AKO 14632 User manual

Device designed to display, control and regulate cooling generators (manual or automatic
programmable defrosting).
1463H202 Ed.03
Surface temperature controller with 3 relays and 2 probes
GB
MODEL FUNCTION RELAY POWER SUPPLY,
50/60 Hz
COOL: 16 A, 250 V, cos ϕ=1, SPST
AKO-14632 Controller DEF: 8 A, 250 V, cos ϕ=1, SPDT 230 V~ ±10%
FAN: 6 A, 250 V, cos ϕ=1, SPST
1- Versions and references
2- Technical data
Temperature range:. . . . . . . . . . . . . . . . . . . . . -50.0 ºC to 99.9 ºC (-58.0 ºF to 211 ºF)
Resolution, Set Point and differential: . . . . . . . 0,1 or 1 ºC/ºF configurable by parameter P7
Input for NTC probe: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149XX
Thermometric accuracy: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 1 ºC
Probe tolerance at 25 ºC: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0,4 ºC
Maximum input power: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 VA
Working ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 ºC to 50 ºC
Storage ambient temperature:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Control device classification:
Independent mounting, with characteristic of automatic operation Type 1.B action, to be
used in a clean situation, logical medium (software) class A and continuous operation.
Degree of contamination 2 on UNE-EN 60730-1
Double insulation between the power supply, the secondary circuit and the relay output.
Allocated pulse temperature: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2500 V
Pressure ball test temperature:
Accessible parts: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75 ºC
Parts that position active elements:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125 ºC
Voltage and current declared by the EMC tests: . . . . . . . . . . . . . . . . . . . . 207 V, 22 mA
Current of radio jamming supression test:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 270 mA
3.1 Fastening
3.2 Connection:
The probe and its lead should NEVER be installed in duc-
ting along with power, control or power supply wiring.
The power supply circuit should be connected with a mini-
mum 2 A, 230 V, switch located close to the unit. Power
supply cables should be H05VV-F 2x0,5 mm2or H05V-K
2x0,5 mm2.
Section of connecting wires for relays contacts should be
2,5 mm2.
3- Installation
The controller should be installed in a place protected from vibrations, water and corrosive
gases, and where ambient temperature does not surpass the value specified in the technical
data.
In order to give a correct reading, the probe should be installed in a place without heat
influences other than the temperature that is to be measured or controlled.
AKO-14632
1
2
4
5
8
3
9
10
11
12
13
14
±10% 50/60 Hz
COOL
C
DEF
FAN
S1-TEM
S2-DEF
DI1
SONDAS
PROBES
*16A
*8A
*6A
*Imax = 16 A
cos
ϕ
=1 250 V
230V~
In=22mA~
4- Funciones del frontal
LED Cool (Compressor)
Permanent: Cooling relay COOL (com-
pressor) energised.
Flashing: Because of the temperature
detected by Sensor 1 (TEM), the COOL
relay should be energised, but is no due to
a programmed parameter.
LED Fan
Permanent: Fan relay energised.
Flashing: Because of the temperature
detected by Sensor 2 (DEF), the Fan relay
should be energised, but is no due to a pro-
grammed parameter.
LED Def
Permanent: Indicates defrost in opera-
tion.
LED Alarm
Permanent: Alarm indicator enabled.
Flashing: Alarm detected, but display
maintained.
LED DT
Permanent: Indicates last defrost ended
by time.
LED Continuous cycle
Permanent: It indicates that the conti-
nuous cycle is active.
LED
Cool ºC
ºF
LED
Def
LED
ºC
LED
ºF
LED
Continuous
Cycle
DOWN
KEY
LEFT
KEY
SET
KEY
UP
KEY
RIGHT
KEY
LED
Fan
LED
Alarm
LED DT
LED ºC
Permanent: Degrees ºC indicator.
Flashing: Programming phase.
LED ºF
Permanent: Degrees ºF indicator.
Flashing: Programming phase.
UP KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, it makes the displayed
value increase.
- When pressed it displays the help messa-
ge dEF corresponding to the short key
function that it performs.
- When pressed for at least 5 seconds, a
manual defrost is started / stopped with
programmed duration.
DOWN KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, it makes the displayed
value reduce.
- When pressed, it displays the help mes-
sage Con corresponding to the function
performed by the key.
- Pressing during 3 seconds,it activates /
deactivates the CONTINUOUS CYCLE
during the time for which it has been
programmed.
RIGHT KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, it makes the level value
increase.
- When pressed, it displays the help mes-
sage oFF corresponding to the function
performed by the key.
- Pressing during 3 seconds it turns off/on
the unit leaving it in STAND-BY. The dis-
play shows oFF when the unit is discon-
nected.
LEFT KEY
- Press once to cancel the alarms, but they
remain displayed.
- Exit programming level.
KEY
- Press once to cancel the alarms, but they
remain displayed.
- In programming, accept the programmed
new value.
- When pressed it displays the help messa-
ge SP corresponding to the function per-
formed by the key.
- When pressed for at least 5 seconds, the
SP Set Point temperature is displayed.
5- Adjustment and configuration
It should only be programmed or modified by personnel who are fully conversant with the
equipment operation and possibilities.
5.1 Set Point temperature
The factory SET POINT default value is 0.0 ºC.
- Press key for at least 5 seconds to DISPLAY SET POINT. It displays the CURRENT SET
POINT value and LED ºC or ºF starts flashing.
- Press or keys to CHANGE SET POINT into the required value.
- Press key to ACCEPT THE NEW SET POINT. The display returns to the CURRENT TEM-
PERATURE display status and LED ºC or ºF stops flashing.
- Press the key to exit the temperature set point without modifying the value.
When PA is displayed, PASSWORD programmed in L5 parameter of tid menu should be
entered to access the CURRENT SET POINT.
- Press key. 0will be displayed to ENTER PASSWORD.
- Press or keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.
- Press key to ACCEPT PASSWORD. The CURRENT SET POINT value will be displayed
and it can be already modified.
5.2 Parameters configuration
Level 1 Menus
When the keys + are pressed simultaneously for at least 10 seconds, the display
shows Pro for 10 seconds. LED ºC or ºF will be flashing, we are in the programming LEVEL
1 MENUS and the first menu “rE” is displayed.
- Press key to access the next menu and key to return to previous one.
- Pressing key, the controller returns to the CURRENT TEMPERATURE display status and
LED ºC or ºF will stop flashing.
When PA is displayed, PASSWORD programmed in L5 of “tid” menu should be entered to
access programming LEVEL 1 MENUS.
- Press key. 0will be displayed to ENTER PASSWORD.
- Press or keys to CHANGE NUMBER and DISPLAY PASSWORD programmed.
- Press key to ACCEPT PASSWORD. The first menu “rE” will be displayed.
171
35
60
94
Ø máx. 3,7
125,5
41,5
Detail of fixing screw-holes.
Suitable fixing screw-holes for universal
flush-mounting wall box
.
Press down lightly
to open the cover.
CURRENT
TEMPERATURE
ACCEPT
PASSWORD
DISPLAY
SET POINT
CHANGE
SET POINT
ACCEPT
THE NEW
ENTER
PASSWORD DISPLAY
PASSWORD CURRENT
SET POINT NEW
SET POINT
If P2=0 or L5=0
PASSWORD
REQUEST
CHANGE
NUMBER
5 Sec.
Level 1 Menus and Description
rE Level 2 Control
Level 3 Description Values Min. Def. Max.
SP Set Point temperature (ºC/ºF) -58.0 0.0 211
C0 Sensor 1 calibration (Offset) (ºC/ºF) -20.0 0.0 20.0
C1 Sensor 1 differential (Hysteresis) (ºC/ºF) 0.1 2.0 20.0
C2 Set Point upper limit (ºC/ºF) C3 99.9 211
(It cannot be set above this value)
C3 Set Point lower limit (ºC/ºF) -58.0 -50.0 C2
(It cannot be set below this value)
C4 Relay protection delay type: 001
0=OFF/ON (From the last switch-off) 1=ON (At switch-on)
C5 Protection delay time (min.) 0 0 255
(Value for the option selected in parameter C4)
C7 Relay time in ON in case of faulty sensor (min.) 0 10 255
(If C7=0 and C8=/ 0, the relay will always be OFF disconnected)
C8 Relay time in OFF in case of faulty sensor (min.) 0 5 255
(If C8=0 and C7=/ 0, the relay will always be ON connected)
C9 Continuous cycle duration (h.) 1 1 24
C10 Compressor stops when opening door? (0 = No) (1 = Yes) 0 0 1
dEF Level 2 DEFROST control
Level 3 Description Values Min. Def. Max.
d0 Defrost frequency (Elapsed time between 2 starts) (h.) 0 6 120
d1 Defrost maximum duration (min.) 0 30 255
Type of message during defrost:
d2 (0=Current temperature display) 022
(1=Defrost start temperature display)
(2=Display dEF message)
d3 Message maximum duration (min.) 0 5 255
(Time added at the end of defrost)
d4 Defrost final temperature by sensor 2 (ºC/ºF) -58.0 8.0 211
Defrost start-up on equipment switch-on:
d5 (0 = No, first defrost according to d0) 0 0 1
(1 = Yes, first defrost according to d6)
d6 Defrost start-up delay on equipment switch-on (min.) 0 0 255
d7 Defrost type: 001
(0=Electrical heater) (1=Hot gas by-pass)
Time calculation between defrost periods:
d8 (0 = Total real time) 0 0 1
(1 = Compressor operation sum)
d9 Drip time, compressor stops and FAN (min.) 0 1 255
relay off when defrost ends
FAn Level 2 FANS control (Evaporator)
Level 3 Description Values Min. Def. Max.
F0 Fans stop temperature by sensor 2 (ºC/ºF) -58.0 4.0 211
If sensor 2 is programmed in P4
F1 Sensor 2 differential (ºC/ºF) 0.1 1.0 20.0
F2 Stop fans, when compressor stops? (0=No) (1=Yes) 0 0 1
F3 Fans status during defrost 001
(0 = Off) (1 = On)
F4 Start-up delay after defrost (min.) 0 3 255
Operates if it is higher than d9
F5 Stop fans if the door opens? (0 = No) (1 = Yes) 0 0 1
AL Level 2 ALARM control (Visual)
Level 3 Description Values Min. Def. Max.
Configuration of temperature alarms
A0 (0=Relative to SP) (1=Absolute) 0 0 1
(If A0=0, A1 and A2 range from 0 to 50 ºC/ºF)
A1 Maximum alarm in sensor 1 (ºC/ºF) A2 0.0 211
Level 2 Parameters
- In the desired menu of LEVEL 1 MENUS,
press key. LEVEL 2 PARAMETERS
programming is accessed. The first para-
meter of the selected menu is displayed
on the screen.
- Press key to access the next parame-
ter and key to return to the previous
one.
- Pressing key, the controller returns to
the LEVEL 1 MENUS
Level 3 Values
- To DISPLAY the CURRENT VALUE of any
parameter, select the required one and
press key. Once it is displayed, you
can CHANGE VALUE, pressing or
key.
- Press key to ACCEPT THE NEW. The
programming returns to LEVEL 2 PARA-
METERS.
- Pressing key, the controller returns to
the LEVEL 2 PARAMETERS
Nos reservamos el derecho de suministrar materiales que pudieran diferir levemente de los
descritos en nuestras Hojas Técnicas. Información actualizada en nuestra web: www.ako.com.
Av. Roquetes, 30-38 | 08812 Sant Pere de Ribes | Barcelona | España
Tel. (34) 938 142 700 | Fax (34) 938 934 054 | e-mail: [email protected] | www.ako.com
Apartado (P.O. Box), 5 | 08800 Vilanova i la Geltrú | Barcelona | España
AKO ELECTROMECÀNICA, S.A.L.
351463202 REV.02 2007 D.L.: B-9221-07
7- Parameters transfer
Portable server
AKO-14918 portable server, with no power
supply, in which parameters programmed in a
powered controller can be copied by transfer.
Parameters can be transferred again from the
server to other identical powered controllers.
Storage dump or fast copy of the para-
meters entered in the portable server
to the controller:
Press the key while the controller is being connected to the power supply until the dis-
play shows CPY, indicating that the transfer was made correctly. Disconnect the controller
and reconnect it to the power supply.
Storage dump can also be done from parameter L6=2.
8- Maintenance
Clean the controller surface with a soft cloth, soap and water. Do not use abrasive deter-
gents, petrol, alcohol or solvents.
9- Warnings
The use of the unit without observing the manufacturer's instructions may alter its safety
qualification.
To ensure correct operation of the apparatus, only NTC type probes supplied by AKO should
be used.
Between -40 ºC and +20 ºC, when the NTC probe is extended up to 1.000 m with minimum
0,5 mm2cable, deviation will be less than 0.25 ºC (Probe extension cable ref. AKO-15586)
REMARK: When time parameters are modified, the new values are applied when the current
cycle is completed. In order for it to have an immediate effect, switch the controller off and
then on again.
A2 Minimum alarm in sensor 1 (ºC/ºF) -58.0 0.0 A1
A3 Temperature alarm delay in the start-up (min.) 0 0 255
(If programmed in A1, A2)
A4 Temperature alarm delay from (min.) 0 0 255
the end of a defrost
A5 Temperature alarm delay from the (min.) 0 30 255
moment at which they should operate due to temperature
A6 Temperature alarm delay from digital input disabling (min.) 0 0 255
If programmed as “Door contact”
A7 Temperature alarm delay from digital input enabling (min.) 0 0 255
If programmed as “Door contact”
A8
Signals if defrost ends due to maximum time (0=No) (1=Yes)
001
A10 Differential Alarms Temperature A1 and A2 0.1 1.0 20.0
InP Level 2 DIGITAL INPUTS
Level 3 Description Values Min. Def. Max.
Digital Input Nº1 configuration
(0=Disabled) (1=Door Contact)
i1C (2=External alarm) (3=Severe external alarm) 0 0 5
(4=Remote defrost)
(5=Change of set point iS1 + it1)
i1d Alarm delay of digital Input Nº 1 (min.) 0 0 255
Polarity of digital input Nº1
i1P (0=Activated on closing contact) 0 0 1
(1=Activated on opening contact)
iS1
Value of auxiliary set point 1 of “COOL” Relay (Compressor)
(ºC/ºF) -58.0 0.0 211
it1 Duration of auxiliary set point 1 (min.) 0 0 255
CnF Level 2 GENERAL STATUS
Level 3 Description Values Min. Def. Max.
P1 Delay of all functions on power supply (min.) 0 0 255
switch on
P2 Allocation of password to Set Point: 001
(0=Without allocation) (1=With allocation of L5 password)
P3 Initial parameters: 001
(1=YES, configure to “Def” and exit programming)
P4 Connected sensors 122
(1 = Sensor 1) (2 = Sensor 1 + Sensor 2)
P5 Address for units with communication 0 0 255
Temperature display mode:
P7 (0=Integers in ºC) (1=One decimal in ºC) 0 1 3
(2=Integers in ºF) (3=One decimal in ºF)
P8 Sensor to be displayed (1=Sensor 1) (2=Sensor 2) 1 1 2
tid Level 2 ACCESS AND INFORMATION control
Level 3 Description Values Min. Def. Max.
L5 Access password to parameters and information 0 0 255
L6 Parameters transfer: (0=Disabled) (1=Send) (2=Receive) 0 0 2
PU Program version (Information)
6- Description of parameters and messages
Values in the Def. column are factory-set.
CHANGE
NUMBER
DISPLAY
VALUE
PASSWORD
REQUEST ENTER
PASSWORD DISPLAY
PASSWORD
CURRENT
VALUE NEW
VALUE
IF L5=0
ACCEPT
DE NEW
CURRENT
TEMPERATURE
LEVEL 2
PARAMETERS LEVEL 3
VALUES
EXIT TO
LEVEL 1
ACCEPT
PASSWORD
PASSWORD
IF PROGRAMMED
CHANGE
VALUE
LEVEL 1
MENUS
10 Sec.
EXIT
PROGRAMMING
ACCEPT
ACCEPT
SIMULTEANOUSLY
EXIT TO
LEVEL 2
REMARK: If no key is pressed for 25 seconds in either of the previous steps, the controller
will automatically return to the CURRENT TEMPERATURE display status without modifying
any of the parameters values.
AKO-14918
Power supply
Transfer
Programming
MESSAGES
PA Password request to enter programming parameters
or SET POINT
dEF It indicates defrosting is being carried out. In order to display "dEF" during defrosting,
it is essential that parameter d2 is set to option 2.
AE Flashing with temperature - External alarm
AES Flashing with temperature - Severe external alarm
AH Flashing with temperature -Maximum temperature alarm.
Sensor 1 temperature exceeds the parameter programmed in A1.
AL Flashing with temperature - Minimum temperature alarm.
Sensor 1 temperature is lower than the parameter programmed in A2.
oFF Unit off - STANDBY Mode (equipment maintains electric power supply)
CPY Parameters received from the parameters server.
E1 Sensor 1 failure (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC
E2 Sensor 2 failure (Open circuit, crossed, temp.> 110ºC or temp.<-55ºC
ES Incorrect sensor configuration (See P4, P8)
EE Memory failure

Other AKO Temperature Controllers manuals

AKO AKO-D14120 User manual

AKO

AKO AKO-D14120 User manual

AKO AKO-16526 User manual

AKO

AKO AKO-16526 User manual

AKO 14642 User manual

AKO

AKO 14642 User manual

AKO AKO-16526A User manual

AKO

AKO AKO-16526A User manual

AKO AKO-16524A User manual

AKO

AKO AKO-16524A User manual

AKO AKO-D14412 User manual

AKO

AKO AKO-D14412 User manual

AKO AKO-16624 User manual

AKO

AKO AKO-16624 User manual

AKO AKO-16523-V User manual

AKO

AKO AKO-16523-V User manual

AKO -D140 Series User manual

AKO

AKO -D140 Series User manual

AKO 16523 User manual

AKO

AKO 16523 User manual

AKO 14212 User manual

AKO

AKO 14212 User manual

AKO AKO-145601 User manual

AKO

AKO AKO-145601 User manual

AKO 16526A User manual

AKO

AKO 16526A User manual

AKO AKO-16525AN User manual

AKO

AKO AKO-16525AN User manual

AKO AKO-D14423-P User manual

AKO

AKO AKO-D14423-P User manual

AKO AKO-16624 User manual

AKO

AKO AKO-16624 User manual

AKO AKO-16520 User manual

AKO

AKO AKO-16520 User manual

AKO AKO-52062 User manual

AKO

AKO AKO-52062 User manual

AKO AKO-16523L User manual

AKO

AKO AKO-16523L User manual

AKO AKO-16523 User manual

AKO

AKO AKO-16523 User manual

AKO AKO-16524A User manual

AKO

AKO AKO-16524A User manual

AKO AKO-16525A User manual

AKO

AKO AKO-16525A User manual

AKO 156332 User manual

AKO

AKO 156332 User manual

AKO AKO-16524A User manual

AKO

AKO AKO-16524A User manual

Popular Temperature Controllers manuals by other brands

Honeywell T775A Product data

Honeywell

Honeywell T775A Product data

Kamstrup MULTICAL 403 Installation and user guide

Kamstrup

Kamstrup MULTICAL 403 Installation and user guide

Auriol AFT 77 A1 operating instructions

Auriol

Auriol AFT 77 A1 operating instructions

THORLABS Blueline Series Operation manual

THORLABS

THORLABS Blueline Series Operation manual

Eurotherm 3116 PID user guide

Eurotherm

Eurotherm 3116 PID user guide

Shinko FCL-130 instruction manual

Shinko

Shinko FCL-130 instruction manual

Carrier NSB-10K-2-O-BB2 Installation and operation

Carrier

Carrier NSB-10K-2-O-BB2 Installation and operation

Adam PMB manual

Adam

Adam PMB manual

dixell XR460C Installing and operating instructions

dixell

dixell XR460C Installing and operating instructions

Novus N1050 user manual

Novus

Novus N1050 user manual

Azbil HTY7903T Specifications & instructions

Azbil

Azbil HTY7903T Specifications & instructions

Omron E5CC Solution guide

Omron

Omron E5CC Solution guide

Lucky Reptile Thermo Control II Operation instructions

Lucky Reptile

Lucky Reptile Thermo Control II Operation instructions

Vaillant VR 92/3 Operating and installation instructions

Vaillant

Vaillant VR 92/3 Operating and installation instructions

Barber-Colman 7EM instruction manual

Barber-Colman

Barber-Colman 7EM instruction manual

Yolink YS8006-UC Installation manual & users guide

Yolink

Yolink YS8006-UC Installation manual & users guide

Autonics TC3YF Series product manual

Autonics

Autonics TC3YF Series product manual

La Crosse Technology Alerts TX60U-IT quick start guide

La Crosse Technology

La Crosse Technology Alerts TX60U-IT quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.