare Parts
7.1 General
7.2 AC-ACR-PANEL Controller
7.3 SmartElec2 Controller
7.4 Heating mediums
8 Fault Finding Guide
8.1 General
8.2 Electrical Heated
8.3 Electronic Controller
8.4 Optional SmartElec2 Controller
8.4.1 Fault Code chart
8.4.2 LED indication
9 Replacing Parts
9.1 Electrical Element
9.1.1 SE
9.1.2 HE
9.2 Rotor and Motor
9.2.1 SE
9.2.2 HE
9.3 LPHW Coil
10 User and Operating Instructions
10.1 Keypad
10.2 Operation
10.3 Engineers Settings
10.3.1 Auto Mode
10.3.2 Door Switch Mode
10.4 Optional SmartElec2 Controller
10.4.1 Keypad
10.4.2 Operation
10.4.3 Network Addressing

3
1.1 Introduction
This instruction manual describes the Airbloc ACR
Recessed range of air curtains.
Models range from 1000mm to 2000mm in length,
in both Standard and High capacity and are
available in either Electrically heated, Ambient or
LPHW. They are designed for discreet positioning
in a suspended ceiling or bulkhead in the
doorways of retail or commercial premises.
Optional case for doorways with restricted space
and no suspended ceiling or bulkhead
Each air curtain is supplied with a fully electronic
controller giving multi fan and heat settings
(electrically operated units) via a simple key pad
which can be mounted up to 50m from the air
curtain. Optional BMS time control, external
thermostats and door interlocks can be installed.
The AC-ACR-PANEL programmer shown above
allows the user to control either a single air
curtain, or a network of up to 6 air curtains with
the same settings, and provides the following
functions:-
- Heat On Off or Auto via optional thermostat
- Off or Low, Medium and High Fan Speeds
For further details please refer to section 10.2
Alternatively on electrically heated models, an
optional SmartElec2 control system consists of a
base unit (installed within the air curtain) and a
program panel that can be installed remote from
the air curtain. Usually, the program panel is
mounted at a low level from the air curtain for user
access and to a maximum distance of 100m. The
base unit and program panel are linked by low
voltage cable as specified in these instructions.
The SmartElec2 factory fitted base unit
provides terminals for 3 phase supply connection
and the low voltage program panel wires. The
SmartElec2 base unit rapidly pulses energy to the
heating elements. This combined with the inbuilt
intelligent sensor control, maintains a fixed outlet
temperature, thereby reducing energy
consumption as compared to an air curtain without
the SmartElec2 control.
The SmartElec2 program panel shown above
allows the user to control either a single air
curtain, or a network of up to 16 air curtains, each
with different settings if required, and provides the
following functions:-
• Heat On or Off
• Off or Low, Medium and High Fan Speeds
• Air Outlet Temperature
For further details please refer to section 10.4
1.2 General
All installations must be in accordance with the
regulations in force in the country of use.
These instructions must be handed to the user on
completion of the installation.
Installers and service engineers must be able to
demonstrate competence and be suitably qualified
in accordance with the regulations in force in the
country of use.
To ensure continued and safe operation it is
recommended that the appliance is serviced
annually.
The manufacturer, offers a maintenance service.
Details are available on request.
The air curtain outlet grille and case air inlet slots
must not be obstructed during use.
1.3 Electrical Supply.
For full electrical loadings, please refer to the
individual technical data sheets within this manual.
It is recommended that the electrical supply to the
base unit in the air curtain is via an appropriate
switched isolator in accordance with the
regulations in force in the country of use and must
be via a fused isolator having a contact separation
of greater than 3mm in all poles.
General Information
fig.1. AC-ACR-PANEL program keypad
fig.2. SmartElec2 Controller
0 F1

4
BMS control, time switches, room thermostats and
door interlocks can be installed at the discretion
and responsibility of the installer.
All units must be wired in accordance with I.E.E
regulations for the Electrical Equipment of
Buildings and the installer should ensure that a
suitable isolating switch is connected in the mains
supply.
Warning
For safety reasons a good earth connection must
ALWAYS be made to the heater and control box.
1.3.1 Electronic controller
Electrically heated supply is either 230V 1 phase
(6 and 9kW options) or 415V 3 phase (9 to 24kW),
Neutral and Earth. Max cable inlet size is 4mm².
Ambient and LPHW supply is 230V 1 phase,
Neutral and Earth. Max cable inlet size is 4mm².
Remote unit is wired to the base unit via a Belden
9174 cable (or direct equiv).
1.3.2 SmartElec2 controller
Electrically heated supply is 415V 3 phase, neutral
and earth. Max cable inlet size is 10mm².
Remote unit is wired to the base unit via pre-wired
4core cable.
Networked air curtain interconnects via pre-wired
4 core cable.
1.4 Location.
Airbloc units should be installed horizontally
directly over the door opening. It is recommended
that the air curtain is installed on the inside of the
building, within the ceiling void or roof space.
Care must be taken to allow complete free air
movement into the inlet grilles of the unit to ensure
correct working operation of the air curtain. The
discharge opening should be as close to the top of
the door as possible and to cover the entire door
width.
Units can be mounted adjacent to each other to
cover the full door opening across wider
entrances.
1.5 Clearance distances
It is recommended that a minimum clearance of
100mm is allowed around the case sizes detailed
below. The clearance allows for cable entry and
prevents combustible surfaces overheating.
The minimum mounting height (floor to grille) is
1.8m. The recommended mounting height is 3m
for standard and 4m for high capacity models.
1.6 Health and Safety
Sole liability rests with the installer to ensure that
all site safety procedures are adhered to during
installation.
Sole liability rests with the installer to ensure that
protective safety wear such as hand, eye, ear and
head protection is used during installation of the
product.
Do not rest anything especially ladders against the
product.
1.7 Standards
Units conform to the European electrical standard
BS EN 60335-2-30 and to the following European
CE directives-
2006/95/EC - low voltage;
2004/108/EC - electromagnetic compatibility.

5
2. Dimensions.
Dimensional detail (mm)
Size ACR100SE6/9;
ACR100SW9;
ACR100SA
ACR150SE12;
ACR150SW12;
ACR150SA
ACR200SE18;
ACR200SW18;
ACR200SA
ACR120HE12;
ACR120HW12;
ACR120HA
ACR180HE18;
ACR180HW18;
ACR180HA
A 253 407
B 1220 1520 2020 1185 1785
C 1182 1482 1982 1150 1750
D 395 550
E 454 608
F 1205 1505 2005 1150 1750
G 1242 1542 2095 1210 1810
H 160 180
J 200 220
2.1 ACR Air Curtain
DIM 'F'
DIM 'G'
DIM 'C'
DIM 'B'
DIM 'A'
DIM 'D'
DIM 'E'
DIM 'H'
DIM 'J'

6
2.3 Optional SmartElec2 Controller dimensions
Cable
Entries
13.35
43.5
87.0
60.3crs
Cable
Entries
7.3560.3crs
7.3560.3crs
Earthing
point
75.0
2.2 AC-ACR-PANEL program keypad
SELECT
60.3crs
Fig.3. Surface mount
Fig.4. optional flush mount
146
85
38
12
40
20 crs
33
3380 crs
4 Holes Ø5mm
Cable/plug
Entry

7
3. Technical Specification.
* Motor current only at high speed
3.1 (Single Phase only) ACR100SE6-1PH ACR150SE6-1PH ACR200SE9-1PH
General Data
Maximum height M3.0
Door width M1.0 1.5 2.0
Heat medium Electric heated
Heat setting kW 3 / 6 4.5 / 9
Fan type / dia Crossflow / 100mm
Fan settings 3
Switching type AC-ACR-PANEL
Weight kg 28.0 34.0 49.0
Electrical Data
Supply voltage 230V 1ph 50Hz
Total load kW 6.1 9.1
amps 26.5 39.6
Motor power W60 90
Max Starting current* amps 0.96 1.5
Max Running current* amps 0.65 0.75
External fuse size amps amps 32 45
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Cable terminal size 6.0mm² Max
Mains terminal block position Separate din rail L1; N & E
Control terminal block position Right side of base unit terminals +12V, DATA & GND
Air Data
Air volume Low speed m³/h 1164 1475 2013
Medium speed m³/h 1405 1780 2432
High speed m³/h 1646 2085 2851
Air velocity Low @ 0M m/s 4.3 5.4
Medium @ 0M m/s 5.6 6.9
High @ 0M m/s 7.0 8.4
High @ 1M m/s 3.5 4.2
High @ 2M m/s 1.6 2.1
High @ 3M m/s 0.8 1.0
Delta T Low speed °C 17 13 26
Medium speed °C 15 11 23
High speed °C 13 920
Noise level @ 1M
Free field Low speed dBA 59
Medium speed dBA 62
High speed dBA 64
Dims Data
Length mm 1182 1482 1982
Depth (width) mm 395
Total height* mm 200
Outlet length mm 1125 1425 1945
Outlet depth (width) mm 85
Grille height mm 40
Mounting bracket centres length mm 1220 1520 2020
Side to 1st bracket centre mm 18
Mounting bracket centres height mm Flush with top of unit
Top to 1st bracket centre mm Flush with top of unit

8
* Motor current only at high speed
**Suffix with –SM for SmartElec2 Energy Saving Control.
3.2 ACR100SE9 ACR150SE12 ACR200SE18
General Data
Maximum height M3.0
Door width M1.0 1.5 2.0
Heat medium Electric heated
Heat setting kW 4.5 / 9 6 / 12 9 / 18
Fan type / dia Crossflow / 100mm
Fan settings 3
Switching type AC-ACR-PANEL / SmartElec2
Weight kg 28.0 34.0 49.0
Electrical Data
Supply voltage 415V 3ph 50Hz
Total load kW 9.1 12.1 18.1
A/pha 12.6 16.8 25.2
Motor power W60 90
Max Starting current* amps 0.96 1.5
Max Running current* amps 0.65 0.75
External fuse size amps A/pha 16 20 32
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Cable terminal size 6.0mm² Max
Mains terminal block position Bottom of base unit.
Terminals N; L1; L2 & L3 Separate din rail
E: N; L1; L2 & L3
Control terminal block position Right side of base unit terminals +12V, DATA & GND
*** SmartElec Energy Saving Control pt. no. SELEC2BU
SmartElec Energy Saving Control wiring 4 core pre-wired
Cable terminal size 10.0mm² Max
Mains terminal block position SmartElec2 Base Unit - terminals N; L1; L2 & L3
Control terminal block position SmartElec2 Base Unit
Air Data
Air volume Low speed m³/h 1164 1475 2013
Medium speed m³/h 1405 1780 2432
High speed m³/h 1646 2085 2851
Air velocity Low @ 0M m/s 4.3 5.4
Medium @ 0M m/s 5.6 6.9
High @ 0M m/s 7.0 8.4
High @ 1M m/s 3.5 4.2
High @ 2M m/s 1.6 2.1
High @ 3M m/s 0.8 1.0
Delta T Low speed °C 26 25 21
Medium speed °C 23 22 20
High speed °C 20 19 19
Noise level @ 1M
in free field Low speed dBA 59
Medium speed dBA 62
High speed dBA 64
Dims Data
Length mm 1182 1482 1982
Depth (width) mm 395
Total height* mm 200
Outlet length mm 1125 1425 1945
Outlet depth (width) mm 85
Grille height mm 40
Mounting bracket centres length mm 1220 1520 2020
Side to 1st bracket centre mm 18
Mounting bracket centres height mm Flush with top of unit
Top to 1st bracket centre mm Flush with top of unit
4.0mm² Max

9
3.3 ACR120HE12 ACR180HE18
General Data
Maximum height M4.0
Door width M1.0 1.5
Heat medium Electric heated
Heat setting kW 6 / 12 9 / 18
Fan type / dia Crossflow / 150mm
Fan settings 3
Switching type AC-ACR-PANEL / SmartElec2
Weight kg 38.0 55.0
Electrical Data
Supply voltage 415V 3ph 50Hz
Total load kW 12.4 18.4
A/pha 17.3 25.6
Motor power W370
Max Starting current* amps 5.0
Max Running current* amps 2.1
External fuse size amps A/pha 20 32
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Mains terminal block position Base unit
N; L1; L2 & L3 Separate din rail
E; N; L1; L2 & L3
Control terminal block position Right side of base unit terminals +12V, DATA & GND
*** SmartElec Energy Saving Control pt. no. SELEC2BU
SmartElec Energy Saving Control wiring 4 core pre-wired
Mains terminal block position SmartElec2 Base Unit - terminals N; L1; L2 & L3
Control terminal block position SmartElec2 Base Unit
Air Data
Air volume Low speed m³/h 1300 1600
Medium speed m³/h 1850 2400
High speed m³/h 2300 3300
Air velocity Low @ 0M m/s 6.0
Medium @ 0M m/s 8.5
High @ 0M m/s 11.0
High @ 1M m/s 5.4 5.5
High @ 2M m/s 3.6 3.7
High @ 3M m/s 2.6 2.5
High @ 4M m/s 1.5 1.6
Delta T Low speed °C 35 35
Medium speed °C 28 27
High speed °C 22 22
Noise level @ 3M
in free field Low speed dBA 50
Medium speed dBA 55
High speed dBA 60
Dims Data
Length mm 1150 1750
Depth (width) mm 550
Total height* mm 227
Outlet length mm 1090 1690
Outlet depth (width) mm 85
Grille height mm 6
Mounting bracket centres length mm 1185 1785
Side to 1st bracket centre mm 17.5
Mounting bracket centres height mm Flush with top of unit
Top to 1st bracket centre mm Flush with top of unit
Cable terminal size 10.0mm² Max
Cable terminal size 4.0mm² Max 6.0mm² Max
* Motor current only at high speed
**Suffix with –SM for SmartElec2 Energy Saving Control.

10
* Motor current only at high speed
3.4 ACR100SA ACR150SA ACR200SA
General Data
Maximum height M3.0
Door width M1.0 1.5 2.0
Heat medium Ambient
Fan type / dia Crossflow / 100mm
Fan settings 3
Switching type AC-ACR-PANEL
Weight kg 28 34 49
Electrical Data
Supply voltage 230V 1ph 50Hz
Total load kW 0.06 0.09
amps 0.26 0.4
Motor power W60 90
Max Starting current* amps 0.96 1.5
Max Running current* amps 0.65 0.75
External fuse size amps amps 3
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Mains terminal block position Base unit L1; N + E
Control terminal block position Right side of base unit terminals +12V, DATA & GND
Air Data
Air volume Low speed m³/h 1164 1475 2013
Medium speed m³/h 1405 1780 2432
High speed m³/h 1646 2085 2851
Air velocity Low @ 0M m/s 4.3 5.4
Medium @ 0M m/s 5.6 6.9
High @ 0M m/s 7.0 8.4
High @ 1M m/s 3.5 4.2
High @ 2M m/s 1.6 2.1
High @ 3M m/s 0.8 1.0
Noise level @ 1M
in free field Low speed dBA 59 62
Medium speed dBA 62 64
High speed dBA 64 66
Dims Data
Length mm 1182 1482 1982
Depth (width) mm 395
Total height* mm 200
Outlet length mm 1125 1425 1945
Outlet depth (width) mm 85
Grille height mm 40
Mounting bracket centres length mm 1220 1520 2020
Side to 1st bracket centre mm 18
Mounting bracket centres height mm Flush with top of the unit
Top to 1st bracket centre mm Flush with top of the unit
Cable terminal size 4.0mm² Max

11
3.5 ACR120HA ACR180HA
General Data
Maximum height M4.0
Door width M1.0 1.5
Heat medium Ambient
Fan type / dia Crossflow / 150mm
Fan settings 3
Switching type AC-ACR-PANEL
Weight kg 40.0 58.0
Electrical Data
Supply voltage 230V 1ph 50Hz
Total load kW 0.4
amps 1.6
Motor power W370
Max Starting current* amps 5.0
Max Running current* amps 2.1
External fuse size amps Amps 10
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Mains terminal block position Base unit L1; N + E
Control terminal block position Right side of base unit terminals +12V, DATA & GND
Air Data
Fan setting 2
Air volume Low speed m³/h 1300 1600
Medium speed m³/h 1850 2400
High speed m³/h 2300 3300
Air velocity Low @ 0M m/s 6.0
Medium @ 0M m/s 8.5
High @ 0M m/s 11.0
High @ 1M m/s 5.5 5.2
High @ 2M m/s 3.7 3.6
High @ 3M m/s 2.5 2.4
High @ 4M m/s 1.6 1.4
Noise level @ 3M
in free field Low speed dBA 50
Medium speed dBA 55
High speed dBA 60
Dims Data
Length mm 1150 1750
Depth (width) mm 550
Total height* mm 227
Outlet length mm 1090 1690
Outlet depth (width) mm 85
Grille height mm 6
Mounting bracket centres length mm 1185 1785
Side to 1st bracket centre mm 17.5
Mounting bracket centres height mm Flush with top of unit
Top to 1st bracket centre mm Flush with top of unit
Cable terminal size 4.0mm² Max
* Motor current only at high speed

12
* Motor current only at high speed
3.6 ACR100SW9 ACR150SW12 ACR200SW18
General Data
Maximum height M3.0
Door width M1.0 1.5 2.0
Heat medium LPHW
Heat setting kW 912 18
Fan type / 100mm Crossflow / 100mm
Fan settings 3
Switching type AC-ACR-PANEL
Weight kg 28 34 49
Electrical Data
Supply voltage 230V 1ph 50Hz
Total load kW 0.06 0.09
amps 0.26 0.4
Motor power W60 90
Max Starting current* amps 0.96 1.5
Max Running current* amps 0.65 0.75
External fuse size amps amps 3
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Mains terminal block position Base unit L1; N + E
Control terminal block position Right side of base unit terminals +12V, DATA & GND
Air Data
Air volume Low speed m³/h 1164 1475 2013
Medium speed m³/h 1405 1780 2432
High speed m³/h 1646 2085 2851
Air velocity Low @ 0M m/s 4.3 5.4
Medium @ 0M m/s 5.6 6.9
High @ 0M m/s 7.0 8.4
High @ 1M m/s 3.5 4.2
High @ 2M m/s 1.6 2.1
High @ 3M m/s 0.8 1.0
Delta T Low speed °C 26 25 21
Medium speed °C 23 22 20
High speed °C 20 19 19
Noise level @ 1M
in free field Low speed dBA 59 62
Medium speed dBA 62 64
High speed dBA 64 66
LPHW Data
LPHW flow l/s 0.20 0.40
Fluid pressure drop kPA 3.8 17.6 20
Flow & return connection mm 15 22
Inlet temp °C 82
Outlet temp °C 71
Dims Data
Length mm 1182 1482 1982
Depth (width) mm 395
Total height* mm 200
Outlet length mm 1125 1425 1945
Outlet depth (width) mm 85
Grille height mm 40
Mounting bracket centres length mm 1220 1520 2020
Side to 1st bracket centre mm 18
Mounting bracket centres height mm Flush with top of the unit
Top to 1st bracket centre mm Flush with top of the unit
Cable terminal size 4.0mm² Max

13
3.7 ACR120HW12 ACR180HW18
General Data
Maximum height M4.0
Door width M1.0 1.5
Heat medium LPHW
Heat setting kW 12 18
Fan type / dia Crossflow / 150mm
Fan settings 3
Switching type AC-ACR-PANEL
Weight kg 40.0 58.0
Electrical Data
Supply voltage 230V 1ph 50Hz
Total load kW 0.4
amps 1.6
Motor power W 370
Max Starting current* amps 5.0
Max Running current* amps 2.1
External fuse size amps amps 10
Programmer keypad pt. no. AC-ACR-PANEL
Program keypad control wiring Belden 9174 (or similar)
Mains terminal block position Base unit L1; N + E
Control terminal block position Right side of base unit terminals +12V, DATA & GND
Air Data
Air volume Low speed m³/h 1600 2900
Medium speed m³/h 2400 4100
High speed m³/h 3300 5000
Air velocity Low @ 0M m/s 6.0
Medium @ 0M m/s 8.5
High @ 0M m/s 11.0
High @ 1M m/s 5.5 5.2
High @ 2M m/s 3.7 3.6
High @ 3M m/s 2.5 2.4
High @ 4M m/s 1.6 1.4
Delta T Low speed °C 35 35
Medium speed °C 28 27
High speed °C 22 22
Noise level @ 3M
in free field Low speed dBA 50
Medium speed dBA 55
High speed dBA 60
LPHW Data
LPHW Flow l/s 0.40 0.53
Fluid Pressure Drop kPA 23 24
Flow & Return connection mm 15 15
Inlet temp °C 82
Outlet temp °C 71
Dims Data
Length mm 1150 1750
Depth (width) mm 550
Total height* mm 227
Outlet length mm 1090 1690
Outlet depth (width) mm 85
Grille height mm 6
Mounting bracket centres length mm 1185 1785
Side to 1st bracket centre mm 17.5
Mounting bracket centres height mm Flush with top of unit
Top to 1st bracket centre mm Flush with top of unit
Cable terminal size 4.0mm² Max
* Motor current only at high speed

14
3.9 SmartElec2 Controller
General Data
Sensor input NTC
Control Setpoint 16 to 35 ºC in steps of 1 degree
Temperature Control Proportional with 1ºC hysteresis
Minimum Power 0% to 99 %
Cycle time 2 seconds fixed
Protection 2 x high speed fuse for the protection of the heater switching devices
Fan Output 3 off Relay for High, Medium and Low Fan setting 3A max 240Vac
Connection
Screw terminals 5 for supply, 3 for heater output, 4 for fan output, 2 for
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for
external sensor, 2 for door
Supply 415 Vrms +/-15% 50/60Hz 5VA max.
Dimensions Program panel 146mm(L) x 85mm(W) x 38mm(D) max.
Mounting positions Program panel fixing centres 80mm x 20mm
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
Display Three 7-segment LCD red for parameter display
Push buttons 3 positive feedback tactile push buttons
3.8 Program Controller
General Data
Sensor input NTC
Protection 2 x ‘slow blow’ fuse for the protection of the heater switching devices.
Fan Output 3 off Relay for High, Medium and Low Fan setting 3A max 240Vac
Connection
Screw terminals 4 for supply, 6 for heater output, 4 for fan output, 2 for
BMS (time) control, 2 for sensor input, 2 for external thermal trip, 2 for
external door switch.
Supply 230V 1Ph or 415 3Ph dependent on model type.
Dimensions Program panel 88mm(L) x 88mm(W) max.
Mounting positions Program panel fixing centres 60.3mm
Temperature 5 to 50 ºC operating; -20 to 65 ºC storage
Display Three 7-segment LCD red for parameter display
Push buttons 3 positive feedback tactile push buttons

15
T1
T2
B2
D2
S2
S1
D1
B1
DATA
GND
+12V
BASE UNIT
(located in air curtain)
230V 50Hz
Mains Supply
Chassis
Earth
PROGRAM PANEL
(rear view shown)
External
Switch
J1
Remove link J1 for
external time switch
DATA
GND
+12V
F1
F2
F3
N
N
AC1-T3
L3
AC2-T3
AC1-T2
L2
AC2-T2
AC1-T1
L1
AC2-T1
Door
Switch Sensor screen
Contractors
Terminal
4. Wiring Diagrams.
F1
F2
Terminal Description Cable
N Neutral 6mm² max
L1 1 phase supply 6mm² max
Pcb Terminal Description
+12V Supply to remote unit
DATA Data to remote unit
GND(s) 0v Terminal
D1, D2 Option door contact
B1, B2 Option BMS switch
S1, S2 Option internal/external sensor
Pcb Fuses Rating (A)
F1 T2A (slow blow)
F2 T3.15A (slow blow)
Cable
1.0mm2
max
4.1 Installer Wiring - Electrically Heated 6 & 9kW SINGLE PHASE ONLY
The program panel is connected to the base unit via a set of 3 way connectors marked "+12V”, “DATA”
and “GND". Interconnecting wiring is via Belden 8132 or equivalent cable as shown. Max length 50m.
It is recommended that this control cable is run separately
within its own trunking to avoid external interference.
Door switch to be volt free and wired normally closed contacts
to terminals D1, D2. (Contacts
broken when door is open).
External switch (ie BMS enable) to
be volt free and wired via normally
open contacts to terminals B1, B2.
Optional internal/external sensor
to be wired to terminals S1, S2.
Protection
External circuit breaker with the appropriate
rating should be installed for the protection
of the installation.

16
T1
T2
B2
D2
S2
S1
D1
B1
DATA
GND
+12V
BASE UNIT
(located in air curtain)
415V 50Hz
Mains Supply
Chassis
Earth
PROGRAM PANEL
(rear view shown)
External
Switch
J1
Remove link J1 for
external time switch
DATA
GND
+12V
F1
F2
F3
N
N
AC1-T3
L3
AC2-T3
AC1-T2
L2
AC2-T2
AC1-T1
L1
AC2-T1
Door
Switch Sensor screen
Pcb Terminal Description Cable
N Neutral 4mm² max
L1 3 phase supply 4mm² max
L2 3 phase supply 4mm² max
L3 3 phase supply 4mm² max
+12V Supply to remote unit
DATA Data to remote unit
GND(s) 0v Terminal
D1, D2 option door contact
B1, B2 option BMS switch
S1, S2 option internal/external Sensor
Pcb Fuses Rating (A)
F1 T2A (slow blow)
F2 T3.15A (slow blow)
Cable
1.0mm2
max
4.2 Installer Wiring - Electrically Heated 9 & 12kW THREE PHASE ONLY
The program panel is connected to the base unit via a set of 3 way connectors marked "+12V”, “DATA”
and “GND". Interconnecting wiring is via Belden 8132 or equivalent cable as shown. Max length 50m.
It is recommended that this control cable is run separately
within its own trunking to avoid external interference.
Door switch to be volt free and wired normally closed contacts
to terminals D1, D2. (Contacts
broken when door is open).
External switch (ie BMS enable) to
be volt free and wired via normally
open contacts to terminals B1, B2.
Optional internal/external sensor to
be wired to terminals S1, S2.
Protection
External circuit breaker with the appropriate
rating should be installed for the protection
of the installation.
F1
F2

17
T1
T2
B2
D2
S2
S1
D1
B1
DATA
GND
+12V
BASE UNIT
(located in air curtain)
415V 50Hz
Mains Supply
Chassis
Earth
PROGRAM PANEL
(rear view shown)
External
Switch
J1
Remove link J1 for
external time switch
DATA
GND
+12V
F1
F2
F3
N
N
AC1-T3
L3
AC2-T3
AC1-T2
L2
AC2-T2
AC1-T1
L1
AC2-T1
Door
Switch Sensor screen
Contractors
Terminal
Terminal Description Cable
N Neutral 6mm² max
L1 3 phase supply 6mm² max
L2 3 phase supply 6mm² max
L3 3 phase supply 6mm² max
Pcb Terminal Description Cable
+12V Supply to remote unit
DATA Data to remote unit
GND(s) 0v Terminal
D1, D2 Option door contact
B1, B2 Option BMS switch
S1, S2 Option internal/external sensor
Pcb Fuses Rating (A)
F1 T2A (slow blow)
F2 T3.15A (slow blow)
Cable
1.0mm2
max
Protection
External circuit breaker with the appropriate
rating should be installed for the protection
of the installation.
4.3 Installer Wiring - Electrically Heated 18kW THREE PHASE ONLY
The program panel is connected to the base unit via a set of 3 way connectors marked "+12V”, “DATA”
and “GND". Interconnecting wiring is via Belden 8132 or equivalent cable as shown. Max length 50m.
It is recommended that this control cable is run separately
within its own trunking to avoid external interference.
Door switch to be volt free and wired normally closed contacts
to terminals D1, D2. (Contacts broken when door is open).
External switch (ie BMS enable) to
be volt free and wired via normally
open contacts to terminals B1, B2.
Optional internal/external sensor
to be wired to terminals S1, S2.
F1
F2

18
T1
T2
B2
D2
S2
S1
D1
B1
DATA
GND
+12V
BASE UNIT
(located in air curtain)
230V 50Hz
Mains Supply
Chassis
Earth
PROGRAM PANEL
(rear view shown)
External
Switch
J1
Remove link J1 for
external time switch
DATA
GND
+12V
F1
F2
F3
N
N
AC1-T3
L3
AC2-T3
AC1-T2
L2
AC2-T2
AC1-T1
L1
AC2-T1
Door
Switch screen
Pcb Terminal Description Cable
N Neutral 4mm² max
L 1 phase supply 4mm² max
+12V Supply to remote unit
DATA Data to remote unit
GND(s) 0v Terminal
D1, D2 Option door contact
B1, B2 Option BMS switch
Pcb Fuses Rating (A)
F1 T2A (slow blow)
F2 T3.15A (slow blow)
Cable
1.0mm2
max
Protection
External circuit breaker with the appropriate
rating should be installed for the protection
of the installation.
4.4 Installer Wiring - Ambient
The program panel is connected to the base unit via a set of 3 way connectors marked "+12V”, “DATA”
and “GND". Interconnecting wiring is via Belden 8132 or equivalent cable as shown. Max length 50m.
It is recommended that this control cable is run separately
within its own trunking to avoid external interference.
Door switch to be volt free and wired normally closed contacts
to terminals D1, D2. (Contacts
broken when door is open).
External switch (ie BMS enable) to
be volt free and wired via normally
open contacts to terminals B1, B2.
F1
F2

19
T1
T2
B2
D2
S2
S1
D1
B1
DATA
GND
+12V
BASE UNIT
(located in air curtain)
230V 50Hz
Mains Supply
Chassis
Earth
PROGRAM PANEL
(rear view shown)
External
Switch
J1
Remove link J1 for
external time switch
DATA
GND
+12V
F1
F2
F3
N
N
AC1-T3
L3
AC2-T3
AC1-T2
L2
AC2-T2
AC1-T1
L1
AC2-T1
Door
Switch Sensor screen
Protection
External circuit breaker with the appropriate
rating should be installed for the protection
of the installation.
230V 50Hz
Mains Supply
3 Port Valve
Terminal Description Cable
N Neutral 4mm² max
L1 1 phase supply 4mm² max
Pcb Terminal Description
12V Supply to remote unit
DATA Data to remote unit
GND(s) 0v Terminal
D1, D2 Option door contact
B1, B2 Option BMS switch
S1, S2 Option internal/external sensor
Pcb Fuses Rating (A)
F1 T2A (slow blow)
F2 T3.15A (slow blow)
Cable
1.0mm2
max
4.5 Installer Wiring - LPHW
The program panel is connected to the base unit via a set of 3 way connectors marked "+12V”, “DATA”
and “GND". Interconnecting wiring is via Belden 8132 or equivalent cable as shown. Max length 50m.
It is recommended that this control cable is run separately
within its own trunking to avoid external interference.
Door switch to be volt free and wired normally closed contacts
to terminals D1, D2. (Contacts
broken when door is open).
External switch (ie BMS enable) to
be volt free and wired via normally
open contacts to terminals B1, B2.
Optional internal/external sensor to
be wired to terminals S1, S2.
F1
F2

20
Fan Motor
Overheat
AC1-T3
T1
T2
B2
D2
S2
S1
D1
B1
DATA
GND
+12V
L3
AC2-T3
AC1-T2
L2
AC2-T2
AC1-T1
L1
AC2-T1
F1
F2
F3
N
N
Elements
Contractors
Terminal
Elements
J1
L(M)
R(M)
R(B)
L(B)
R(T)
L(T)
R= RIGHT SIDE
L= LEFT SIDE
T= TOP ELEMENT
M= MIDDLE ELEMENT
B= BOTTOM ELEMENT
L
N
E
4.6 Factory Wiring - Electrically heated 6 & 9kW SINGLE PHASE ONLY
The element output is connected to the right and left
side of each terminal block marked "AC1-T1”, “AC2-T1”,
AC1-T2”, “AC2-T2”, “AC1-T3” and “AC2-T3”
The fan output is connected to a 4 way connector
marked "N”, “F1”, “F2” and “F3".
The thermal trip is connected to a 2 way connector
marked "T1" & “T2”
Pcb Terminal Description
L1 Heater Elements one third
L2 Heater Elements one third
L3 Heater Elements one third
T1 Thermal Overheat trip
T2 Thermal Overheat trip
N Neutrals
F1 Fan - low speed
F2 Fan - medium speed
F3 Fan - high speed
J1 Factory BMS link
This manual suits for next models
16
Table of contents
Other Airbloc Heater manuals
Popular Heater manuals by other brands

L.B. White
L.B. White Guardian 60 Assembly and installation instructions