Carbolite P1 User manual

MC18-GB – v1.04
Operating Instructions
Temperature Controller
T
yp
e 3216 P1 P5
English

2 MC18-GB – v1.04

3216 Controller
3
MC18-GB – v1.04
Contents
1INTRODUCTION TO THE CONTROLLER AND MANUAL 4
1.1 USING THIS MANUAL 4
1.2 PID CONTROL 4
2BASIC OPERATION 5
2.1 CONTROLLER LAYOUT (HOME DISPLAY) 5
2.2 KEYS 5
3QUICK START GUIDE 6
3.1 OPERATION AS A SIMPLE CONTROLLER 6
3.2 CHANGING THE SET POINT 6
3.3 USING THE CONTROLLER 6
3.4 UNDERSTANDING USER LEVELS 6
4SETTING UP THE CONTROLLER 8
4.1 MAXIMUM OUTPUT POWER SETTING 8
4.2 CUSTOMER ID. 8
4.3 UNITS 8
4.4 LANGUAGE 8
4.5 SCROLLING TEXT 8
4.6 CUSTOMER CALIBRATION 9
4.7 HOLDBACK 10
5PROGRAMMING 10
5.1 CREATING A PROGRAM 10
5.2 RUNNING A PROGRAM 12
5.3 PROGRAM STATUS 12
5.4 PROGRAM EXAMPLE 14
6OPTIONS 15
6.1 DIGITAL COMMUNICATIONS –RS232 15
6.2 DIGITAL COMMUNICATIONS –RS485 15
6.3 COMMS ADDRESS 16
6.4 ALARM OPTION 16
6.5 REMOTE INPUT AND OUTPUT (ANALOGUE COMMUNICATIONS) 16
7NAVIGATION DIAGRAMS 16
7.1 3216P1 &3216P5 17
8CONTROLLER FAULT 18
8.1 FAULT CODE DIAGNOSTIC TABLE 18
9GLOSSARY OF TERMS 18

Introduction
4 MC18-GB – v1.04
1 Introduction to the Controller and Manual
1.1 Using This Manual
This manual aims to explain how to set up and operate the Eurotherm 3216 series of
controllers; it must be read in conjunction with the product main manual.
Due to the complex nature of furnace or oven control the use of technical terms throughout
this manual is unavoidable. Explanations of these terms can be found in the ‘Glossary of
Terms’ at the back of this manual.
This manual covers the operation of:
1.1.1 3216P1 - Controller/Programmer
The 3216P1 is a digital temperature controller which uses PID algorithms to give excellent
temperature control. This controller can store and run a single program of 8 ramp/dwell
segments. The 3216P1 can also be used as a simple temperature controller.
1.1.2 3216P5 - Controller/Programmer
The 3216P5 is a digital temperature controller which uses PID algorithms to give excellent
temperature control. This controller can store up to 5 programs of 8 ramp/dwell segments.
The 3216P5 can also be used as a simple temperature controller.
1.2 PID Control
The 3216 series of controllers use PID (Proportional Integral Derivative) temperature
control. This type of control uses a complex mathematical control system to adjust the
power being sent to the elements and to hold the furnace or oven at the desired
temperature.

Basic Operation
5
MC18-GB – v1.04
2 Basic Operation
2.1 Controller Layout (Home Display)
2.2 Keys
Page Key The Page key is used to access level 2 when held down
for 3 seconds.
Scroll Key 3The Scroll key is used to scroll through the parameters.
ACK
Page + Scroll
3
When pressed simultaneously the ACK function is used
to:
•Return to the Home Menu.
•Acknowledge an alarm if activated.
•Reset a program after the program has ended
Arrow Keys
ST
The arrow keys are used individually to adjust the
selected parameters and in combination to run a program
Note: If a parameter is selected and no further action is taken, the display will time out and
revert back to the home display in its working level after approximately 1 minute
Power Output
Indicato
r
Scroll Key Down KeyUp Key
Alarm
Indicato
r
Hold Indicator
Setpoint
Tem
p
erature
Measured
Temperature
Run Indicator
Remote
Indicator
(When configured)
Scroll KeyPage Key

Quick Start Guide
6 MC18-GB – v1.04
3 Quick Start Guide
3.1 Operation as a simple controller
When switched on, the controller goes through a short test routine and then shows the
measured temperature (PV = Process Value) in the upper part of the display, and below it,
the set temperature (Set Point).
3.2 Changing the Set Point
Press Up Sor Down Tto select the required SP. If the SP is higher than the measured
temperature, the OP1 indicator will illuminate in the top left corner of the display, indicating
that the controller is calling for power (giving an output).
The controller will immediately attempt to reach the set temperature and then maintain it.
3.3 Using The controller
The parameters in the controller are first shown by a short code (mnemonic). After 5
Seconds a description of the parameter will scroll once along the display and then revert
back to the mnemonic. The scrolling text can be interrupted at any time by a single press of
any of the buttons, but will not scroll again until the parameter is returned to. In this manual
the mnemonic will be shown first, followed by the scrolling text in brackets;
e.g. Prog <program number>
3.4 Understanding User Levels
There are two user levels in the controller; Level 1(Operator) and Level 2 (Supervisor).
Level 1 (Operator) is for the day to day operation of the controller. These parameters are
not protected by a security code.
Level 2 (Supervisor) provides access to additional parameters. Access to these is protected
by a security code
To Enter Level 2
1. Press and hold the page key for 3 seconds.
2. The display will show Leu 1 GOTO
3. Release the page Key
4. Press the UpSor Down Tto choose LEu 2 (level 2)
5. Press the Up Sor Down Tto enter the code (Level 2 Code = 9).
If the correct code is entered, PASS should momentarily be displayed and then revert to the
level 2 home display (See Section 5.3)
If an incorrect code is entered the display reverts back to Level 1 home display (See Section
5.3)

Quick Start Guide
7
MC18-GB – v1.04
When level 2 operations have been completed, the supervisor must return to Level 1 either
manually or by ‘power cycling’, there is no time out function.
To Return to Level 1
1. Press and hold the page Key
2. Press Down Tto select LEu 1
It is not necessary to enter a code when going from a higher level to a lower level
When level 1 is selected, the display reverts to the home display (See Section 2.1)
Table showing parameters accessible in level 1 and Level 2
Operator LEVEL 1 Supervisor LEVEL 2
Home display Home Display
Programming Programming
Program Status Program Status
Alarms (if configured)
Current Transformer Input (if configured)
Comms (if configured)
Controller setup
Customer Calibration
TIP
If while navigating the controller a parameter has been passed or you need to access
parameters which would be at the end of a scroll list, press and hold Scroll 3and use Up
Sto return to a previous parameter.

Programming
8 MC18-GB – v1.04
4 Setting up the controller
Before using the controller (or during its lifetime) certain parameters may have to be set,
depending on specific requirements. To do this the controller must be set to supervisor level
(Level 2) see section 3.4
4.1 Maximum Output Power Setting
Press scroll 3until the display shows OP.HI <Output High>. Using Up Sand Down T
select the output power required as a percentage.
Depending on the furnace or oven model, the maximum output power setting OPHi may be
accessible or locked.
For Silicon Carbide heated furnaces, the parameter is accessible to allow compensation for
element ageing. Refer to the product manual for details.
In many models the maximum output power setting depends on the supply voltage, refer to
the product manual for details.
4.2 Customer ID.
A furnace or oven identification number can be entered if required. This maybe used to
identify one of many units, for production or quality control systems.
Press scroll 3until the display shows ID <customer ID>. Using the Up SDown Tenter
your own identification number. This can range from 1-9999.
4.3 Units
Press scroll 3until the display shows units <Display Units>. Using the Up Sor Down
Tselect the required units.
Mnemonic Description
nonE No units (Default °C)
°C Celsius
°F Fahrenheit
°K Kelvin
PErc %
4.4 Language
The scrolling text on the 3216 can be shown in different languages, this can only be set at
the factory and therefore must be specified at the time of placing an order.
4.5 Scrolling Text
If at any time the scrolling text is not required.
Press and hold the Page for three seconds until “GOTO” is displayed

Programming
9
MC18-GB – v1.04
Press Scroll 3until the display shows. TEXT <ENABLE/DISABLE SCROLLING TEXT>
Use the Up SDown Tto select ON or OFF
4.6 Customer Calibration
The 3216 series of controllers are calibrated for life at manufacture, there may however be
sensor or other system errors, which affect the accuracy of the measured temperature.
Customer calibration can be used to compensate for these errors.
Dual Offset
Dual point calibration uses two offset values at two corresponding temperatures; this
changes the calibration linearly as the temperature increases or decreases.
Press scroll 3until the display shows CAL.P (Enter Calibration Code) Use Up SDown
Tto enter the password code. (Calibration Pass Code = 95). When the correct password
has been entered the display will show PNT.LO. If the wrong pass code is entered the display
will revert to zero pass code, until the correct pass code is entered.
When the correct pass code is entered and PNT.LO (Adjust Low Point) is displayed. Use
Up SDown Tto enter the Low Temperature Point, which you want to apply an Offset.
Press scroll 3until the display shows OFS.LO (Adjust Low OFFset). Use Up SDown Tto
enter the amount Offset you want to apply to the Low Temperature Point.
Press scroll 3until the display shows PNT.HI (Adjust High Point). Use Up SDown T
to enter the High Temperature Point, which you want to apply an Offset.
Press scroll 3until the display shows OFS.HI (Adjust High OFFset). Use the Up SDown
Tto enter the amount Offset you want to apply the High Temperature Point.
Once the calibration details have been entered, press scroll 3until the display shows the
next required parameter or return to the home list. The calibration data will now be protected
by the pass code. To edit the data the above procedure must be followed.

Programming
10 MC18-GB – v1.04
Single Offset
If a constant offset is required across the temperature range, set the required “High Point”
(PNT.HI) and “Low Point” (PNT.LO) to the required values (not the same), then set the “low
Offset” (OFS.LO) and “High Offset” (OFS.HI) to the same value.
Caution! - Do not make PNT.LO and PNT.HI the same value as the controller will
not work correctly and could cause your furnace or oven to overheat.
4.7 Holdback
If the temperature ramp rate of the program is quicker than the furnace or oven can achieve,
the program will wait until the temperature of the furnace or oven catches up.
e.g. If a Holdback value of 10 is set and the program is set to ramp to a setpoint of 600°C,
the program will reach 600°C, then go into an hold state; the hold indicator will light until the
furnace or oven temperature reaches 590°C, the program will then continue to control
again.
The hold back will only apply once per Segment, therefore when control has been re-
established, the hold back will not apply again to that segment, even if the furnace or oven
temperature go outside the hold back band.
Holdback can only be accessed in supervisor level (level 2) by scrolling with the Scroll 3
until the display shows H.BACK <PROGRAM HOLD BACK>: Use the Up SDown Tto select the
required Hold Back value.
If a multi programmer is used, each program can have its own Holdback value assigned to
it.
Note: When a Holdback is set, each segment used must have a Ramp Rate assigned
to it, in order for it to be recognised by the program.
5 Programming
5.1 Creating a Program
Programs can be created in level 1 or level 2 of the 3216 P1 and 3216P5. Each program
contains 8 Ramp/Dwell pairs.
Note:
A currently active program cannot be altered. Go into reset mode before starting to create or
modify a program
Program Number (3216 P5 Only)
Press scroll 3until the display shows PROG <PROGRAM NUMBER.>Select the program
number.

Programming
11
MC18-GB – v1.04
Ramp Units
Press scroll 3until the display shows RAMP.U <Ramp Units>: Use the Up SDown Tto
select the Ramp Units of Hour, Min or Seconds.
Dwell Units
Press Scroll 3until the display shows DWEL.U <Dwell Units>: Use the Up SDown Tto
select the Dwell Units of Hour or Min.
Holdback (See section 4.7)
Press Scroll 3until the display shows H.BACK <Program Hold Back>: If a Holdback value is
required, use the Up SDown Tto enter the required value or select “OFF” if no holdback is
required.
Ramp Rate
Press Scroll 3until the display shows RMP.1 <Ramp Rate 1>: Using the Up SDown T
enter the value for the first ramp rate depending on the Ramp Units selected. If the Ramp
segment is not required select “OFF”.
Target Setpoint
Press Scroll 3until the display shows T.SP 1 <Target SP 1>: Enter the temperature that
you want the unit to ramp up to using “Ramp rate 1”.
If “Ramp Rate 1” has been set to “OFF”. The unit will Heat/Cool directly to the Target SP.
Dwell Time
Press Scroll 3until the display shows DWELl. 1 <DWELL TIME 1>: Enter the time to dwell
at “Target SP 1”. If the dwell segment is not required, use the Down Tto select OFF, which
is below the Zero value.
This Process is repeated for each of the 8 segments of the program.
If not all the segments are used for a program, the Ramp & Dwell of each of the subsequent
Segments should be set to OFF.
A program will end in one of two ways, either revert to the control Set Point or dwell at the
temperature set in the last segment used. When a program finishes on a dwell and the dwell
time expires the temperature will revert to the control setpoint.
Note: Before running a program ensure that the control set point is set to Zero to avoid
unexpected heating at the end of the program.

Programming
12 MC18-GB – v1.04
5.2 Running a Program
If using the 3216P5 controller Press Scroll 3to display PROG <PROGRAM NUMBER> select the
required Program Number before running a Program.
Table below shows the key presses to run a program
Operation Action Indication
To RUN a program Press and quickly
release S+ TIndicator – RUN = On
Scrolling Display – Current Program state
To HOLD a
program Press and quickly
release S+ TIndicator – RUN = Flashing
Scrolling Display – Program Hold
To RESET a
program Press and Hold
S+ Tfor more than
1 second
Indicator – RUN = Off
Scrolling Display - None
Program Ended Indicator – RUN = Off
Scrolling Text – Program End
To RESET a
program after it
has completed
Press and Hold
S+ Tfor more than
1 second
Or
Press and quickly
release
Ack 3
Indicator – RUN = Off
Scrolling Display - None
5.3 Program Status
While the program is running in level 1 or level 2, the Home Display shows two values at
any one time:
Process Value
The upper display shows the measured temperature of the furnace (PV).
PSP, Segment Type and Number
The lower display continually alternates between the programs current set value (Program
SP = PSP) and scrolling text, indicating the current status of the program whether RAMP or
DWELLING followed by the segment number.
Additional information can be obtained using the scroll 3key while the program is running.
Working Output Power
From the home display, press Scroll 3until the display shows WRK.OP <WORKING OUTPUT
POWER>This shows the power being used as a percentage.

Programming
13
MC18-GB – v1.04
Time Remaining
Press scroll 3until the display shows T.REMN <TIME REMAINING>. This shows the dwell
time remaining for the current segment. There is no value for “Ramp Time Remaining”
therefore when the program is ramping the dwell time set will be shown and will only begin
to count down when the ramp has finished.
Program Review
Further presses of scroll 3will reveal the settings of the current program running. These
parameters are locked, while the program is running.
Program Hold with Holdback
If a holdback value has been set (see Programming section 4.7) and the program goes into
a hold state, the red “HLD” indicator will light, until the “PV” catches up.
If while in this condition the program itself is put into “Hold” by pressing the Up S, Down T
together, the “HLD” indicator will turn off and the “Run” indicator will flash, indicating the
program is on hold. When the program is started again by pressing the up S, down T
together, the “Run “ indicator will stop flashing and show continually and the “HLD” indicator
will light, if the “PV” has not caught up with the program.
Power Failure
If there is a power failure while the program is running and the power is subsequently
restored, the scrolling text will read <POWER FAIL - PROGRAM RESET>.
To acknowledge this message and to reset the program Press “ACK” function
Alarms
Alarms are used to alert the operator when a pre-set level has been exceeded or a function
error has occurred such as a sensor break. They are indicated by a scrolling message on
the display and a flashing red ALM (Alarm) indicator. The alarm may also switch an output –
usually a relay to allow external devices to be operated when an alarm occurs. Alarms only
operate if they have been configured and are dependant on customer requirements.
How to Acknowledge an alarm will depend on the type of latching which has been
configured. A non-latched alarm will reset itself when the alarm condition is removed. A
latched alarm requires acknowledgement with the “ACK” Function (Section 2.2) before it is
reset.
If an alarm has been activated the red “ALM” indicator will light and the scrolling text will
indicate the type of alarm.
To Acknowledge an alarm and cancel the “ALM” indicator, press ACK function.
Note:
The alarm indicator may seem to be permanently on when viewed from above. When an
alarm is active the indicator should only be flashing, to confirm this, the controller must be
viewed directly from the front.

Program Example
14 MC18-GB – v1.04
5.4 Program Example
The following sequence of entries creates and runs the program shown graphically below.
1. Press Scroll until the display shows RAMP.U <SP RAMP UNITS>. Select MIN.
2. Press Scroll until the display shows DWELL.U <DWELL UNITS>. Select MIN.
3. Press Scroll until the display shows RMP.1 <RAMP RATE 1>. Select 5
4. Press Scroll until the display shows T.SP1 <TARGET SP 1>. Select 600
5. Press Scroll until the display shows DWEL.1 <DWELL TIME 1>. Select 30
6. Press Scroll until the display shows RMP.2 <RAMP RATE 2>. Select 4
7. Press Scroll until the display shows T.SP2 <TARGET SP 2>. Select 400
8. Press Scroll until the display shows DWEL.2 <DWELL TIME 2>. Select 30
9. Press Scroll until the display shows RMP.3 <RAMP RATE 3>. Select OFF
10. Press Scroll until the display shows T.SP3 <TARGET SP 3>. Select 600
11. Press Scroll until the display shows DWEL.3 <DWELL TIME 3>. Select 60
12. Press Scroll until the display shows RMP.4 <RAMP RATE 4>. Select 3
13. Press Scroll until the display shows T.SP4 <TARGET SP 4>. Select 800
14. Press Scroll until the display shows DWEL.4 <DWELL TIME 4>. Select OFF
15. Press Scroll until the display shows RMP.5 <RAMP RATE 5>. Select 5
16. Press Scroll until the display shows T.SP5 <TARGET SP 5>. Select 400
17. Press Scroll until the display shows DWEL.5 <DWELL TIME 5>. Select 480
18. Press the ACK function to return to the home display (section 2.2).
19. Press the Up S, Down Ttogether, to run the program.
3°C/Min 5°C/Min
4°C/Min
30 Min 30 Min 60 Min
800
°
C
480 Min
Segment 1
RMP.1 = 5°C/Min
T.SP1 = 600°C
DWEL.1 = 30 Min
Segment 2
RMP.1 = 4°C/Min
T.SP1 = 400°C
DWEL.1 = 30 Min
Segment 3
RMP.1 = OFF
T.SP1 = 600°C
DWEL.1 = 60 Min
Segment 4
RMP.1 = 3°C/Min
T.SP1 = 800°C
DWEL.1 = OFF
Segment 5
RMP.1 = 5°C/Min
T.SP1 = 400°C
DWEL.1= 480 Min
5°C/Min
600
°
C
600
°
C
400
°
C
400°C
5°C/Min

Options
15
MC18-GB – v1.04
6 Options
Because options can be ordered in a variety of combinations and for a variety of purposes,
exact instructions are not given here. The full Eurotherm manual may be required to
determine customer parameter settings. To reveal or hide parameters in the controller it is
necessary to go into configuration modes and enter a security codes. Please consult
Carbolite.
6.1 Digital Communications – RS232
If the RS232 option is supplied, then the furnace is fitted with one subminiature D-socket
connected to the controller communications (comms) module. RS232 is suitable for direct
connection to a personal computer (PC), using a “straight through” cable as follows (the
linked pins at the computer end are recommended but may not be necessary). The cable is
usually 9-pin at the furnace end and 9-pin at the computer, but other alternatives are shown
in parentheses.
Furnace end of cable RS232 Cable: furnace to PC Computer end of cable
female 9-pin (25-pin) 9-pin (25-pin) male
Rx 3 (2) 3 (2) Tx
Tx 2 (3) 2 (3) Rx
Com 5 (7) 5 (7) Com
7,8 (4,5) Link
together
1,4,6 (6,8,20) Link
together
6.2 Digital Communications – RS485
If an RS485 option is supplied, then the furnace is fitted with two sub-miniature D-sockets.
Connection between products is by “straight” cable as follows:
RS485 cable:
furnace to furnace
female 9-pin (25-pin) 9-pin (25-pin) female
−3 (2) 3 (2) −
+ 2 (3) 2 (3) +
Com 5 (7) 5 (7) Com
If a boxed KD485 RS485 to RS232 converter is supplied, then the connection cable from
furnace to KD485 should be a “straight” cable, the same as the furnace-to-furnace cable.
The connection between the KD485 and the PC should be a “crossover” cable, the same as
the Furnace to PC cable in section 6.1.

Options
16 MC18-GB – v1.04
6.3 Comms Address
Typically the comms address is set to 1, but this can be changed. In the case of RS485 and
multiple instruments it is necessary to set different addresses.
To change the address value access the level 2 list. In level 2 press the scroll key 3until
the ADDR (ADDRESS) parameter is displayed. Use the Up SDown Tto select the address
value.
6.4 Alarm Option
When an alarm board is fitted with free contacts for customer use, the contacts are taken to
a panel plug on the control panel, wired as indicated:
The purpose of the 2 amp fuse is to guard against the connection of a mains supply to the
panel plug.
The instrument configuration, and parameters available to the operator, depend on the
customer requirements.
6.5 Remote Input and Output (Analogue Communications)
When analogue communications are fitted, the contacts are taken to Insulated terminal
sockets on the control panel.
Controller configuration depends on customer requirements.
Remote input (when specified) may be switched on and off using the Alternative Setpoint
Enable parameter in the controller home list, if this was made available for a particular
application. Remote output does not require switching on and off.
7 Navigation Diagrams
load
Controller
2A fuse
su
pp
l
y
n/o
controller

Navigation
17
MC18-GB – v1.04
7.1 3216P1 & 3216P5
WRK.OP TEXT WRK. OP rmp. 8
Prog Prog t.sp8
ramp.U ramp. U dwel.8
dwel.U dwel. U A1 . #
rmp.1 h.back A2. #
t.sp1 rmp.1 A3. #
dwel.1 t.sp1 A4. #
dwel. 1 op. hi
rmp.8 LD.AMP
t.sp8 LK.AMP
dwel.8 LD.ALARM
LD. AMP If Configured LK.ALARM
ID HC.ALARM
ADDR
ID
UNITS
CAL. P PNT.LO
OFS.LO
PNT.HI
OFS.HI
Through to
If Configured
Through to
Multi programOnly
If Configured
If Configured
Do not raise the power limit
(If accessible) above the
design level for the product
3 Sec Pass code = 9
3 3
3
Pass code = 95
T
S
33

Controller Fault
18 MC18-GB – v1.04
8 Controller Fault
8.1 Fault Code Diagnostic Table
Error Code Explanation Actions
S.br Temperature sensor failure Replace the Furnace or Oven
Temperature Sensor
9 Glossary of Terms
Process Value (PV) The actual temperature of the furnace or oven. °C
Setpoint (SP) The target temperature the furnace or oven is trying to
reach. °C
SP Ramp Rate The speed at which the furnace or oven is allowed to
heat up or cool down. °C/Min
Control Setpoint The temperature that can be directly set into the
controller using the Up and Down keys -
Element The heating device used in the furnace or oven. -
Thermocouple The temperature-measuring device used in the furnace
or oven. -
PID Proportional Integral Derivative: the control system used
by the controller. -
Overtemperature (O/T) The condition which a furnace or oven may enter if part
of the main control circuit fails. -
Overtemperature
Protection
A system to prevent the product or process being
damaged if it has gone into an overtemperature
condition. -
Ramp/Dwell Pairs A Program is split up into segments, each segment
Contains a Ramp and a dwell. -
Program A sequence of stored Parameters set by the operator,
which will run automatically when started. -
Latched Alarm Will hold the alarm condition once it has been detected. -
Non-Latching Alarm Will reset itself when the alarm condition is removed. -
Power Cycling The Power to the controller is turned off and then back
on. -

Notes
MC18-GB – v1.04

Copyright © 2008 Carbolite Limited
For preventive maintenance, repair and calibration of all Furnace
and Oven products, please contact:
Thermal Engineering Services
Telephone: UK: 0845 3308035 Int: +44 1433 623335
Fax: UK: 0845 3308036 Int: +44 1433 623336
Carbolite, Parsons Lane, Hope,
Hope Valley, S33 6RB, England.
Telephone: (01433) 620011
Int: +44 1433 620011
Facsimile: (01433) 621198
Int: +44 1433 621198
E-mail: [email protected]
MC18-GB-C – 1.04 05/06/08
This manual suits for next models
3
Table of contents
Other Carbolite Temperature Controllers manuals