
12 Subject to technical amendments without prior notice | 83070100bUK | ait-deutschland GmbH
7 Electrical installation
IMPORTANT
Anincorrectrotatingeldwillcauseirreparabledam-
age to the compressor.
► Ensurethatthereisaclockwiserotatingeld for
the compressor load in-feed.
Basic electrical connection information
● Thespecicationsofthelocalenergysupplycom-
pany may apply to electrical connections.
●Equip the power supply for the heat pump with an
all-pole circuit breaker with at least 3 mm contact
spacing(accordingtoIEC60947-2)
●Observe the level of the tripping current (“Tech-
nicaldata/Scopeofsupply”,page21)
●Comply with the electromagnetic compatibility
(EMC)regulations
●Lay power supply cables and communication ca-
blessucientlyfarapart(>100mm)
●Cable on site
Permitted type of communication cable:
3x0.75mm²,(LiYY,EKKXorequivalent),
maximum cable length: 20 m
For the hydraulic tower HT 7 load cable:
One 3 x 2.5mm² cable with protective conductor,
diameter of sheath cable 10 mm
For the electric heating element load cable:
One 5 x 2.5mm² cable with protective conductor,
diameter of sheath cable 9-13 mm
7.1 Preparatory work
Installationofoutdoorsensors(required)
IMPORTANT
Install one of the RS (Split) sensors supplied with
the unit on the north or north-east side of buildings.
RS(Split)mustnotbeexposedtodirectsunlightand
must be installed so that it is protected from rain. The
cable entry into the housing must point towards the
ground.
1. Open the RS (Split) housing and align ≥ 2 m
above the ground at a suitable mounting point.
2. Mark and drill mounting holes. Hammer down the
wall plugs and screw the housing with cable entry
down to the wall.
3. Close the housing.
IMPORTANT
Moisture must no be trapped in the housing. If nec-
essary, completely drain the inside of the housing be-
fore installing the housing cover.
Make sure that the housing is leaktight as a result
of the zero potential installation and that water can-
not penetrate the housing at any time (for example,
duringtheconstructionstage).Sealanyexistingca-
ble ducts.
4. Route the sensor cable to the inside of the build-
ing and to the electrical switch box of the hydraulic
tower HT 7.
5. ConnectthesensorcableasBT1(outdoorsensor).
“7.2 Electrical connection”, from page 13
Installingaroomtemperaturesensor(optional)
NOTE
The control system works without a room
temperature sensor. However, in order to
read the current indoor temperature on the
display of the control panel and to change
the room temperature via the control system,
a room temperature sensor must be installed
and activated in the control system menu.
1. Install RS (Split) in a neutral location where the
set temperature is desired.
An example of a suitable location is a free interior wall
inthehallandapprox.1.5mfromtheoor.
NOTE
The sensor must not be prevented from mea-
suring a correct room temperature – for ex-
ample, by placing it in a niche, between
shelves, behind a curtain, above or near a
heat source, in a draught area of the exter-
nal door or in direct sunlight. Closed radiator
thermostats can also cause problems.
Changes of temperature in the home take time. For
example, switching underoor heating on for a short
period of time will not lead to a noticeable change in
room temperature.
If the RS (Split) is placed in a room with underoor
heating, it should only have a display function and no
control function for the room temperature.