
Residential HRV/ERV
14
wall or in the ceiling. If the diffuser is located in a common area, it is recommended to place
it on the ceiling so that it can better mix with the air in the room before reaching occupants.
This will improve comfort in cold weather. If diffusers are installed on the wall, place them at
least 12 inches (30 cm) from the ceiling.
Adjustable grilles can be used to balance the flow rates. Field supplied balancing dampers
can be external to the unit to balance the amount of fresh air being supplied relative to the
other diffusers. These grilles should not be adjusted after balancing the unit.
Zone Register Terminals (ZRT®)
Aldes patented* Exhaust Zone Register Terminals (ZRT®) are designed to introduce
flexibility and on-demand control to central ventilation systems. Used in both large
and small systems, the ZRT zonally regulates ventilation without the need for individual
fans. Each ZRT is a combination grille, register box, control damper, and optional flow
regulator(s). This unique combination provides up to four different control schemes
without the need for expensive pneumatic,
electronic, or DDC control systems.
By replacing static grilles in large central exhaust
systems, the ZRT-1 model provides on-off control
for on-demand ventilation. The optional Constant
Airflow Regulator can be installed in the ZRT-1’s
extended duct collar to place a maximum flow
limit on each terminal. The ZRT-1 does not work
well when continuous low ventilation is needed;
therefore using the ZRT-1 in a location such as a half
bath is the best application of use.
The ZRT-2 model can be used for combination low-flow indoor air quality ventilation
and on-demand high-flow spot ventilation using the same central fan system. This is
achieved by integrating a minimum Constant Airflow Regulator directly into the damper
sub-assembly. With the damper completely closed, the factory-calibrated will still allow
steady, low-continuous ventilation during fan operation. When other ZRT are opened
for on-demand control of spot ventilation, the closed ZRT-2 will maintain the specified
low-continuous rate through the minimum. By opening the ZRT-2’s control damper, the
low-flow is removed from the air stream, allowing either controlled (optional using a
second) or full maximum-boost ventilation. Using the ZRT-2 in a location such as a full
bathroom is the best application of use.
Humidity Control
Tight, well-insulated homes may have high indoor humidity levels during the heating
season. High humidity will be apparent from visible condensation on windows. The amount
of window condensation will increase as outdoor temperatures drop.
ZRT-1
*U.S. Pat. No. 7,766,734 Canada Pat. No. 2,570,948