AKO AKO-16624 User manual

AKO-16624
Temperature and moisture controller for cold room store
User Manual
GB 1662H402 Ed.01

2
Index
AKO Electromecánica thanks and congratulates you for purchasing our product, in whose development and manufacture the most innovative
technology has been used, as well as strict production and quality control processes.
Our commitment to satisfy our customers and our continuous efforts to improve every day can be seen in the various quality certifications we
have obtained.
This is a high performance, high technology product. The operation and final performance of the equipment depend on proper planning,
installation, configuration and commissioning. Read this manual carefully before installation, and always follow its instructions.
Only qualified personnel should install or perform technical assistance on this product.
This product is designed to be used in the applications described in the product manual. AKO Electromecánica gives no guarantee of its
operation in any use not foreseen in the manual, and is not responsible for any damage resulting from improper use, configuration,
installation or commissioning.
It is the responsibility of the installer and the customer to comply with and ensure others comply with all regulations applicable to
installations incorporating our products. AKO Electromecánica is not responsible for any damage caused by non-compliance with regulations.
Follow strictly the instructions given in this manual.
To maximise the service life of our equipment, these recommendations should be followed:
Do not expose electronic equipment to dust, dirt, water, rain, humidity, high temperatures, chemicals or corrosive substances of any sort.
Do not submit the equipment to blows or vibrations nor try to manipulate it differently from shown in the manual.
Never exceed the specifications and limitations indicated in the manual.
Always respect the specified ambient working and storage conditions.
During and after installation, avoid leaving loose, broken, unprotected or damaged wiring, since they might constitute a risk for the
equipment and its users.
AKO Electromecánica reserves the right to make any non-metrology modification to the documentation or the equipment without previous
notice
Page
Warnings............................................................................................................................................3
Wiring................................................................................................................................................3
Maintenance ......................................................................................................................................3
Description.........................................................................................................................................4
Installation.........................................................................................................................................6
Initial configuration ............................................................................................................................7
Operation...........................................................................................................................................9
Configuration ...................................................................................................................................22
Connectivity .....................................................................................................................................30
Technical specifications.....................................................................................................................31
Accessories ......................................................................................................................................32
1662H402 Ed.01

3
Warnings
-If the equipment is used without adhering to the manufacturer's instructions, the device safety
requirements could be compromised. Only probes supplied by AKO must be used for the unit to operate
correctly.
2
-From -40 ºC to +20 °C, if the NTC probe is extended to 1000 m with at least a 0.5 mm cable, the maximum
deviation will be 0.25 ºC (cable for probe extension ref. AKO-15586. Earth the cable mesh at one end only).
-Only NTC type probes supplied by AKO must be used for the appliance to operate correctly.
-It must be installed in a place protected from vibrations, water and corrosive gases, where the ambient
temperature does not exceed the value indicated in the technical data.
-For the reading to be correct, the probe must be used in a place without thermal influences apart from the
temperature you want to measure or control.
-IP65 protection degree is only valid with the protection cover closed.
-The IP65 protection degree is only valid if the cables enter the device through a tube for electric conduits +
gland with IP65 or above. The size of the glands must be suitable for the diameter of the tube used.
-Do not spray the unit directly with high-pressure hoses, as this could damage it.
IMPORTANT:
ŸThe AUXILIARY relays are programmable, and their operation depends on the configuration.
ŸThe function of the digital inputs depends on the configuration.
ŸThe recommended currents and powers are the maximum working currents and powers.
Wiring
Always disconnect the power supply to do the wiring.
The probes and their cables must NEVER be installed in a conduit together with power, control or power
supply cables.
For disconnection, the power supply circuit must be equipped with at least a 2 A, 230 V switch, located near
the device. The power supply cable shall be of the H05VV-F or NYM 1x16/3 type. The cross-section to be used
2
will depend on the local regulations in force, but must never be less than 2.5 mm .
2
Cables for relay or contactor outputs must have a cross-section of 2.5 mm and allow working temperatures equal
to or over 70 °C and must be installed with as little bending as possible.
The 120/230 V~ wiring area must be kept clear of any other external element.
The wiring to be undertaken depends on the option selected in the initial configuration wizard (see
p. 8). Use the appropriate diagram based on the option selected.
Check the available options on the diagram sheet included with your device.
Maintenance
Clean the surface of the unit with a soft cloth, water and soap.
Do not use abrasive detergents, petrol, alcohol or solvents, as this might damage the unit.
1662H402 Ed.01

1662H402 Ed.01
4
AUX
Indicators
Constant: Stand-By Mode activated. Regulation
is paused.
Flashing: Controlled stop process for the
regulation in progress.
Constant: Cold room door open.
Flashing: The door has been open for a longer
time than defined in parameter A12.
There is an active alarm, but not an active HACCP
alarm.
Constant: HACCP alarm active.
Flashing: HACCP alarm recorded and
unconfirmed. Press the key to confirm an MUT
HACCP alarm.
There is an active alarm relating to the
temperature or moisture probes.
Constant: Evaporator fans active.
Flashing: The evaporator fans should be active
but a delay is preventing this.
Constant: The cold solenoid is active.
Flashing: The solenoid should be active but a
delay or protection is preventing this.
Constant: Compressor active.
Flashing: The compressor should be active but a
delay or protection is preventing this.
Active heat provision, whether via evaporator
resistors or Hot Gas.
Humidifier relay active.
Defrost relay active.
Continuous cycle mode active.
Cold room light active.
Alarm in progress muted.
Temperature displayed in ° Fahrenheit /
º Centigrade.
Programming mode active.
Dehumidifier relay active / virtual control relay
active.
The lower display shows the relative moisture
value.
Constant: CAMM module in operation.
Flashing: Malfunction in CAMM module.
Bluetooth activated (only with CAMM module).
AUX
Shows temperature
Shows relative moisture /
hour (in line with b23)
Keypad
Description

1662H402 Ed.01
5
Keypad
Pressing it for 3 seconds activates/deactivates the Stand-By mode. In this mode, regulation is paused and
the m icon is displayed.
In the programming menu, it exits the parameter without saving changes, returns to the previous level or
exits programming.
Pressing once without holding displays the temperature of probe S2 for 10 seconds (if it is enabled).
Pressing it for 3 seconds starts/stops the defrost.
In the programming menu, it allows scrolling through the different levels, or during the setting of a
parameter, changing its value.
By pressing down for 3 seconds, activate / deactivate the air extractor fan (if enabled).
In the programming menu, it allows scrolling through the different levels, or during the setting of a
parameter, changing its value.
Pressing once without holding activates/deactivates the cold room light.
Pressing it for 3 seconds accesses the condensed programming menu.
Pressing it for 6 seconds accesses the expanded programming menu.
In the programming menu, it accesses the level shown on the display or, during the setting of a parameter,
accepts the new value.
By pressing once without holding down, the effective value of the temperature and moisture Set Points is
displayed, taking into consideration temporary modifications by other parameters.
When an alarm is in progress, pressing once without holding mutes the acoustic alarm.
By pressing down for 3 seconds, access the Set Point settings.

6
Installation
-Remove the bezels (1)
-Make a 1/4 turn of the screws (2) anti-clockwise and
open the door (3).
-Install the necessary glands (4 / 5) by drilling holes in the
points indicated on the box.
-Mark and make the holes in the wall with the aid of the
template included.
-Fix the device to the wall. If it is a brick wall, use the screws and plugs supplied; if the wall is made of sheet
metal (cold room store), use the screws provided without plugs (6).
-Wire the device by following the recommendations indicated on p. .3
-Close the cover (3), tighten the screws (2) and replace the bezels (1).
1
2
3
6
4Ø Max. 25 mm
5Ø Max. 20 mm
1662H402 Ed.01

7
AUX
AUX
AUX
AUX
1
AUX
AUX
2
3
AUX
4
Step 1: Cold regulation type
Select the most suitable option based on the type of
installation to be carried out and press SET. The available
options are shown in the table on the following page.
Step 2: Moisture regulation type
Select the most suitable option based on the type of
installation to be carried out and press SET. The available
options are shown in the table on the following page.
Step 3: Temperature Set Point
Use keys N and Q to enter the desired Set Point value
and press SET.
Step 4: Moisture Set Point
Use keys N and Q to enter the desired moisture Set Point
(SPH) value and press SET.
Initial configuration
The first time the unit receives the power supply, it will enter into ASSISTANT mode. The lower display will show the
message In1 flashing with 0.
The configuration wizard will not reactivate. To reactivate it, activate the Stand-By mode (by pressing the m
key for 3 seconds) and wait until the unit completely halts regulation (the m indicator will light up
permanently) and press keys N, Q and SET in sequence.
If this is not the first time you run the wizard, after completing the last step the display will show the message dFp
(default parameters). You may choose between two options:
0: Only change the parameters which affect the wizard. The other parameters will remain the same.
1: All parameters return to their factory setting except those which have been modified by the wizard.
1662H402 Ed.01

8
1662H402 Ed.01
In1 table
In2 table
* If the DEF relay is free (In1=3, 6 or 9), it can be used to connect the extractor fan, configuring o80=1. If the HUMID.
relay is free (In2=5, 8, 11 or 14), it can be used to connect the extractor fan, configuring o81=1 (see p. 28).
# Values marked with the # symbol are blocked due to the In1/In2 option chosen. To modify them, choose a
different In1/In2 option.
In1
Installation type (Cold regulation)
Parameters
Cold
regulation
Pump
Down
Defrost
Evaporator
fans
Pd
o00
o80
I10
I11
d7
F3
0
Demo mode: it displays the temperature but does not regulate the temperature or activate relays.
1
Solenoid
No
Electric
Yes
#0
0
#2
0
0
#0
0
2
Solenoid
No
Air
Yes
#0
0
0
0
0
#1
#1
3
Solenoid
No
No
Yes
#0
0
0
0
0
#2
0
4
Solenoid + compressor
Yes
Electric
Yes
#1
#1
#2
#5
#1
#0
0
5
Solenoid + compressor
Yes
Air
Yes
#1
#1
0
#5
#1
#1
#1
6
Solenoid + compressor
Yes
No
Yes
#1
#1
0
#5
#1
#2
0
7
Solenoid + compressor
No
Electric
Yes
#0
#1
#2
0
0
#0
0
8
Solenoid + compressor
No
Air
Yes
#0
#1
0
0
0
#1
#1
9
Solenoid + compressor
No
No
Yes
#0
#1
0
7
0
#2
0
In2
Installation type (Moisture regulation)
Parameters
Diagram
to be
used
Humidifier
Heat provision
Dehumidifier
Extractor
fan
o10
o20
o81
I20
I21
1
ON/OFF
-
-
*
0
#0
#2
0
0
A
2
4-20 mA
-
-
*
0
#0
#2
0
0
B
3
ON/OFF
Resistors
-
*
0
#1
#2
0
0
A
4
4-20 mA
Resistors
-
*
0
#1
#2
0
0
B
5
No
Resistors
-
*
0
#1
0
0
0
A
6
ON/OFF
Hot gas
-
*
#4
#0
#2
#5
#1
A
7
4-20 mA
Hot gas
-
*
#4
#0
#2
#5
#1
B
8
No
Hot gas
-
*
#4
#0
0
#5
#1
A
9
ON/OFF
Hot gas + resistors
-
*
#4
#1
#2
#5
#1
A
10
4-20 mA
Hot gas + resistors
-
*
#4
#1
#2
#5
#1
B
11
No
Hot gas + resistors
-
*
#4
#1
0
#5
#1
A
12
ON/OFF
-
Yes
*
0
#2
#2
0
0
C
13
4-20 mA
-
Yes
*
0
#2
#2
0
0
D
14
No
-
Yes
*
0
#2
0
0
0
C

9
Operation
Messages
MESSAGES
Pump down malfunction error (stop), the time configured in parameter C20 has been exceeded
(see p. 15).
Only displayed on screen.
Pump down malfunction error (start-up), the time configured in parameter C19 has been
exceeded (see p. 15).
Only displayed on screen.
Probe 1/2/3 failure (open circuit, crossed circuit or temperature outside the limits of the probe)
(Equivalent limits in °F).
Only E2 and E3: Damp evaporator probe (see p. 19).
Activates the alarm relay and the audible alarm.
Moisture probe failure (Open circuit, crossed circuit or values beyond probe limits) (see p. 19).
Activates the alarm relay and the audible alarm.
Open door alarm. Only if the door remains open for a longer time than defined in parameter
A12 (see p. 19).
Activates the alarm relay and the audible alarm.
Maximum temperature in control probe alarm. The temperature value programmed in A1 has
been reached (see p. 18).
Activates the alarm relay and the audible alarm.
Minimum temperature in control probe alarm. The temperature value programmed in A2 has
been reached (see p. 18).
Activates the alarm relay and the audible alarm.
External alarm activated (by digital input) (see p. 18).
Activates the alarm relay and the audible alarm.
Severe external alarm activated (by digital input) (see p. 18).
Activates the alarm relay and the audible alarm.
Alarm for defrost completed due to time-out. The time set in d1 has been exceeded (see p. 20).
HACCP alarm. The temperature has reached the value of parameter h1 during a longer period
than established in h2 (see p. 19).
Activates the alarm relay and the audible alarm.
HACCP alarm due to a power supply failure. The temperature established in h1 has been
reached, following a power supply failure (see p. 19).
Activates the alarm relay and the audible alarm.
Indicates that a defrost is being performed (see p. 16).
Only displayed on screen.
AUX
AUX
AUX
AUX
AUX
AUX
AUX
AUX
AUX
AUX
AUX
AUX
AUX
1662H402 Ed.01

10
1662H402 Ed.01
MESSAGES
Password request. See parameters b10 and PAS (see p. 27).
Only displayed on screen.
Shown sequentially with the temperature: The controller is in demo mode, the
configuration has not been made.
Maximum moisture alarm in moisture probe. The temperature value programmed in A21 has
been reached (see p. 19).
Activates the alarm relay and the audible alarm.
Minimum moisture alarm in moisture probe. The temperature value programmed in A22 has
been reached (see p. 19).
Activates the alarm relay and the audible alarm.
Indicates that the extractor fans are activated. (see p. 18).
AUX
AUX
AUX
AUX
AUX

1662H402 Ed.01
11
Cold regulation
Solenoid control (COOL Relay)
Cold production is regulated by means of opening /
closing the solenoid valve.
When the temperature in probe S1 reaches the set
point (SPt) value plus the probe's differential (C1),
the solenoid opens and causes the temperature to
drop. Once the set point (SPt) value is reached, the
solenoid closes.
Compressor control (Relay AUX 1)
With Pump Down (In1: 4, 5, 6)
Requires the connection of a low pressure
switch in digital input 1.
When the temperature in probe S1 reaches the set
point (SPt) value plus the probe’s differential (C1), the
solenoid opens, causing the pressure in the evaporator
to increase and, therefore, the low pressure switch
deactivates and the compressor starts up.
Once the set point (SPt) value is reached, the
solenoid closes, causing the pressure in the
evaporator to decrease, triggering the low pressure
switch and stopping the compressor.
For further details of the process, see the next page.
Without Pump Down (Inl: 7, 8, 9)
The compressor operates simultaneously with the solenoid valve, starting up when the latter opens and stopping
when it closes.
Operation in the event of a fault in probe S1
If probe S1 fails (fault, disconnection, etc. ), compressor behaviour will depend on parameter C6, with one of 3
options available:
C6=0: The compressor is stopped until probe S1 begins to operate again.
C6=1: The compressor is started-up until probe S1 begins to operate again
C6=2: The compressor operates in line with the times programmed in C7 (ON) and C8 (OFF).
Calibration of probe 1
Parameter C0 allows for correction of the temperature detected by probe 1; this is particularly useful when
the probe cannot be located in the ideal place.
Set Point locking
Parameters C2 and C3 allow for an upper and lower limit to be established for the set point (SPt), to protect
the product or installation from Set Point manipulation.
SPt+C1
SPt+C1
SPt
SPt
Solenoid
Solenoid
Low
pressure
switch
Compressor
Compressor
ON
ON
ON
ON
ON ON
C7 C7C8
S1
S1

1662H402 Ed.01
12
ON
ON
ON
OFF-ON (C4=0) OFF-ON / ON-OFF (C4=1)
Spt
SPH
- rH01
DehumidificationHumidification
SPH
+ rH01
SptSPt+C1
SPH
SPt+C1
C5 C5C5
OFF
OFF
OFF
COOL COOL
%HR
Compressor protection timing
Parameter C4 allows for selection of the type of timing to be applied to protect the compressor. These delays
prevent continuous compressor starts and stops.
These timings affect the COOL and AUX 1 relays (if o00=1)
OFF-ON (C4=0): Minimum time in OFF mode before each start-up.
OFF-ON / ON-OFF (C4=1): Minimum time in ON and OFF mode for each cycle.
The delay time is defined by means of parameter C5; if C5=0, timing is disabled.
Moisture regulation
Moisture regulation is carried out using the moisture probe and the regulation of different devices:
To increase moisture
ŸHumidifier: Connected to the HUMID. relay (In2: 1, 3, 6, 9 and 12) (Control ON/OFF) or to the
analogue output AN. OUT (In2: 2, 4, 7, 10 and 13) (Control 4-20 mA), it increases
cold room moisture as necessary.
To reduce moisture
ŸDehumidifier: Connected to the AUX 3 relay (In2: 12, 13 and 14), reduces cold room moisture as
necessary.
ŸCold provision: Through cold provision, cold room moisture is reduced, provided that the cold
room’s temperature is higher than the temperature Set Point.
ŸHeat + cold provision: Through heat provision, whether via resistors or Hot Gas (or both), the unit can
produce cold for a longer period of time to reduce moisture even below the
temperature Set Point, since heat provision will regulate the temperature.
If the moisture probe reaches the Set Point value (SPH) plus the
differential (rH01), dehumidification is activated until the SPH is reached.
If the moisture probe reaches the Set Point value (SPH) minus the
differential (rH01), humidification is activated until the SPH is reached.

1662H402 Ed.01
13
Regulation types, depending on the installation
The controller’s priority is temperature regulation.
Humidification + Dehumidification (via cold provision) - In2: 1 and 2
To increase moisture, the humidifier is activated and to reduce moisture, cold provision is activated, provided that
the temperature is above the SPt.
If the temperature reaches the SPt value, dehumidification stops.
Humidification + Dehumidification (via cold + heat provision) - In2: 3, 4, 6, 7, 9 and 10
To increase moisture, the humidifier is activated and to reduce moisture, cold provision is activated.
If, during this process, the temperature falls below the SPt minus the C1 differential, heat provision is activated,
firstly via Hot Gas (if available) and, after the time defined in rH06 has elapsed, via electrical resistors (if available),
until the temperature reaches the SPt again.
Should heat provision via Hot Gas not be available, the resistors are activated without taking parameter rH06 into
account.
Humidification + Dehumidification (via dehumidifier + cold provision) - In2: 12 and 13
To increase moisture, the humidifier is activated and to reduce moisture, the dehumidifier is activated.
If, after the time defined in rH05 has elapsed, moisture has not reduced to the SPH value and the cold room
temperature is higher than the SPt, heat provision is activated to reduce moisture.
If the temperature reaches the SPt value, cold provision stops but the dehumidifier remains active until the SPH
value is reached.
Only Dehumidification (via cold + heat provision) - In2: 5, 8 and 11
The controller cannot increase cold room moisture; it can only reduce it by activating cold provision.
If, during this process, the temperature falls below the SPt minus the C1 differential, heat provision is activated,
firstly via Hot Gas (if available) and, after the time defined in rH06 has elapsed, via electrical resistors (if available),
until the temperature reaches the SPt again.
Should heat provision via Hot Gas not be available, the resistors are activated without taking parameter rH06 into
account.
Only Dehumidification (via dehumidifier + cold provision) - In2: 14
The controller cannot increase cold room moisture; it can only reduce it by activating the dehumidifier.
If, after the time defined in rH05 has elapsed, moisture has not reduced to the SPH value and the cold room
temperature is higher than the SPt, heat provision is activated to reduce moisture.
If the temperature reaches the SPt value, cold provision stops but the dehumidifier remains active until the SPH
value is reached.
Humidifier control
Humidifier control can be carried out in two possible ways:
ŸON/OFF: Regulation is carried out by activating or deactivating the humidifier. (In2: 1, 3, 6, 9 and 12)
Ÿ4-20 mA: The analogue output (AN. OUT) is used to adjust humidifier power using a PI regulation. (In2: 2,
4, 7, 10 and 13).
100%
50%
SPH
- rH01
Power
applied to
the humidifier
SPH
+ rH01
SPH
0%
%HR

1662H402 Ed.01
14
Operation in the event of a fault in probe SH
If probe SH is faulty (failure, disconnection, etc.), the controller stops regulating moisture and shows the message
EK on the lower display.
Calibration of probe SH
Parameter rH00 allows for correction of relative moisture as detected by probe SH; this is particularly useful when
the probe cannot be located in the ideal place.
Moisture Set Point locking
Parameters rH02 and rH03 allow for an upper and lower limit to be established for the moisture set point (SPH),
to protect the product or installation from unsuitable Set Point manipulation.
Operating mode selector
Pressing an external switch allows us to quickly change between two operating modes: temperature and moisture
regulation or only temperature regulation.
This function may be useful if the same cold room is used for different types of applications.
The external switch should be connected to one of the digital inputs and this should be configured as a “Temp.
control / temp. + moist. selector” (I10 / I20 / I30=4).
Door management
Door management allows for the installation's behaviour to be controlled, should the cold room door open
through parameters C22 and C23.
Parameter C22 defines whether cold production should be stopped if the door opens. If C22=1, when the door
opens, the fans stop and, 15 seconds later, the solenoid closes (COOL relay).
Parameter C23 defines the maximum time, in minutes, that the installation can remain without producing cold
whilst the door is open. If C23=0, cold is not produced with the door open.
SP
Door
C23
COOL
Open
ON ON
SPt+C1
Configuration:
C22: 1
C23: 5
S1

15
Pump down function
This function foresees problems in the compressor caused by movements of coolant, using a stop/start technique
for the installation, controlled via the liquid solenoid, the low pressure switch and the compressor itself.
This function is only available for In{ options 4, 5, and 6 and 12 and requires the connection of a low pressure
switch in digital input 1. (I10=5)
STOP
When the temperature in probe S1 reaches the set point (SPt) value, the COOL relay deactivates, closing the liquid
solenoid.
Because the compressor continues to operate, pressure in the evaporator quickly drops. Upon reaching a given
value, the low pressure switch activates, changing the status of digital input 1, which stops the compressor (relay
AUX 1).
This manoeuvre isolates all of the coolant in the high-pressure line, far from the compressor crankcase, preventing
serious faults upon start-up.
Should the low pressure switch fail, the controller stops the compressor once the safety interval defined in C20 has
elapsed, displaying the message “Pd” (an informative message that does not affect the unit's operation).
If C20 time is 0 (default value), the compressor will not stop until the low pressure switch is activated, but it will
display the “Pd” message after 15 minutes.
START
When the temperature in probe S1 reaches the set point value plus the differential (SPt+C1), the COOL relay
activates, opening the liquid solenoid. This increases the pressure in the evaporator, deactivating the low pressure
switch, which turns the compressor on.
If, some time (determined by C19) after the liquid solenoid is opened (COOL relay set to ON), the low pressure
switch does not deactivate, the controller will once again close the solenoid (COOL relay set to OFF) and the “LP”
message will be displayed. This manoeuvre will be repeated every 2 minutes, indefinitely, until the pressure switch
is deactivated and the installation reverts to its normal operation.
If C19 time is 0 (default value), the solenoid will remain open until the low pressure switch deactivates, but it will
display the “LP” message after 5 minutes.
STAND-BY
If the pump down function is active, a certain amount of time may elapse between starting the stand-by function
and the controller stopping; this is because certain installation control phases cannot be interrupted.
ON
Liquid solenoid
Low pressure
switch
Pressure
switch fault
Pressure
switch fault
Compressor
Pressure in
evaporator
ON
ON
+
C20 C19
OFF
OFF
OFF
COOL
D1
AUX 1
SPt SPtSPt+C1 SPt+C1
1662H402 Ed.01

1662H402 Ed.01
16
Defrost
Types of defrost
There are 5 possible defrost types, depending on the option selected in the wizard (In1):
Electric (InI=1, 4 and 7) (d7=0)
Defrost is performed through electrical resistors, supplying the evaporator with heat. The operation of fans in this
mode depends on parameter F3; the compressor and solenoid are stopped.
By air (InI=2, 5 8) (d7=1)and
Usually used in positive cold rooms (> 3°C), since the inside temperature of the cold room is sufficient to melt
evaporator ice. By default, the fans are activated so that air may circulate through the evaporator; to stop them,
change parameter F3 to 0. The compressor and solenoid are stopped.
No defrost InI= d7( 3, 6 and 9) ( =2)
Defrost is not carried out
Defrost control
Defrost start
Defrost will start if:
-The time programmed in parameter d0 has elapsed since the start of the last defrost.
-We press the H key for 3 seconds.
-Through the app or through AKONet.
Defrost completion
Defrost will complete if:
-The temperature programmed in parameter d4 has been reached in probe 2. This requires a 2nd probe
(l00=2) to be available, located in the evaporator.
-The time configured in parameter d1 has elapsed (maximum defrost duration).
-We press the H key for 5 seconds.
-Through the app or through AKONet.
Drip time
This is established through parameter d9 and sets the time added at the end of defrost to allow for the removal of
surplus water from melted evaporator ice, during which there is no cold regulation.
DEFROST
COLD REGULATION
COLD REGULATION
F4
Máx. d1 d3d9
d0
SPt
SPt+C1
d4
DEFROST
DRIP TIME FAN START-UP
DELAY
"DEF” MESSAGE
S1

1662H402 Ed.01
17
SPt SPt
F0
S2
F0-F1
Fans
COOL ON ON
ON
ON ON
SPt+C1
F2=1
F2=0
Fan start-up delay
This is established through parameter F4 and allows for the possible drops left in the evaporator to freeze before
the fans activate, preventing them from being projected into the cold room. It also prevents heat being supplied to
the cold room due to defrost in the evaporator.
If defrost is cancelled before 1 minute has elapsed, the drip time (d9) is not applied and the fans are
activated without taking into account the start-up delay (F4).
If defrost is by air, the drip time (d9) and fan start-up delay (F4) are deactivated.
Message displayed during defrost
This is established using parameter d2, and you can choose between displaying the real temperature captured by
probe 1 (d2=0), showing the temperature captured by probe 1 at the start of the defrost (d2=1), or displaying the
dEF (d2=2) message. Parameter d3 defines the time during which the aforementioned message will be displayed
once the drip time (d9) and fan stop time (F4) are complete.
Other parameters
Using parameter d5, you can configure whether the unit performs a defrost (d5=1) or not (d5=0) when it receives
power (first start-up or after a power supply failure). Should the option YES (d5=1) be selected, defrost will begin
once the delay time defined in d6 has elapsed.
Using parameter d8, we define the time tally established in d0, choosing between total time elapsed (d8=0) or
the sum of compressor operation time (d8=1).
REMARK: If parameter d1 is configured to 0, no defrosts are performed.
Evaporator fan control
Fans are controlled through probe 2 (evaporator) and parameters F0 (stop temperature) and F1 (probe differential).
If probe 2 is not connected or an error in the probe (E2) is detected, the fans continuously operate without taking
into account parameters F0 and F1, but taking the remaining parameters (F2 to F4) into account.
Using parameter F2, the status of the fans during compressor stops is defined.
Using parameter F3, the status of the fans during defrost is defined.
Parameter F4 defines the fan start-up delay time after defrost (see p. 16).
Parameter C22 defines whether fans stop when the door is opened.

18
Anti-stratification function (Only if F2=1)
This prevents layers of air of different temperatures (stratification) from forming inside the cold room by moving the
air using the evaporator’s fans.T
he fans are activated if they stop for a longer period than that defined in parameter F10 and deactivate once the
time defined in F11 has elapsed.
Extractor fans
This allows for air to be extracted from inside the cold room using an extractor fan connected to the DEF or
HUMID. relay.
To activate this function, the DEF or HUMID. relay should be available and configured as “Extractor fans” (o80=1
or o81=1).
The DEF relay is available depending on the option chosen in In1 (3, 6 or 9) and the HUMID. relay is available
depending on the option chosen in In2 (5, 8, 11 or 14).
Alarms
The device warns the user through an on-screen message, activation of a relay (only if o10=1) and a sound alarm
when the criteria programmed in the parameters are met.
Maximum / minimum temperature alarm
It shows the message “AK” or “AL” when the temperature
in probe 1 reaches the value configured in parameters A1
(maximum temperature) and A2 (minimum temperature).
This value may be:
ŸAbsolute (A0=1): The temperature at which the alarm should activate must be indicated in A1/A2.
ŸA0=0): The increase or decrease in the number of degrees necessary for the alarm to Relative to the SP (
activate, in relation to the set point, must be indicated in A1/A2. This option enables us to change the set
point without having to reset the maximum and minimum alarms.
Parameter A10 establishes the differential of both parameters (Hysteresis).
Example
We configure the following parameters in a controller: SP=2, A1=10, A10=2
-If A0=0 (Relative to the SP), the maximum temperature alarm will activate when 12 degrees are
reached in probe 1, and will deactivate when 10 degrees are reached.
-If A0=1 (Absolute), the maximum temperature alarm will activate when 10 degrees are reached in
probe 1, and will deactivate when 8 degrees are reached
External alarm / severe external alarm
The message EA (External alarm) or SEA (Severe external
alarm) is displayed when the digital input configured as
external alarm or severe external alarm is activated.
The severe external alarm also deactivates all the loads and,
therefore, temperature regulation stops. When this alarm disappears, the device returns to its normal operation.
At least one of the digital inputs must be configured as an external alarm (I10 or I20=2) or as a severe external
alarm (I10 or I20=3).
AUX
AUX
AUX
AUX
1662H402 Ed.01

19
1662H402 Ed.01
Temperature probe error alarm
If one of the enabled probes is crossed, in open circuit or out of range, the message
E1, E2 or E3 will be shown, depending on whether probe S1, S2 or S3 is involved.
Evaporator probe error alarm due to moisture ingress
If, at the start of defrost, the temperature in probe S2 is 20°C higher than the
temperature in probe S1, the defrost ignores probe S2 and completes due to time-out.
The display shows the message E2, activates the alarm relay (only if o10=1) and sound
alarm.
The alarm can be silenced, but the B alarm icon will not disappear until:
ŸThe controller is switched off and then on again.
ŸDefrost without error is started in probe S2.
Moisture probe error alarm
If the moisture probe is crossed, in open circuit or out of range, the message EX will appear on the lower display.
Maximum / minimum moisture alarm
This shows the message AKX or ALX when the moisture in probe SH reaches the value configured in parameters
A21 (maximum moisture) and A22 (minimum moisture).
This value may be:
ŸAbsolute (A20=1): The temperature at which the alarm should activate must be indicated in A21/A22.
ŸRelative to the SPH (A20=0): The increase or decrease in moisture % for the alarm to activate, in relation to
the set point, must be indicated in A21/A22. This option enables us to change the set point without having
to reset the maximum and minimum alarms.
Parameter A23 establishes the differential of both parameters (Hysteresis).
Open door alarm
The door has been open for a longer time than defined in parameter A12, the open
door alarm is activated.
In order to detect the open door, configuration is required of one of the digital inputs
as “door contact” (I10 or I20=1).
Activates alarm relay (only if P62=1) and sound alarm.
HACCP alarm
The alarm is activated should situations be detected which could endanger the
integrity of the products stored in the cold room.
If the temperature of the cold room is higher than that defined in parameter h1 for a
length of time exceeding that defined in parameter h2, the alarm activates, displaying
the message HCP. on screen.
Upon pressing the mute key, the sound alarm switches off, but the alarm remains.
Once the temperature drops below parameter h1, if the mute key has been pressed, the alarm disappears. If the
mute key has not been pressed, the audible alarm deactivates but the HACCP indicator remains in flashing mode,
indicating than a non-confirmed HACCP alarm has occurred.
Press the mute key to confirm an HACCP alarm.
If, during a power failure, a HACCP alarm occurs, when the power supply returns, the HACCP alarm is activated and
the display shows the messages HCP and PF (power failure) alternately.
AUX
AUX
AUX
AUX

1662H402 Ed.01
20
Alarm delays
These delays prevent certain alarms from being shown, to allow the installation to recover its normal operation
after certain events.
-Delays in start-up (A3): This delays the activation of the temperature and moisture alarms upon receiving
power supply (start-up or after a power supply failure). This allows for the installation to start up, avoiding
alarms.
-Delay after a defrost (A4): This delays the activation of the temperature and moisture alarms when a defrost
completes.A205
-Delay to minimum and maximum temperature alarm (A5): This delays the activation of the maximum (A1)
and minimum (A2) temperature alarms, from when the temperature in probe 1 reaches the programmed
value.
-Delay to minimum and maximum moisture alarm (A24): This delays the activation of the maximum (A21) and
minimum (A22) moisture alarms, from when the moisture reaches the programmed value.
-Delay to activation of external alarm (A6): This delays the activation of the external alarm, from when the
digital input becomes active.
-Delay to deactivation of external alarm (A7): This delays the deactivation of the external alarm, from when
the digital input becomes active.
-Delay to open door alarm (A12): This delays the activation of the alarm upon detecting that the door is open.
Configuration of alarm relay
Should relay AUX 2 have been configured as an alarm (o10=1), parameter A9 allows for the relay status to be
defined when an alarm is triggered:
A9=0 Relay active (ON) in the event of an alarm (OFF without alarm)
A9=1 Relay inactive (OFF) in the event of an alarm (ON without alarm)
Alerts
The device alerts the user through an on-screen message when an event occurs which requires his/her attention.
However, it does not activate the sound alarm or the alarm relay (if active).
Alert: defrost finished by time
The message Adt is displayed when a defrost has completed due to time-out, if parameter
A8=1.
Pump down malfunction error (stop)
The message Pd is displayed if a malfunction is detected when the installation is stopped
using the pump down manoeuvre. (See p. ).15
Pump down malfunction error (start-up)
Displays the LP message if a malfunction is detected when the installation is started up using
the pump down manoeuvre. (See p. 1 ).5
Light control
Relay AUX 1 or AUX 2 must be configured as “Light” (o00 or o10=2).
Switching the lights on or off is controlled using:
The push-button: One press switches the lights on or off.LHT
The cold room door: When the door is opened, the lights remain on for the time defined by parameter b01. If the
value is 0, when the door closes the lights go out. (One of the digital inputs must be configured as door contact
(I10, I20 or I30=1).
The control even occurs with the equipment in Stand-by.
AUX
AUX
AUX
Other manuals for AKO-16624
1
Table of contents
Other AKO Temperature Controllers manuals