Amana BBA24A2A Technical document

Model and Manufacturing
numberslistedinthismanual.
MODEL M/N
BBA24A2A P1206401C
BBA36A2A P1206402C
BBA48A2A P1206403C
BBA60A2A P1206404C
BBA24A2A P1206415C
BBA36A2A P1206416C
BBA48A2A P1206417C
BBA60A2A P1206418C
TECHNICAL INFORMATION MANUAL
BBA* Blowers
•RefertoServiceManualRS6200003forinstallation,op-
eration, and troubleshooting information.
•All safety information must be followed as provided in
the Service Manual.
•Refer to the appropriate Parts Catalog for part number
information.
®is a trademark of Maytag Corporation and is used under license to Goodman
Company, L.P. All rights reserved. Copyright © 2004 Goodman Company, L.P.
RT6221002 Rev. 1
December 2004
This manual is to be used by qualified HVAC technicians only. Goodman
does not assume any responsibility for property damage or personal injury
due to improper service procedures performed by an unqualified person.

PRODUCT IDENTIFICATION
2 Rev. 1
The model and manufacturing number are used for positive identification of component parts used in manufacturing.
Please use these numbers when requesting service or parts information.
IF REPAIRS ARE ATTEMPTED BY UNQUALIFIED PERSONS, DANGEROUS
CONDITIONS (SUCH AS EXPOSURE TO ELECTRICAL SHOCK) MAY RE-
SULT. THIS MAY CAUSE SERIOUS INJURY OR DEATH.
GOODMAN WILL NOT ASSUME RESPONSIBILITY FOR ANY INJURY OR
PROPERTY DAMAGE ARISING FROM IMPROPER SERVICE OR SERVICE
PROCEDURES. IF YOU PERFORM SERVICE ON YOUR OWN PRODUCT, YOU ASSUME RESPONSIBIL-
ITY FOR ANY PERSONAL INJURY OR PROPERTY DAMAGE WHICH MAY RESULT.
WARNING
WARNING
CAUTION
Design Series
A: First Series
Product Type
B: Blower Unit
System Type
B:Multi-position
Blower Capacity
24: 2 Ton
36: 3 Ton
48: 4 Ton
60: 5 Ton
B B A 24 A 2 A
Efficiency
A: Standard
C: Variable Speed
Voltage
2: 230 V-1-60
Factory Heat
A: 0 KW

PRODUCT DESIGN
3 Rev. 1
BBA blower cabinets are designed as a two-piece blower coil. The BBA blower section can be attached to a CCA_FC_,
CHA_TC_,orCHF_TC_ cased evaporator coil. This two piece arrangement allows for a varietyofmix-matching possibili-
ties providing greater flexibility.
The BBA blower cabinets can be positioned for upflow, counterflow, horizontal right or horizontal left operation. All units
are constructed with R-4.2 insulation. In areas of extreme humidity (greater than 80% consistently), the installer should
insulate the exterior of the blower with insulation having a vapor barrier equivalent to ductwork insulation, providing local
codes permit.

4 Rev. 1
BBA BLOWER COIL SPECIFICATIONS
11 3/8
2
2 1/16
2
7/8 Knockout
3 Knockouts
1 - 3/32
1 - 23/64
1 - 23/32
21 1/8
19 5/8
"W"
"B"
"H"
"A"
4
Dimensions, inches (mm) Shipping Physical Information
MODEL W H A B Weight
lbs.(kg) Blower Wheel
(D x W) Blower Motor
(HP) MCA1MOP1
BBA24A2A 16 - 1/2 15 15
63
(28.6) 9 x 7 1/4 1.9 15
BBA36A2A (419) 22 - 1/4
(565)
(381) (381) 68
(30.8) 10 x 7 1/3 3 15
BBA48A2A 20 - 1/2
(521) 19
(483) 19
(483) 78
(35.4) 10 x 10 1/3 3.8 15
BBA60A2A 24 - 1/2
(622) 26 - 1/4
(667) 23
(584) 23
(584) 90
(40.8) 11 x 10 1/2 4.9 15
1Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat
installed. Refer to unit nameplate for MCA and MOP with approved accessory heaters installed.

5 Rev. 1
BBA BLOWER COIL SPECIFICATIONS
EHK/ECB ELECTRIC HEATER DATA
CAUTION
To avoid the risk of fire, overcurrent protection must not exceed the value listed above.
Minimum Circuit Ampacity
Heater EHK05B/C EHK07B/C EHK10B/C EHK15B/C EHK20B/C EHK25B/C EHK30B/C ECB15B/C + ECB20B/C + ECB25B/C + ECB30B/C +
Model ECB05B/C ECB07B/C ECB10B/C ECB15B/C ECB20B/C ECB25B/C ECB30B/C SPK02A SPK02A SPK03A SPK03A
L1/L2 27.8 41.3 53.8 53.8 53.8 79.8 105.7
BBA24A2A L3/L4 26 52
L1/L2 29 42.4 55 55 55 55 55 80.9 106.9 132.8 158.8
BBA36A2A L3/L4 26 55 55 52
L5/L6 26 55
L1/L2 29.7 43.2 55.7 55.7 55.7 55.7 55.7 81.6 107.6 133.6 159.5
BBA48A2A L3/L4 26 55 55 55
L5/L6 26 55
L1/L2 30.9 44.4 56.9 56.9 56.9 56.9 56.9 82.8 108.8 134.8 160.7
BBA60A2A L3/L4 26 55 55 52
L5/L6 26 55
Maximum Overcurrent Protection
Heater EHK05B/C EHK07B/C EHK10B/C EHK15B/C EHK20B/C EHK25B/C EHK30B/C ECB15B/C + ECB20B/C + ECB25B/C + ECB30B/C +
Model ECB05B/C ECB07B/C ECB10B/C ECB15B/C ECB20B/C ECB25B/C ECB30B/C SPK02A SPK02A SPK03A SPK03A
L1/L2 30 45 60 60 60 80 110
BBA24A2A L3/L4 30 60
L1/L2 30 45 60 60 60 60 60 90 110 150 175
BBA36A2A L3/L4 30 60 60 60
L5/L6 30 60
L1/L2 30 45 60 60 60 60 60 90 110 150 175
BBA48A2A L3/L4 30 60 60 60
L5/L6 30 60
L1/L2 35 45 60 60 60 60 60 90 110 150 175
BBA60A2A L3/L4 30 60 60 60
L5/L6 30 60
External
Static BBA24A2A
Airflow (CFM) BBA36A2A
Airflow (CFM) BBA48A2A
Airflow (CFM) BBA60A2A
Airflow (CFM)
(in. w.c.) Low Med High Low Med High Low Med High Low Med High
0.2 590 830 1100 1030 1280 1430 1090 1490 1720 1480 1680 2110
0.3 550 790 1070 1000 1250 1420 1060 1450 1670 1420 1630 2050
0.4 500 740 1040 960 1210 1370 1020 1400 1620 1350 1560 2020
0.5 680 970 920 1160 1320 970 1340 1550 1280 1490 1940
0.6 600 880 860 1100 1240 910 1280 1470 1210 1420 1870
0.7 790 800 1030 1150 750 1170 1380 1100 1340 1770
0.8 660 690 940 1070 650 1060 1220 1000 1240 1660
0.9 850 970 850 970 850 1110 1550
230 V,no heaters,no filter,no coil
BBA BLOWER PERFORMANCE DATA

6 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
20047601 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
LOW VOLTAGE
HIGH VOLTAGE
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR MIB-MTR INDOOR BLOWER
CAP
MIB
R
C
Y
E
O
G
W2
CR
LED
L1
L2
UNUSED
FAN
IDLE
FAN
FAN
COM
UNUSED UNUSED
TH
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
HI
MED
LOW
FIELD
CONNECTION
208/240
VAC 1ø
L1
L2
GND 3
WARNING: DISCONNECT POWER BEFORE SERVICING.
WN
WN
1
2
1
2
3UNIT MUST BE PROPERLY GROUNDED.
USE COPPER CONDUCTORS ONLY,
SUITABLE FOR MINIMUM 75°C.
PUT DESIRED SPEED TAP ON
TERMINAL MARKED "FAN". IF
DESIRED, PUT OFF CYCLE SPEED
TAP ON TERMINAL MARKED "FAN
IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
RD6
BK9
YL7 YL7
VT BR
VT14
BU
YL
OR
RD
BK
MIB
CAP
L2 L1
FAN
IDLE
FAN
FAN
COM
L2 L1
TRANSFORMER
COM
208
240
R
C
Y
E
O
G
W2
L
O
G
I
C
THERMISTOR
101112
987
654
321
12 PIN
CONNECTOR
CONTROL
BOARD
THERM
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
4
3A FUSE MAX
4
BK27
BU24
RD26
FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS
WHEN ELECTRIC HEAT IS FIELD ADDED, USE WIRE
NUTS PROVIDED WITH HEATER KIT, AND
LOCATE THE REPLACEMENT WIRING DIAGRAM UPON
THIS DIAGRAM.
96
5
USED WITH 11047201 CONTROL BOARD
5
BBA(24-60)A2A

7 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ DSK02A
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 30A
11139001 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 1Ø VAC
RD-L1
BK-L2
CIRCUIT BREAKERS
BBA MODELS ONLY
BU
GY
R1
FL1
HT1
69
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1 R1
2
3
4
5
7
10
11
G
N
D
L2 L1
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
RD-L1
BK-L2
OR

8 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
COLOR CODE
1ST GROUP COLOR
2ND GROUP NUMBER
OR-ORANGE BK-BLACK
YL-YELLOW BU-BLUE
VT-VIOLET RD-RED
BR-BROWN TN-TAN
GN-GREEN GY-GRAY
* Approved Thermostats are: D9945804
10636702
10636701
D9807605
With Outdoor Thermostat - ATK Controlling ALL Electric Heat
Morning Warmup Could be Slow -
4.8 to 28.8KW
ROOM THERMOSTAT
(6 wires)
BBA or BBC BLOWER COIL
(6 wires)
RH OUTDOOR UNIT
ATK ControllingALL Electric Heat Except In The
Defrost Mode
ROOM THERMOSTAT
(6 wires)
BBAor BBC BLOWER COIL
(6 wires)
RH OUTDOOR UNIT
RYEW 1W
2CX/
ATK05
O
G
RG
RYEW2O
YW2
EO
C
C
RYEW 1W
2CX/
ATK 05
O
G
RG
RYE
W2O
YW2
EO
C
C
RH-HEAT PUMP WITH INDOOR BLOWER COIL
WITH APPROVED THERMOSTATS*

9 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ EHK05B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
R1
11146301 REV. 0FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY
HT-HEATER
FL-FUSABLE LINK
1
2
3UNIT MUST BE PROPERLY GROUNDED.
USE COPPER CONDUCTORS ONLY.
SUITABLE FOR MINIMUM 75°C
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LEDON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27
(HI)
FL1
HT1
412 PIN
CONNECTOR
LED
W2
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FL1 HT1 R1
11
10
7
5
4
3
2
1
WARNING: DISCONNECT POWER
BEFORE SERVICING.
RD-L1
BK-L2 RD
L1
BK
L2
VT WH
BBA MODELS ONLY
69
5
5 FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
R1
L2
L1
GND
FIELD CONNECT
208/240 10 VAC
WN WN
3
2
OR

10 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ EHK07/10B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
L2
L1
GND
11146401 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY
HT-HEATER
FL-FUSABLE LINK
1
2
3UNIT MUST BE PROPERLY GROUNDED.
USE COPPER CONDUCTORS ONLY.
SUITABLE FOR MINIMUM 75°C
PUT DESIRED SPEEDTAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27
(HI)
412 PIN
CONNECTOR
LED
W2
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
1
WARNING: DISCONNECT POWER
BEFORE SERVICING.
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2 RD-L1 RD
L1
BK-L2
BK
L2
VT YL
WH
BBA MODELS ONLY
WN WN
R2
FL2
HT2
R1
FL1
HT1
69
3
2
FL2 HT2 R2
FL1 HT1 R1 5
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
R2
R1
OR
OR
2
3
4
5
7
10
11

11 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ EHK15B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
11146501 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSEDSPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2
BBA MODELS ONLY
VT
PK
YL
WH
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
69
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R3
R2
2
3
4
5
7
10
11
G
N
D
L2 L1
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
WN WN
G
N
D
L4 L3
3
2
WN WN
RD-L1 RD
L1
BK-L2
BK
L2
RD
L3
BK
L4
OROROR

12 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ EHK20B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
11146601 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2
BBA MODELS ONLY
VT
OR
YL
PK
WH
GY
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
R4
FL4
HT4
69
FL4 HT4 R4
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R4
R2
2
3
4
5
7
10
11 R3
G
N
D
L2 L1
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
WN WN
G
N
D
L4 L3
3
2
WN WN
RD-L1 RD
L1
BK-L2
BK
L2
BK-L4
RD-L3
RD
L3
BK
L4
OROROROR

13 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ EHK25B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
11146701 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSEDSPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2
BBA MODELS ONLY
VT
OR
YL
BR
PK
WH
GY
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
R4
FL4
HT4
R5
FL5
HT5
69
FL5 HT5 R5
FL4 HT4 R4
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R4
R5
2
3
4
5
7
10
11 R3
R2
G
N
D
L2 L1
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
WN WN
G
N
D
L4 L3
3
2
WN WN
G
N
D
L6 L5
3
2
WN WN
RD-L1 RD
L1
BK-L2
BK
L2
BK-L4
RD-L3
RD
L3
BK
L4 RD-L5
BK-L6
OROROROROR

14 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ EHK30B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
11146801 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEEDTAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
4
12 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2
BBA MODELS ONLY
BU
OR
YL
VT
BR
PK
WH
GY
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
R4
FL4
HT4
R5
FL5
HT5
R6
FL6
HT6
69
FL6 HT6 R6
FL5 HT5 R5
FL4 HT4 R4
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1 R6
R4
R5
2
3
4
5
7
10
11 R3
R2
R1
G
N
D
L2 L1
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
WN WN
G
N
D
L4 L3
3
2
WN WN
G
N
D
L6 L5
3
2
WN WN
RD-L1
RD
L1
BK-L2
BK
L2
BK-L4
RD-L3
RD
L3
BK
L4 RD-L5
BK-L6 RD-L5 BK-L6
OROROROROROR

15 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ ECB05B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
6
54
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 30A
11146901 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSEDSPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2
CIRCUIT BREAKERS
BBA MODELS ONLY
VT
WH
R1
FL1
HT1
69
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
2
3
4
5
7
10
11
G
N
D
L2 L1
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
RD-L1
BK-L2
OR

16 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ ECB07/10B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 30A
11147001 REV. 0
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSEDSPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FAN
COM
CAP MIB FAN
IDLE
FAN
L2 L1
FIELD CONNECT
208/240 10 VAC
RD-L1
BK-L2
CIRCUIT BREAKERS
BBA MODELS ONLY
VT
YL
WH
R1
FL1
HT1
R2
FL2
69
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R2
2
3
4
5
7
10
11
G
N
D
L2 L1 G
N
D
3
22
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
RD-L1 RD
L1
BK-L2
BK
L2
OROR
HT2

17 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ ECB15B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 60A 30A
11147101 REV. 1
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSEDSPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FIELD CONNECT
208/240 1Ø VAC
RD-L1
BK-L2
CIRCUIT BREAKERS
BBA MODELS ONLY
VT
PK
YL
WH
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
69
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R3
R2
2
3
4
5
7
10
11
G
N
D
L2 L1 L4 L3G
N
D
3
2
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
60A 30A
FIELD CONNECT 208/240 1Ø VAC
W/ SPK02A INSTALLED
L2 L1 GND
3
2
L2 L1 L4 L3
RD-L1 RD
L1
BK-L2
BK
L2 RD
L3
BK
L4
OROROR
L4
L2
L3
L1
FAN
COM
CAP MIB FAN
IDLE
FAN

18 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ ECB20B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 60A 60A
11147201 REV. 1
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSEDSPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FIELD CONNECT
208/240 1Ø VAC
RD-L1
BK-L2 RD-L1 RD
L1
BK-L2
BK
L2
BK-L4
RD-L3
RD
L3
BK
L4
CIRCUIT BREAKERS
BBA MODELS ONLY
VT
OR
YL
PK
WH
GY
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
R4
FL4
HT4
69
FL4 HT4 R4
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R4
R2
2
3
4
5
7
10
11 R3
G
N
D
L2 L1 L4 L3G
N
D
3
2
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
60A 60A
FIELD CONNECT 208/240 1Ø VAC
W/ SPK02A INSTALLED
L2 L1 GND
3
2
L2 L1 L4 L3
OROROROR
L1
L4
L2
L3
L1
FAN
COM
CAP MIB FAN
IDLE
FAN

19 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ ECB25B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 60A 60A 30A
11147301 REV. 2
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BE PROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FIELD CONNECT
208/240 1Ø VAC
RD-L1
BK-L2
CIRCUIT BREAKERS
BBA MODELS ONLY
VT
OR
YL
BR
PK
WH
GY
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
R4
FL4
HT4
R5
FL5
HT5
69
FL5 HT5 R5
FL4 HT4 R4
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1
R1
R4
R5
2
3
4
5
7
10
11 R3
R2
G
N
D
L2 L1 L4 L3 L6 L5G
N
D
G
N
D
3
2
3
2
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
60A 60A 30A
FIELD CONNECT 208/240 1Ø VAC
W/ SPK03A INSTALLED
L2 L1 GND
3
2
L2 L1 L4 L3 L6 L5
RD-L1
RD
L1
BK-L2
BK
L2
BK-L4
RD-L3
RD
L3
BK
L4 RD-L5
BK-L6
OROROROROR
L6
L4
L2
L5
L3
L1
FAN
COM
CAP MIB FAN
IDLE
FAN

20 Rev. 1
WIRING DIAGRAMS
TO AVOID PERSONAL INJURY OR DEATH DUE TO ELECTRICAL
SHOCK, DISCONNECT THE POWER BEFORE SERVICING.
WARNING
!
Wiring is subject to change, always refer to the wiring diagram on the unit for the most up-to-date wiring.
BBA w/ ECB30B/C
OR
RD
BK
COM
208
240
T
R
A
N
S
F
O
R
M
E
R
BU YL
YL7
YL7
VT14
VT
TH
CAP
MIB
BR
UNUSED
L1
L2
121110
987
654
321
R
C
Y
E
O
G
RC
THERM
UNUSED
UNUSED FAN
IDLE
FAN
FAN
COM
1
CIRCUIT
BREAKERS 60A 60A 60A
11147401 REV. 2
FACTORY SUPPLIED WIRING
FIELD SUPPLIED WIRING
LOW VOLTAGE
HIGH VOLTAGE
COLOR
CODE: 1ST GROUP-COLOR
2ND GROUP-NUMBER
BLACK-BK
BLUE-BU
RED-RD
TAN-TN
GRAY-GY
WHITE-WH
ORANGE-OR
GREEN-GN
YELLOW-YL
VIOLET-VT
BROWN-BR
PINK-PK
WN-WIRE NUT TH-THERMISTOR
CAP-CAPACITOR
MIB-MOTOR INDOOR BLOWER
R-RELAY HT-HEATER
FL-FUSABLE LINK
1
3UNIT MUST BEPROPERLY GROUNDED.
PUT DESIRED SPEED TAP ON TERMINAL
MARKED "FAN". IF DESIRED, PUT OFF
CYCLE SPEED TAP ON TERMINAL MARKED
"FAN IDLE". PUT UNUSED SPEED TAPS
ON TERMINALS MARKED "UNUSED".
CONTROL BOARD MALFUNCTION CONTINUOUS NONE
6 FLASHES
SYSTEM ERROR 3 SECONDS
THERMISTOR ERROR
THERMISTOR AND/OR BOARD ERROR
NORMAL OPERATION
MODE
4 FLASHES
2 FLASHES
1/2 SECOND ON
LED ON TIME
LED FLASH CODE
3 SECONDS
3 SECONDS
1/2 SECOND OFF
LED OFF TIME
3A FUSE MAX
4
LOW VOLTAGE
HIGH VOLTAGE
RD26 (LOW)
BU24 (MED)
BK27 (HI)
412 PIN
CONNECTOR
LED
W2
TRANSFORMER
208
L1 240
L2
COM
FIELD CONNECT
208/240 1Ø VAC
RD-L1
BK-L2
RD-L1
RD
L1
BK-L2
BK
L2
BK-L4
RD-L3
RD
L3
BK
L4 RD-L5
BK-L6 RD-L5 BK-L6
CIRCUIT BREAKERS
BBA MODELS ONLY
BU
OR
YL
VT
BR
PK
WH
GY
R1
FL1
HT1
R2
FL2
HT2
R3
FL3
HT3
R4
FL4
HT4
R5
FL5
HT5
R6
FL6
HT6
69
FL6 HT6 R6
FL5 HT5 R5
FL4 HT4 R4
FL3 HT3 R3
FL2 HT2 R2
FL1 HT1 R1
5
WARNING: DISCONNECT POWER BEFORE
SERVICING.
5FIELD LOW VOLTAGE CONNECTIONS
PER INSTALLATION INSTRUCTIONS.
Y
E
W2
O
G
C
R
L
O
G
I
C
THERMISTOR
1 R6
R4
R5
2
3
4
5
7
10
11 R3
R2
R1
G
N
D
L2 L1 L4 L3 L6 L5G
N
D
G
N
D
3
2
3
2
3
2
2USE COPPER CONDUCTORS ONLY,
SUITABLE FOR 75°C MINIMUM.
60A 60A 60A
FIELD CONNECT 208/240 1Ø VAC
W/ SPK03A INSTALLED
L2 L1 GND
3
2
L2 L1 L4 L3 L6 L5
OROROROROROR
L6
L4
L2
L5
L3
L1
FAN
COM
CAP MIB FAN
IDLE
FAN
This manual suits for next models
11
Table of contents
Other Amana Control Unit manuals
Popular Control Unit manuals by other brands

Mircom
Mircom BBX-2000 Mechanical installation

Automationdirect.com
Automationdirect.com Productivity 2000 P2-15TD1 manual

Telit Wireless Solutions
Telit Wireless Solutions LN960 HW User Guide

Huawei
Huawei UPS5000-E-200K-SM user manual

Siemens
Siemens LMV36.520A1 Basic documentation

Anderson
Anderson Greenwood Series Installation and maintenance instructions