WARNING!
"I"
"0"
4
Operation and Maintenance:
To prevent coil damage resulting
from multiple start attempts in a
short period of time, a starting
inhibit function has been added
to the coil circuit.
A start attempt is dened as any
application of control voltage to
the coil. A short interrupt in the
incoming voltage, or voltage
dip, will be seen as a start
attempt as well.
The starting inhibit function can
only be reset by disconnecting
control voltage from A1 and A2
for at least 30 seconds.
In this case the coil circuit has
not been damaged, but action
should be taken to avoid the
control power interruptions
where applicable.
For Emergency Switching O,
the coil Circuit A1-A2 and the
Interface Circuit B1-B2 must be
disconnected.
Interface mode: Insert jumper in
position "EI", see illustration on
page 5.
Operating without interface mode:
Insert jumper in position "E".
Attention: With power supply
applied to A1-A2, the operating
voltage is present on the coding
plug.
After a short circuit the main
contacts and arc-chute must be
examined!
With the arc-chute removed the
contactor is mechanically locked.
When the coil is energized the
arcchute is mechanically locked.
Before removing the arc-chute,
switch o the contactor!
If the contacts are welded, the
arcchute can be removed by
exerting more force. Slight welds
can be separated with a
screwdriver.
Attention: Do not bend contacts
and connecting bars!
Do not lubricate or grease
magnet assemblies.
The main contacts, arc chute,
auxiliary switch block and magnet
coil can be replaced.
Attention: Voltage indication on
magnet coil, control printed
circuit board and 100-DFSV must
correspond.
Max. number of auxiliary contact
blocks allowable per contactor:
- 2 auxiliary contact blocks max.
with contactor mounted in the
horizontal position.
- 4 auxiliary contact blocks for all
other mounting positions.
Use original spare parts only to
assure the reliability of the
contactor!
Betrieb und Wartung:
Zur Verhinderung von Schäden
durch mehrere in einem kurzen
Zeitraum erfolgte Startversuche
ist eine Halt- Funktion im
Spulenkreis eingebaut.
Jedes Anlegen einer Spannung
an die Spule wird als
Startversuch angesehen. Eine
kurze Unterbrechung oder
Absenkung der Steuerspannung
wird als Startversuch deniert.
Zur Aufhebung der Halt-Funktion
muss die Steuerspannung an A1
und A2 während 30s
unterbrochen werden.
Der Spulenkreis ist nicht beschä-
digt, aber es sollten Massnahmen
ergrien werden um Steuer-
spannungsunterbrüche oder
-absenkungen nach Möglichkeit
zu vermeiden.
Für das Stillsetzen im Notfall,
muss der Steuerstromkreis A1-A2
und der Interface-Kreis B1-B2
unterbrochen werden.
Interfacebetrieb: Kodierstecker auf
Position "EI", siehe Illustration auf
Seite 5. Betrieb ohne Interface:
Kodierstecker auf Position "E".
Achtung: Bei angelegter
Spannungsversorgung an A1-A2
liegt die Betriebsspannung am
Kodierstecker an.
Nach einem Kurzschluss müssen
Hauptschaltstücke und
Löschkammer überprüft werden!
Bei entfernter Löschkammer ist
das Schütz mechanisch verriegelt.
Bei erregter Spule ist die
Löschkammer mechanisch
verriegelt. Vor dem Abnehmen der
Löschkammer ist das Schütz
auszuschalten! Bei verschweissten
Kontaktstücken kann die
Löschkammer mit erhöhter
Betätigungskraft entfernt werden.
Leichte Verschweissungen können
mit Schraubendreher getrennt
werden.
Achtung: Kontaktstücke und An-
schlussschienen nicht verbiegen!
Der Magnetkern darf nicht geölt
oder gefettet werden.
Austauschbar sind Hauptschalts-
tücke, Löschkammer, Magnet-
spule und Hilfsschalterblöcke.
Achtung: Spannungsangabe auf
Magnetspule, Steuerprint und
100-DFSV müssen korrespon-
dieren.
Maximal zulässige Anzahl
Hilfsschalterblöcke pro Schütz:
- Maximal 2 Hilfsschalterblöcke in
horizontaler Montagelage.
- Maximal 4 Hilfsschalterblöcke in
allen anderen Montagelagen.
Nur Original-Ersatzteile verwenden
um die Betriebssicherheit der
Schütze zu gewährleisten!
Emploi et maintenance:
Pour éviter des dommages dus à des
démarrages répétés sur une courte
période de temps, une fonction de
blocage de démarrage est intégrée
au circuit de contrôle de la bobine.
Par dénition, chaque application de
la tension de commande sur la bobine
est considérée comme une tentative de
démarrage.
Une courte interruption
de
la tension d’entrée ou un creux de tension
seront également vus comme tels.
Pour réinitialiser le système après
un tel blocage de démarrage, il est
nécessaire d’interrompre le circuit
A1/A2 pendant au moins 30 secondes.
Le circuit de commande de la
bobine n’est pas endommagé lors
de ces évènements, mais des
mesures devraient être prises pour
éviter ce genre d’interruptions ou
creux de tension.
Pour la mise à l'arrêt en cas
d'urgence, le circuit de commande
A1-A2 et le circuit de l'interface
B1-B2 doivent être interrompus.
Service avec interface: Pont de
codage sur position "EI",selon
l'illustration de la page 5.
Service sans interface: Pont de
codage sur position "E".
Attention: lorsque la tension d´ali-
mentation est appliquée en A1-A2,
la tension de service est également
présente sur le che de codage.
Après un court-circuit, il faut vérier
les pièces de la commutation princi-
pale ainsi que la chambre d'extinction!
Le contacteur est verrouillée
mécaniquement lorsque l'on enlève
la chambre d'extinction. La chambre
d'extinction est verrouillée mécanique-
ment lorsque la bobine est excitée.
Déclencher le contacteur avant
d'enlever la chambre d'extinction!
Si les pièces de contact sont soudées,
la chambre d'extinction peut être
enlevée en exerçant une force accrue.
Des soudures légères peuvent être
défailes, le cas échéant, au moyen
d'un tournevis.
Attention: ne pas plier les contacts
et les barres de connexion.
Ne jamais lubrier ou graisser
l'assemblage de l'aiment.
Les éléments suivants peuvent être
remplacés: Pièces de commutation
principale, chambre d'extinction,
bobine magnétique et bloc de
commutation auxiliaire.
Attention: les tension indiquées sur
la bobine magnétique, la plaquette
de commande et la 100-DFSV
doivent correspondre.
Nombre maximum de blocs de
commutation auxiliaires permis sur
un même appareil:
- 2 blocs max. lorsque l´appareil est
installé horizontale.
- 4 blocs max. lorsque l´appareil est
installé dans toutes les autres
positions.
N’utiliser que des pièces de rechange
d’origine an d’assurer la sécurité de
fonctionnement des contacteurs!
Funzionamento e manutenzione:
Per evitare danni causati da vari
tentativi di partenza in un breve
periodo di tempo è incorporata e
funzione per arrestare del circuito
della bobina.
Ogni applicazzione di una tensione
alla bobina è considerata come un
tentativo di partenza. Una breve
interruzione o la riduzione della
tensione di controllo è denita
come un tentativo di avviazione.
Per annullare la funzione per
arrestare, la tensione di controllo
sui attacchi A1 e A2 deve essere
interrotta per 30 secondi.
In questo caso il circuito di controllo
della bobina non è danneggiato,
ma dovrebbero essere adottate
delle contromisure per evitare che
la tensione di controllo venga
ridotta o interrotta.
Per la messa d'arresto in caso
d'emergenza, il circuito di commando
A1-A2 e il circuito del'interface
B1-B2 deve essere interrotto.
F
unzionamento interfaccia; Inserire
la presa a codice nella posizione "EI"
vedi illustrazione a pagina 5. Funziona-
mento senza interfaccia: Inserire la
presa a codice nella posizione "E".
Attenzione: Se A1-A2 sono sotto
tensione d´alimentazione, la
tensione d´esercizio èapplicatta
alla presa a codice.
Dopo un cortocircuito, i pezzi di
contatto principale e la camera di
spegnimento sono da vericare!
A camera di spegnimento distaccata
,
il relé è bloccato meccanicamente.
A bobina eccitata, la camera di spegni
-
mento è bloccata meccanicamente.
Prima di smontare la camera di
spegnimento, disinserire il
contattore! In presenza di pezzi di
contatto ssati con saldatura, la
camera di spegnimento è smonta-
bile solo applicando una ragguarde-
vole forza sica. Saldature leggere
possono casomai essere separate
con un cacciavite.
Attenzione: non storcere i pezzi di
contatto e barre di collegamento!
Non lubricare o ingrassare
l'insieme
del magnete.
Scambiabili sono i pezzi di contatto
principale, la camera di spegni-
mento, la bobina magnetica e i
blocchi di contatto ausiliari.
Attenzione: Devono coincidere le
indicazione di tensione nella
bobina magnetica, il segnale di
comando e 100-DFSV.
Massimo numero di elementi di
contatto ausiliari consentiti per
contattore:
- massimo 2 elementi di contatto
ausiliari in caso di installazione
orizzontale.
- massimo 4 elementi di contatto
ausiliari in tutti gli altri casi di
installazione.
Impiegare solo pezzi di ricambio
originali, anché garantire la
sicurezza del contattore!
Servicio y mantenimiento:
Para evitar daños causados por
múltiples intentos de encender el
circuito, una función de parar es
integrada en el circuito de la
bobina.
Un intento de encender es cada
aplicación de voltaje de control a
la bobina. Una prevé interrupción
del voltaje de entrada o la bajada
del voltaje también es reconocido
como intento.
Para quitar la función de parar, el
voltaje de entrada debe ser
desconectada por 30 secundas de
A1 e A2.
En el caso que ocurrió la función
de parar, el circuito de la bobina
no es dañado. Si es posible hay
que evitar interrupciones del
corriente control.
Para la puesta en suspensiòn en caso
de emergencia, el circuito de mando
A1-A2 y el circuito de interface
B1-B2, tiene que ser interrumpido.
Funcionamiento Interface: Jumper
enchufado en posición "EI", mire la
ilustración en pagina 5. Modo de
funcionamiento sin Interface:
Jumper enchufado en posición "E".
Atención: Si la alimentación de
corriente se aplica en A1-A2, la
tensión de funcionamiento esta
presente en calvija de la codigo.
¡Después de un cortocircuito es
ecesario vericar los contactos
principales y la cámara de extinción!
Cuando se retira la cámara de extin-
ción el contactor queda enclavado
mecánicamente en posición descon-
ectado. Cuando el contactor está
conectado la cámara de extinción
está enclavada mecánicamente.
¡Desconectar el contactor antes de
retirar la cámara de extinción!
En caso de soldadura de contactos,
es posible desmontar la cámara de
extinción actuando sobre los tornillos
con un mayor esfuerzo. Si la soldadura
de contactos es ligera, estos pueden
separarse con un atornillador.
¡Atención: no doblar las piezas de
contacto y las barras de conexión!
No lubrique o engrase los
conjuntos magnéticos.
Los contactos principales, la cámara
de extinción, la bobina y los bloques
de contactos auxiliares pueden
serreemplazados.
¡Atención: Deben coincidir las indi-
caciones de tensión en la bobina
magnetica, la señal demando y
100-DFSV.
Máximo numero de bloques de
contacto auxiliar por cada contacto:
- 2 bloques de contacto auxiliar
maximo cuando el contactor esta
montado en la posición horizontal.
- 4 bloques de contacto auxiliar
maximo en todas las otras
posiciones de montaje.
¡Utilizar únicamente piezas de
recambio originales para asegurar
el funciona- miento correcto de los
contactores!