INTRODUCTION
Alpha-page is an call/alarm/fault signal monitoring system designed to instantly send
user programmed messages to alpha-numeric pocket pagers in response to an incoming signal.
The signal can be an AC or DC voltage or a dry contact closure. The system is stand-alone, it
does not require a computer or any other equipment. Alpha-page is designed to interface to
systems utilizing "home run" signal wiring. It is not intended for use in "multiplexed" systems
which do not use individual signal wires.
Alpha-page uses alphanumeric pocket pagers which can receive messages containing
numbers, letters, and punctuation symbols. You program a specific message for each call/
alarm/fault signal using a standard computer keyboard. Therefore, the message on a system
user's pager indicates the exact nature of the event, for example "Security alert-court room 1",
"blower motor 2-overheating", or "John Smith-room 101" (nurse call). The system can be
configured to best meet the needs of the facility. For example, the system can contain several
pagers that can each receive all pages. Or, several pagers may be used but each only receives
selected pages.
User programming is protected from erasure due to power failure with a built-in
lithium battery with a life-span of up to ten years. With the rechargeable 12V, 7Amp-hour
battery option, the entire system operates with battery back-up for up to 36 hours. When main
power is restored, the battery is automatically recharged.
MLS-EC1 ENCLOSURE INSTALLATION
The entire Alpha-page system (except transmitter and pagers) fits in the MLS-EC1
surface-wall mount enclosure. Determine a suitable location for the MLS-EC1. Remember,
wiring from each alarm/fault contact needs to be run to the MLS-EC1. Mount the MLS-EC1
in a location that will allow the most convenient means of running the required wiring
between the contacts being monitored and Alpha-page. Refer to drawings C022397-1 and
C022397-2 for enclosure dimensions and mounting hole locations.
ALARM SIGNAL WIRING
Each signal wire that is to cause a message to be transmitted must be connected to a
MLS-32L signal input board. Refer to the drawings in this manual for basic wiring
information. Note that there must always be a common voltage reference connected to the
"COM" terminal of the MLS-SPU1 board.
Alpha-page can monitor up to 256 alarm/fault signals. Each MLS-32L signal input
board can accommodate 32 call/alarm/fault signal wires. Therefore, more than one MLS-32L
board is required if more than 32 alarm/fault signals are being monitored, up to eight can be
used. The system can be expanded at any time by simply adding additional MLS-32L boards.
Each MLS-32L board is programmed with an "address" (1-8) which identifies it from the
other MLS-32L boards. Programming is accomplished by placing a programming jumper over
stake-pin pair 1-8 on the MLS-32L board (refer to drawing C022397-3). Later, you will
program each input with its own message. When programming messages, inputs are identified
on the liquid crystal display (LCD) as input 001-input 256. These will correspond to terminals
on MLS-32L boards. Terminals 1-32 on the MLS-32L board addressed as #1 will correspond