Altronix R2416UL Series User manual

More than just power.TM
R2416UL
- 24VAC @ 7A (170VA) or
28VAC @ 6A (170VA).
- Sixteen (16) Fuse Protected Outputs.
R2416300UL
- 24VAC @ 14A (300VA) or
28VAC @ 12.5A (300VA).
- Sixteen (16) Fuse Protected Outputs.
R2416600UL
- 24VAC @ 28A (600VA) or
28VAC @ 25A (600VA).
- Sixteen (16) Fuse Protected Outputs.
R2416ULCB
- 24VAC @ 7A (170VA) or
28VAC @ 6A (170VA).
- Sixteen (16) PTC Protected Outputs.
R2416300ULCB
- 24VAC @ 14A (300VA) or
28VAC @ 12.5A (300VA).
- Sixteen (16) PTC Protected Outputs.
R2416600ULCB
- 24VAC @ 28A (600VA) or
28VAC @ 25A (600VA).
- Sixteen (16) PTC Protected Outputs.
R2416UL Series
UL Listed Rack Mount
CCTV Power Supplies
Installation Guide
Models Include:
Rev. 040506
- 2 - R2416UL Series
Overview:
Altronix R2416UL Series Rack Mount CCTV Power Supplies provide 24VAC or 28VAC distributed via sixteen
(16) fuse or PTC protected outputs for powering CCTV cameras, heaters and other video accessories.
Sixteen (16) Output Rack Mount Configuration Reference Chart:
Altronix
Model Number
Output Voltage
(VAC)
Total Output
Current (Power)
Number of Outputs
PTC Protected auto-
resettable Outputs
(Class 2 power-limited
for Dry locations,
Class 3 for Wet locations)
Fuse Protected Class 1
Outputs
Individual Output
Current (max per
output - not to exceed
total output current)
Fuse Ratings
Primary In-line
Fuse Ratings
115VAC 50/60Hz
Input Current
Agency
Listings
R2416UL 24VAC 3.5A 8 – P3.5A 3.5A 3.5A/
250V 2.9A
28VAC 3A
R2416ULCB 24VAC 3.5A 8P– 2.5A – 3.5A/
250V 2.9A
28VAC 3A
R2416300UL 24VAC 12.5A 16 – P3.5A 3.5A – 3A
28VAC 10A
R2416300ULCB 24VAC 12.5A 16 P– 2.5A – – 3A
28VAC 10A
R2416600UL* 24VAC 25A 16 – P3.5A 3.5A – 6A
28VAC 20A
R2416600ULCB 24VAC 25A 16 P– 2.5A – – 6A
28VAC 20A
*24VAC models: Outputs 1-8 provide 12.5A (300VA) max. Outputs 9-16 provide 12.5A (300VA) max.
*28VAC models: Outputs 1-8 provide 10A (280VA) max. Outputs 9-16 provide 10A (280VA) max.
Specifications:
Installation Instructions:
1. Mount unit in the desired rack location (space unit at least 3” from any video monitors).
Do not obstruct side air vents.
2. Set power disconnect circuit breaker to OFF position (Fig. 1d, pg. 3).
3. The unit is factory set for 24VAC operation.
For 28VAC operation, adjust unit prior to mounting and applying power as follows:
a. Open bottom of the unit by removing six (6) screws (Rack Mechanical Drawing and Dimensions, pg. 4).
b. Change the wire position so that the black wire [28V] is connected to the terminal marked [P] and
the yellow wire [24V] is connected to the terminal marked [S].
c. After securing all wires for proper voltage place bottom panel back on the unit and fasten with the
six (6) screws.
Note: R2416ULCB set for 28VAC operation is not Class 2 Rated, not power-limited.
4. Plug power cord into a grounded 115VAC 50/60 Hz receptacle (Fig. 1c, pg. 3), ground should be connected
as indicated in (Fig. 1e, pg. 3).
5. Set power disconnect circuit breaker to RESET (ON) position (Fig. 1d, pg. 3).
6. Measure output voltage before connecting devices. This helps avoiding potential damage.
All terminals with common suffix (P) “1P, 2P...” are the same polarity.
Agency Listings:
• UL Listed for Commercial
CCTV Equipment (UL 2044).
CUL Listed - CSA Standard C22.2 No. 1-98,
Audio, Video and Similar Equipment.
• CE European Conformity.
Output:
• 24VAC or 28VAC outputs (Factory set @ 24VAC).
• Surge suppression.
• Filtered and electronically regulated output.
• Short circuit and thermal overload protection.
Visual Indicators:
• Sixteen (16) individual power LED indicators.
Visual Indicators (cont’d):
• Illuminated power disconnect circuit breaker
with manual reset.
Features:
• Unit maintains camera synchronization.
• Ease of installation saves time and eliminates
costly labor.
• Removable terminal blocks with locking
screw flanges.
Rack Dimensions (H x W x D):
• 2U rack mount chassis for use in standard
EIA 19” rack.
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm)
R2416UL Series - 3 -
7. Set power disconnect circuit breaker to OFF position (Fig. 1d, pg. 3).
8. Connect devices to the removable terminal blocks marked [1P & 1N] through [16P & 16N] (Fig. 1a, pg. 3).
When wiring is completed on the terminal blocks they can be locked down by tightening screw flanges.
9. Upon completion of the wiring, set power disconnect circuit breaker to RESET (ON) position (Fig. 1d, pg. 3).
10. Green power LEDs on faceplate will illuminate when power is present. When an output is in a trouble
condition (blown fuse or tripped PTC) the corresponding LED will not be illuminated (Fig. 1, pg. 3).
a. Blown fuse (R2416UL, R2416300UL, and R2416600UL) - Set power disconnect circuit breaker on the
back of the unit to the OFF position (Fig. 1e, pg. 3).
Remove front faceplate to access fuses. Replace with fuses rated @ 3.5A/250VA
(Altronix model # Fuse1).
b. Tripped PTC (R2416ULCB, R2416300ULCB, and R2416600ULCB) - To reset PTC, set power switch
on the back of the unit to the OFF position. After approximately 30 secs. set power disconnect circuit
breaker to the ON (RESET) position (Fig. 1d, pg. 3).
11. Illuminated power disconnect circuit breaker with manual reset:
OFF position - Switch not illuminated. Outputs not powered.
RESET (ON) position - Circuit breaker illuminated. Outputs powered.
Circuit breaker tripped - Circuit breaker is not illuminated. Power LEDs on faceplate are not illuminated.
Outputs not powered.
To reset circuit breaker set power disconnect circuit breaker to RESET (ON) position (Fig. 1d, pg. 3).
Note: Do not exceed units electrical load ratings as indicated in reference chart (pg. 2).
Do not place mechanical load on unit. Data racks should always be properly ventilated.
Unit is designed optimally for normal data room office installations.
CAUTION: Equipment to be installed / serviced by authorized / trained personnel only.
Shut branch circuit power before installing / servicing equipment.
WARNING: To reduce the risk of fire or electric shock, do not expose the unit to rain or moisture.
This installation should be made by qualified service personnel and should conform to
the National Electrical Code and all local codes.
XFMR*XFMR*
NPS
Divider
PTC1
PN
S
S P N S P N
24VAC Output
(Factory Set) 28VAC Output
28VAC (Black)
24VAC (Yellow)
COM (Brown)
28VAC (Black)
24VAC (Yellow)
COM (Brown)
AC Power
LEDs
Used
on PTC
models AC Power
LEDs
AC Power
LEDs
AC Power
LEDs
Removable
Terminal
Block Strain Relief
Line Cord
Illuminated
Power Disconnect
Circuit Breaker
with manual reset
Fuse Fuse
Green Wire
Earth GND
Fig. 1 Fig. 1a Fig. 1b Fig. 1c
Fig. 1e
Fig. 1d
Class 2 Rated Power-Limited Outputs.
Except for R2416UL, R2416300UL, R2416600UL and R2416ULCB
when set for 28VAC.
- 4 - R2416UL Series
Altronix is not responsible for any typographical errors.
140 58th Street, Brooklyn, New York 11220 USA | phone: 718-567-8181 | fax: 718-567-9056
website: www.altronix.com | e-mail: [email protected] | Lifetime Warranty | Made in U.S.A.
IIR2416ULSeries D19R MEMBER
For fuse protected models:
Replace fuses with the same type and rating 3.5A/250V.
The lightning flash with arrowhead symbol within an equilateral triangle is intended to alert the user
to the presence of an insulated DANGEROUS VOLTAGE within the product’s enclosure that may
be of sufficient magnitude to constitute an electric shock.
The exclamation point within an equilateral triangle is intended to alert the user to the presence of
important operating and maintenance (servicing) instructions in the literature accompanying
the appliance.
CAUTION: To reduce the risk of electric shock do not open
enclosure. There are no user serviceable parts inside. Refer servicing
to qualified service personnel.
Rack Mechanical Drawing and Dimensions:
3.26” x 19.125” x 8.5” (83mm x 486mm x 216mm)
N P N PN PN P N PN PN PN P N P N PN PN P N P N PN PN P
OFF
RESET
16 15 14 13 12 11 10 98 7 654 3 21
Bottom View
Rear View
Front View
17.5” (444.5mm)
19.125” (486mm)
2.95”
(75mm)
3.26”
(83mm)
8.5”
(215.9mm)
1.0”
(25.4mm)
0.65” (16.5mm)
2.52”
(64mm)
1.5”
(38mm)
3.5A
250V

This manual suits for next models

6

Other Altronix Power Supply manuals

Altronix R615DC416 User manual

Altronix

Altronix R615DC416 User manual

Altronix SMP7CTX Series User manual

Altronix

Altronix SMP7CTX Series User manual

Altronix SMPWP Series User manual

Altronix

Altronix SMPWP Series User manual

Altronix eFlow104N Series User manual

Altronix

Altronix eFlow104N Series User manual

Altronix ALTV244-300/220 User manual

Altronix

Altronix ALTV244-300/220 User manual

Altronix WayPoint307A User manual

Altronix

Altronix WayPoint307A User manual

Altronix 220VAC Series User manual

Altronix

Altronix 220VAC Series User manual

Altronix VertiLine33D User manual

Altronix

Altronix VertiLine33D User manual

Altronix AL300ULM User manual

Altronix

Altronix AL300ULM User manual

Altronix TROVE T1KE34D User manual

Altronix

Altronix TROVE T1KE34D User manual

Altronix LPS5C24X User manual

Altronix

Altronix LPS5C24X User manual

Altronix eFlow3NB User manual

Altronix

Altronix eFlow3NB User manual

Altronix ALTV1224C220 User manual

Altronix

Altronix ALTV1224C220 User manual

Altronix Trove1V1 User manual

Altronix

Altronix Trove1V1 User manual

Altronix WPTV244UL Series User manual

Altronix

Altronix WPTV244UL Series User manual

Altronix ALTV2416 Series User manual

Altronix

Altronix ALTV2416 Series User manual

Altronix eFlow6N User manual

Altronix

Altronix eFlow6N User manual

Altronix ALTV2416300UL Operating and maintenance instructions

Altronix

Altronix ALTV2416300UL Operating and maintenance instructions

Altronix AL125ULPX User manual

Altronix

Altronix AL125ULPX User manual

Altronix ALTV244WP Series User manual

Altronix

Altronix ALTV244WP Series User manual

Altronix LPS3R User manual

Altronix

Altronix LPS3R User manual

Altronix AL842ADA220 User manual

Altronix

Altronix AL842ADA220 User manual

Altronix AL175ULX User manual

Altronix

Altronix AL175ULX User manual

Altronix AL300ULX User manual

Altronix

Altronix AL300ULX User manual

Popular Power Supply manuals by other brands

DuraComm EH-30 quick start guide

DuraComm

DuraComm EH-30 quick start guide

Antec TPII-380 user manual

Antec

Antec TPII-380 user manual

iTechworld SOLAR BLANKET KIT user guide

iTechworld

iTechworld SOLAR BLANKET KIT user guide

Schumacher SJ1289 user manual

Schumacher

Schumacher SJ1289 user manual

Amada UNIFLOW UF-R4000A Operation manual

Amada

Amada UNIFLOW UF-R4000A Operation manual

DTS Megashock 5 installation manual

DTS

DTS Megashock 5 installation manual

Scame ADVANCE-GRP Series Installation, use and maintenance

Scame

Scame ADVANCE-GRP Series Installation, use and maintenance

Akyga AK-ND-43 user manual

Akyga

Akyga AK-ND-43 user manual

Bogen PRSLSI Specifications

Bogen

Bogen PRSLSI Specifications

Elmdene G13804NU manual

Elmdene

Elmdene G13804NU manual

Phoenix Contact QUINT4-PS/1AC/48DC/5 datasheet

Phoenix Contact

Phoenix Contact QUINT4-PS/1AC/48DC/5 datasheet

Peak PKC0AS owner's manual

Peak

Peak PKC0AS owner's manual

Würth 0827 940 213 operating manual

Würth

Würth 0827 940 213 operating manual

RD DPS5015 user manual

RD

RD DPS5015 user manual

Elmdene 2401ST quick start guide

Elmdene

Elmdene 2401ST quick start guide

ICT PRT-PSU-DIN-2A installation manual

ICT

ICT PRT-PSU-DIN-2A installation manual

Intel ATX12VO Design guide

Intel

Intel ATX12VO Design guide

Kodak PPS1800 user manual

Kodak

Kodak PPS1800 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.