- 2 - T2MK3F8Q2 Installation Guide
Overview:
Altronix T2MK3F8Q2 Trove Mercury kit is pre-assembled and consists of Trove2M2 enclosure with factory installed Altronix power supply/charger
and sub-assemblies. T2MK3F8Q2 kit also accommodates various combinations of Mercury boards for up to eight (8) doors in a single enclosure.
Configuration Chart:
Altronix
Model Number
120VAC
60Hz
Input
Current
(A)
Nominal DC
Output Voltage Maximum Supply
Current for Main and
Aux. Outputs on Power
Supply board and
ACM8 Access Power
Controller’s outputs
Fail-Safe/
Fail-Secure or
Dry Form “C”
Outputs
Current
Per
ACM8
Output (A)
Power
Supply
Board
Input
Fuse
Rating
Power
Supply
Board
Battery
Fuse
Rating
ACM8
Board
Input
Fuse
Rating
ACM8
Board
Output
Fuse
Rating
[DC] [Aux]
Output
Range
(VDC)
Output
Range
(VDC)
T2MK3F8Q2 3.5 20.19-
26.4
20.19-
26.4 24VDC @ 5.8A 8 2.5 5A/
250V
10A/
32V
10A/
250V
2.5A/
250V
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/ANSI, and with all local codes and authorities having jurisdiction.
Product is intended for indoor use only.
1. Remove backplane(s) from enclosure. Do not discard hardware.
2. Mark and predrill holes in the wall to line up with the top three keyholes in the enclosure. Install three upper fasteners and screws in the
wall with the screw heads protruding. Place the enclosure’s upper keyholes over the three upper screws, level and secure. Mark the position
of the lower three holes. Remove the enclosure. Drill the lower holes and install the three fasteners. Place the enclosure’s upper keyholes
over the three upper screws. Install the three lower screws and make sure to tighten all screws.
3. Mount included UL Listed tamper switch (Altronix Model TS112 or equivalent) in
desired location, opposite hinge. Slide the tamper switch bracket onto the edge of the
enclosure approximately 2” from the right side (Fig. 1, on the right).
Connect tamper switch wiring to the Access Control Panel input or the appropriate
UL Listed reporting device. To activate alarm signal open the door of the enclosure.
4. Mount Mercury boards to backplane, refer to pg. 3.
5. Refer to the eFlow Power Supply/Charger Installation Guide for eFlow6NB,
and corresponding Sub-Assembly Installation Guides for LINQ2 and ACM8
for further installation instructions.
Hardware:
Fig. 1
Tamper Switch
(provided)
To Access Control Panel or
UL Listed Reporting Device
Edge of
Enclosure
Enclosure
Snap On Spacer | 5/16” Pan Head Screw | Lock Nut