- 2 - AL802ADA220J
Overview:
Altronix AL802ADA220J is an extremely cost-effective 8A remote power supply/battery charger. It may be
connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary applications include Notification
Appliance Circuit (NAC such as strobes and horns) expansion support to meet ADA requirements. It also pro-
vides auxiliary power to support system accessories. The unit delivers electronically regulated and filtered 24 volt
power to Class B, Style W, Y or Class A, Style Z NAC loop circuits. Additionally, a separate 1.0A auxiliary out-
put with reset for four (4)-wire smoke detectors is available. The 8A max. alarm current can be divided between
the four (4) outputs for powering NAC devices. Each output is rated at 2.5A max., and can be independently
programmed for Steady, Temporal Code 3 or Strobe Synchronization. All outputs may be programmed for Input
to Output Follower Mode (output will follow input, i.e. March Time Input, March Time Output). In non-alarm
condition independent loop supervision for Class A, Style Z and/or Class B, Style W, Y FACP NAC circuits is
provided. In the event of a loop trouble, the FACP will be notified via the steered input (input 1 or input 2). In
addition, there are common trouble output terminals [NC, C, NO] which are used to indicate general loop/system
trouble. A common trouble input is provided for optional NC (normally closed) devices to report trouble to the
FACP. Two (2) FACP signaling outputs can be employed and directed to control supervision and power delivery
to any combination of the four (4) outputs.
Specifications:
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to all local codes.
Input:
• Power input 220VAC (working range 198VAC-
256VAC), 50/60 Hz, 1.5A.
• Two (2) Class A, Style Z or two (2) Class B,
Style W, Y FACP inputs.
• Two (2) NC dry contact trigger inputs.
Output:
• 24VDC @ 8A max total alarm current.
• 2.5A max current per output.
• Separate 1.0A auxiliary output.
• Programmable supervised indicating circuit outputs:
Four (4) Class B, Style W, Y or Two (2) Class A,
Style Z or One (1) Class A, Style Z and Two (2)
Class B, Style W, Y (see Application Guide).
• Thermal and short circuit protection with auto reset.
Battery Backup:
• Built-in charger for sealed lead acid or
gel type batteries.
• Automatic switchover to stand-by battery when
AC Fails.
• Zero voltage drop when switching over to
battery backup.
Supervision:
• AC fail supervision (form “C” contact, 1A/28VDC).
Factory set for 30 seconds with optional 2.5 to 3
hour delay setting (field selectable).
• Instant local AC trouble reporting relay
(form “C” contact, 1A / 28VDC).
• Battery presence and low battery supervision
(form “C” contact, 1A / 28VDC).
Visual Indicators:
• Input and output status LED indicators.
Special Features:
• 2-wire horn/strobe Sync mode allows audible
notification appliances (horns) to be silenced
while visual notification appliances (strobes)
continue to operate.
• Sync protocols include Potter/Amseco, Faraday,
Gentex®,System Sensor®, and CooperWheelock®.
• Temporal Code 3, Steady Mode, Input to Output
Follower Mode (maintains synchronization of
notification appliances circuit).
• Compatible with 12VDC or 24VDC fire panels.
• Output loop supervision steered to Input 1 or Input 2.
• Signal circuit trouble memory (helps identify
intermittent loop problems).
• Common trouble input and output.
• Ground fault detection.
Added Features:
• Unit includes power supply, red enclosure, cam
lock, and battery leads.
Enclosure Dimensions (approx. H x W x D):
18” x 14.5” x 4.5”
(457.2mm x 368.3mm x 114.3mm).