Anywire BL296 B-08F-4A-20 Series User manual

-BL296*B08F*4A20 1/16-
BL296□B-08F□-4A-20
Ver.1.1
BL296SB-08FS-4A-20
BL296PB-08FS-4A-20
BL296XB-08FS-4A-20
BL296SB-08F-4A-20
BL296PB-08F-4A-20
BL296XB-08F-4A-20 e-CON
(4 poles)
e-CON
(4 poles)
NPN input
NPN output
NPN input/NPN output
PNP input
PNP output
PNP input/PNP output
[Type]
A WARNING indicates a potentially hazardous
situation which, if not handled correctly, could
result in death or serious injury.
[Warranty]
■Warranty period
The warranty on the delivered Product shall continue to be effective for one (1)
year after the delivery thereof to a location as designated by the original owner.
■Scope of warranty
Should a defect occur in any part of the Product during the foregoing warranty
period when it is used normally in accordance with the specications described
in this Products Guide, the Company shall replace or repair the defect free of
charge, except when it arises as a result of:
[1] Misuse or abuse of the Product by the owner;
[2] Fault caused by other than the delivered Product;
[3] The unauthorized modication or repair of the Product by any person other
than the Company’s personnel;
[4] Any unusual force of nature, disaster or other cause beyond the Company’s
control.
The term “warranty,” as used herein, refers to the warranty applicable to the
delivered product alone. The Company shall not be liable for consequential or
incidental damages resulting from any malfunction.
■Repair at cost
After the expiration of the warranty period, the owner shall be responsible for all
costs and expenses incurred for the troubleshooting and repair of the Product.
Even during the warranty term, the Company shall repair any defects arising
from causes other than within the scope of the warranty as specied above, at
the owner’s cost.
■Changes in the product specications and the descriptions in the manual
The descriptions in this manual may be subject to change without notice.
Precautions that must be observed in order to use this system safely are indicated as shown below.
You must observe these precautions.
[Notes on Safety]
A CAUTION indicates a potentially hazardous situation
which, if not handled correctly, may result in personal
injury or property damage.
AnyWireASLINK System Products Guide
■Note on use ⇒
A separate Address Writer is required to set addresses and other data.
*
For more information, refer to [Various Settings] on page 9.
CAUTION
WARNING
○
System power supply
Use a stable, 24V DC power supply. Use of an unstable power supply may cause problems with the system.
○
Separately route high-voltage and power cables
Although the AnyWireASLINK has a high noise margin, install the transmission line and I/O cables away from high-voltage and power
cables.
○
Connectors and terminals
-
Pay careful attention to the length and installation of cable wiring to ensure that connectors and cables are neither overloaded nor disconnected.
- Make sure to prevent any metal objects from getting inside the connectors or the terminal blocks.
- Short-circuits caused by metal objects or mis-wiring are likely to damage the device.
○
Do not impose any external loads on the units. Doing so may cause a failure.
○
Do not disconnect or reconnect between the transmission line and slave units when the transmission line is active. A malfunction may occur.
○
Use the AnyWireASLINK within the range of the specications and conditions shown below.
○
System Safety
This system is intended for general industrial applications. It does not have functions for supporting applications requiring higher
levels of safety such as safety-related devices or accident prevention systems. The product must not be used for these purposes.
○
Always turn off the power in installing or replacing the system.
○
Prolonged continuous ow of a rated load current or higher or a transit current due to load short-circuit, etc., in the hybrid unit including
the output unit and the output circuit may result in smoking or ring. An external safety device such as a fuse must be installed.
CAUTION
WARNING
[About Pictogram*1]
Ver. 1.0*2Compatible with
Ver. 1.1*3
*1 The pictogram may not be marked (or stuck) depending on the product.
*2 AnyWireASLINK device not compatible with Ver. 1.1 (word transmission and
single unit simplified replacement functions)
Some products, not marked with the Ver. 1.1 pictogram, are compatible with
the functions included in Ver. 1.1. Refer to the lot No. and the product guide
for ultimate confirmation.
*3 For details of Ver. 1.1, refer to the subsequent pages.
ASLINKTERMINAL [ASLINK Integrated Terminal]

-BL296*B08F*4A20 2/16-
A
1
B
2
C
3
D
4
E
5
F
6
G
7
H
8
I
9
J
10
K
11
L
12
Lot No. 19ECBNB
As a result of the addition of functions, indication of lot No. has been changed from 3 digits (conventional format:
year and month only) to 6 digits or 7 digits.
The master unit compatible with the word transmission function provides areas for transmission and receiving of word
data (numerical information) such as analog data and sensing level data.
Using this function enables reduction of occupancy of bit information area by word data.
To enable word transmission, it is necessary that the system should be congured only with slave units compatible with
the word transmission function.
A slave unit incompatible with the word transmission function cannot be connected to the AnyWireASLINK system to
conduct word transmission.
For slave units that handle word data, word address settings are required.
[About AnyWireASLINK Ver. 1.1]
[About Lot No.]
[About Word Transmission]
*3 Some products have no indication of function version.
Year: Numbers
(Lower two digits of the Christian era)
Month: Alphabet (as per the table below)
“19E” means May 2019.
Single unit simplied replacement*1
Word transmission*1*2
Functions available with Ver. 1.1
*1 To use these functions, the master unit compatible with each function is required.
For details, refer to this manual together with the manual for the master unit.
*2 You can use this function with the word-transmission AnyWireASLINK unit connected.
To handle word data, word address settings are required for slave units.
It depends on slave units whether word address setting is enabled or not.
New functions have been added to AnyWireASLINK products in May 2019 onward. Also, for the purpose of
differentiation of compatible functions, indication of product lot number (lot No.) has been changed.
Compatible functions vary depending on lot No. Please understand the following description thoroughly to use each
product.
Functions added to Ver. 1.1 are as follows:
Example:
S/W version
Year and month H/W version
Alphabet
Month
Function version*3

-BL296*B08F*4A20 3/16-
NEW
ASLINK
master unit
ASLINK
master unit
Function version:
When an equipment parameter is changed due to functional upgrading, etc., the function
version will be updated (for example: A→B→C).
When a slave unit of a new function version is replaced with that of an old function version,
the single unit simplied replacement function cannot be used.
[About Single Unit Simplified Replacement]
During replacement of a slave unit, this function enables automatic settings of address and parameters of the existing
slave unit into a new slave unit. (After replacement of the slave unit, address and parameter setting procedure using the
address writer is not required.)
■Step 1 Turn OFF the 24V DC power supply for the master unit.
■Step 2 Disconnect a slave unit to be replaced.
■Step 3 Connect a new slave unit.
■Step 4 Turn ON the 24V DC power supply to the master unit.
- It is necessary that both the master unit and slave unit should be compatible with the single unit simplied replacement function.
- Before disconnection and connection of the slave unit, be sure to turn OFF the power supply.
- For compatibility of a slave unit with the single unit simplied replacement function, see the lot No. and the manual for the slave unit.
- When a slave unit of a new function version is replaced with that of an old function version, the single unit simplied replacement
function cannot be used.
- Operation is enabled in the case where the model of the slave unit before replacement is the same as that after replacement.
- If the model of the slave unit before replacement is different from that after replacement, a model mismatching error occurs, disabling
address and parameter settings.
- Operation is enabled in the case where the address of the slave unit for replacement is the factory-set address (bit address 511).
- Several slave units cannot be simultaneously replaced. For replacement of several slave units, conduct the replacement procedure for
each unit one by one.
- For a slave unit incompatible with the single unit simplied replacement function, set an address and parameters by using the address
writer as in the conventional manner.
- For details of the single unit simplied replacement function (limitations, conditions, etc.), refer to the manual for the master unit.
■Identication of function version
Function version information is given on the lot label.
*
The design and contents of the lot label may vary depending on the product model and lot No.
CAUTION

-BL296*B08F*4A20 4/16-
○○ × ××
×○×
○
○○
○
Lot No. 19ECBNB
*3 This terminal can be used in connection to the AnyWireASLINK unit for word transmission. Note that this terminal cannot handle word data by setting a word address.
Word transmission*3
Single unit simplied replacement
Remote address change
Function Lot No.
Connection targetsSpecicationsModel Functions
Functions
Address
*1 This terminal can be used in connection to the AnyWireASLINK unit for word transmission. Note that this terminal cannot handle word data by setting a word address.
*2 To use these functions, a master unit that supports each function is required. For details, refer to the manual for the master unit together with this manual.
[Functions]
Bit
transmission
ASLINKTERMINAL
4-wire (isolated) type
integrated compact
terminal
e-CON (4 poles)
General-purpose
sensors, switches
General-purpose
output devices
NPN input: 8 points,
NPN output: 8 points
NPN input: 4 points/output: 4 points
PNP input: 8 points,
PNP output: 8 points
PNP input: 4 points/output: 4 points
Detection of
sensor cable
disconnection
Bit
address
setting
Slave unit voltage
drop Sensing level drop I/O short-circuit
Word
address
setting
■Function list
■Detecting functions (Status details)
Available with S/W version “A” or later version
This unit has undergone addition of functions and change of specications according to version upgrading.
Available functions and specications of the unit vary depending on lot No.
[Function Compatibility by Lot No.]
Bottom of this unit
Lot No. is indicated on the lot label. Example:
■How to check
S/W version
Function version
H/W version
Single unit
simplied
replacement
Remote
address
change
*1*2*2
Word
transmission
I/O disconnection I/O power supply
drop

-BL296*B08F*4A20 5/16-
The branching
has no limitation.
AnyWireASLINK
master
Black:
DN
Red: DP
Black: DN
Red: DP
Black: DN
Black: DN
Red: DP
Red: DP
Black: DN Red: DP
2 points
2 points
2 points
2 points
2 points
2 points
2 points
2 points
2 points
16 points
16 points
24V DC*
Black: DN
Red: DP
General-purpose
power supply lter
ASLINK lter
Black: DN
Red: DP
General-purpose
power supply lter
24V DC*
*Make sure to use a 24V DC
stabilized power supply for
the power supply to be
connected.
*When complying with the
UL Standard, make sure to
use a 24V DC stabilized
power supply of “NEC
Class 2 Output.”
4P link connector is
convenient for
branching.
Dedicated at cable
1.25mm2(4-wire)
The sum of the
portions of DP, DN is
the total line length.
1.25mm2
0.75mm2
MAX 2A
MAX 1.2A
MAX 1A
MAX 0.6A
MAX 0.5A
MAX 0.3A
0.5mm2MAX 0.8A MAX 0.4A MAX 0.2A
If the load current consumption
is large, a four-wire (isolated)
terminal can be selected.
This terminal can correspond
to I/O of the controller with an
external power supply.
■
Relationship between the size and length of
the transmission line and the supply current (Table 1)
Size of
the transmission
line (DP, DN)
Supply current on the transmission line (DP, DN)
Total length:
50m or less
Total length: Over 50m,
no longer than 100m
Total length: Over 100m,
no longer than 200m
CAUTION
- Refer to Table 1 so that the size and length of the transmission
line and the allowable supply current lie within an appropriate
range.
- Connect the same symbols (DP, DN) correctly between the
AnyWireASLINK master unit and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in the
“total line length.”
-
Connect the terminator (with polarity) to the DP, DN terminal
farthest from the AnyWireASLINK master unit.
[System Configuration Example]
[Installation Location]
- Locations where this product is not directly subject to vibration or shock
- Locations where this product is not directly exposed to dust
- Locations where this product is not directly exposed to conductors, such as metal chips or spatters
- Locations without condensation
- Locations where the atmosphere is free of corrosive gases, ammable gases, and sulfur
- Locations far from high-voltage or high-current cables
- Locations far from servos, inverters, and other cables and controllers that generate high-frequency noise
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending on the load current.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving simplied wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of connections, hybridization with a four-wire (isolated)
terminal, which supports local power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an external power supply.
[How to Connect AnyWireASLINK]
AnyWireASLINK terminator
One terminator should be connected to the DP, DN terminal farthest
from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.

-BL296*B08F*4A20 6/16-
DP
DN
24V
0V
POWER IN SLAVE
LG
24V
0V L
N
FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
ANF-01
24V
0V L
N
FG
~
24V
0V
24V
0V
PE
ANF-01
ANF-01
DP
DN
24V
0V
LG
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
DP
DN
DP
DN
24V
0V
DP
DN
24V
0V
24V
0V
L
N
FG
24V
0V
24V
0V
PE 24V
0V
24V
0V
PE
DP
DN
24V
0V
DP
DN
24V
0V
A
B
POWER IN SLAVE
POWER IN SLAVE
~
Terminator
Terminator
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
If the total length of the section where all the DP, DN, 24V, and 0V lines run in parallel is more than 50m
AnyWireASLINK master
AnyWireASLINK master
[Notes on Combined Use with 4-Wire (Isolated) Terminal]
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
If the total length of the sections where all the DP, DN, 24V, and 0V lines run in parallel in the power supply system is more than 50m, connect an
ASLINK lter (Type ANF-01) or a lter manufactured by COSEL Co., Ltd. (Type EAC-06-472) in series to the 24V and 0V lines at a position where
these four lines start running in parallel.
This will improve noise resistance, suppress the adverse effects of crosstalk caused by transmitted signals, and stabilize signals.
The above lters must be inserted regardless of whether power is supplied to all terminals collectively from the power supply for the master or
power is supplied to each terminal individually from their local power supply.
Insert the “ASLINK lter [Type ANF-01]” regardless of installation method and distance when complying with CE Standard.
②
Local power supply/branching
If the total length of the
section where all the
DP, DN, 24V, and 0V
lines run in parallel is
more than 50m
24V DC
stabilized
power supply General-purpose power
supply lter
(Use it if necessary.)
2-wire
terminal
2-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
If the total length of the sections (A + B)
where all the DP, DN, 24V, and 0V lines
run in parallel is more than 50m
■Filter allowable current
■AnyWire Type: ANF-01 Connection example
2-wire
terminal
4-wire
terminal
4-wire
terminal
ANF-01
Filter of COSEL Co., Ltd. EAC-06-472 MAX 6A/24V DC
MAX 5A/24V DC
Product Type Allowable power current
ASLINK lter
①
Power supply to the entire system

-BL296*B08F*4A20 7/16-
DP
DN
24V
0V
LINELOAD
LG
24V
0V L
N
FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
24V
0V L
N
FG
~
24V
0V
24V
0V
PE
DP
DN
24V
0V
LG
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
DP
DN
DP
DN
24V
0V
DP
DN
24V
0V
24V
0V
24V
0V
PE 24V
0V
24V
0V
PE
DP
DN
24V
0V
DP
DN
24V
0V
A
B
LINELOAD
LINELOAD
24V
0V
L
N
FG
~
If the total length of the section where all the DP, DN, 24V, and 0V lines run in parallel is more than 50m
AnyWireASLINK master
24V DC stabilized
power supply
General-purpose
power supply lter
(Use it if necessary.)
2-wire
terminal
4-wire
terminal
4-wire
terminal
AnyWireASLINK master
If the total length of the
section where all the
DP, DN, 24V, and 0V
lines run in parallel is
more than 50m
*
When using this lter, please be careful of the positions of LOAD and LINE.
24V DC stabilized
power supply
General-purpose
power supply lter
(Use it if necessary.)
2-wire
terminal
2-wire
terminal
4-wire
terminal
24V DC
stabilized
power supply
General-purpose power
supply lter
(Use it if necessary.)
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
If the total length of the sections (A + B)
where all the DP, DN, 24V, and 0V lines
run in parallel is more than 50m
■COSEL Co., Ltd. Type: EAC-06-472 Connection example
①
Power supply to the entire system
②
Local power supply/branching
Terminator
Terminator
*
When using this lter, please be careful of the positions of LOAD and LINE.
EAC-06-472
*
EAC-06-472
*
EAC-06-472
*

-BL296*B08F*4A20 8/16-
OUT
I/O
1: 24V
2: N/C
3: 0V
4: OUT
1: 24V
2: N/C
3: 0V
4: IN
■BL296XB-08F□-4A-20
4567
■BL296PB-08F□-4A-20
1: 24V
2: N/C
3: 0V
4: OUT
1: 24V
2: N/C
3: 0V
4: IN
1: 24V
2: N/C
3: 0V
4: IN
IN 0 1 2 3
IN 0 1 2 3
4567
OUT 0 1 2 3
OUT 0
1 2 3
■BL296SB-08F□-4A-20
e-CON compliant 4P socket*1
e-CON compliant 4P socket
e-CON compliant 4P socket
e-CON compliant 4P socket
Setting port
Black: DN
Red: DP
White: 0V
Green: 24V
LED indicators
Black: DN
Red: DP
White: 0V
Green: 24V
[Name of Each Part]
*The dotted lines are connected internally.
*1Prepare the connector separately.
*The 24V pins and 0V pins are individually connected inside.
If current is supplied collectively at a single 24V or 0V pin,
limit it to 0.5A or less.
■Bottom Lot label
OutputInput
Transmission
line
[Pin Assignment]

-BL296*B08F*4A20 9/16-
Address setting
Address setting
■Common procedure for address writer operation
[Various Settings]
Be sure to connect to the AnyWireASLINK master unit to use.
ARW-04 (address writer) of Rev. (Ver.) 1.01 or later version, or ARW-03 of Rev. (Ver.)
2.10 or later version is required for address setting.
For the details of the operating method, refer to the product guide of the address writer.
Connect this unit to the AnyWireASLINK master unit.
Set an address with the address writer with the transmission
signal (DP/DN) and power supply (24V/0V) being connected.
An address number is set as a beginning number from which part of the transmission frame is occupied to the terminal.
Set the address number within the range of bit address “0 to 254.”
(For the input/output mixed type, the same address number should be assigned to both input and output.)
- Set the address number so that the area occupied by the terminal does not exceed the transmission points of the master unit.
- Make sure that the address number setting is not duplicated.
- Also, use the address writer to read an address number that has been written in the terminal.
While power is supplied, make
sure that the above lines are not
short-circuited. Short-circuiting
the lines may cause a fault of the
unit.
Setting port
(hidden inside)
Black: DN
Red: DP
Green: 24V White: 0V
24V DC*
* For the power supply to be
connected, be sure to use
a 24V DC stabilized
power supply.
Transmission
signal
AnyWireASLINK
master
CAUTION
CAUTION
(Output)
(Input)
(Output)
(Input)
1:24V
3:0V
BL296SB-08F –
1:24V
4:OUT
BL296PB-08F –
1:24V
3:0V
BL296SB-08FS –
1:24V
4:OUT
BL296XB-08F –1:24V
3:0V
1:24V
3:0V
4:OUT
3:0V
BL296PB-08FS –
4:OUT
3:0V
BL296XB-08FS –
The factory-set address is “bit address 511,” which indicates that an
address has not been set.
Input and output operations are disabled with the factory-set address.

-BL296*B08F*4A20 10/16-
I/O 0
I/O 1
LINK
ALM
I/O 2
I/O 3
I/O 4
I/O 5
I/O 6
I/O 7
b3b4b5b7 b6 b2 b1 b0b11b12b13b15 b14 b10 b9 b8
BL296XB-08F-4A-20, BL296XB-08FS-4A-20
OUT0
n
IN0
OUT1
n+1
IN1
OUT2
n+2
IN2
OUT3
n+3
IN3
BL296SB-08F-4A-20, BL296SB-08FS-4A-20
BL296PB-08F-4A-20, BL296PB-08FS-4A-20
n+1
OUT1
n
OUT0
n+3
OUT3
n+2
OUT2
n+5
OUT5
n+4
OUT4
n+7
OUT7
n+6
OUT6
n+1
IN1
n
IN0
n+3
IN3
n+2
IN2
n+5
IN5
n+4
IN4
n+7
IN7
n+6
IN6
If an error is indicated, identify a cause of the error
by checking lit/ashing status with the table on the
left, and eliminate the cause of the error.
Once the cause of the error is eliminated, the error
indication will be automatically reset.
Address
offset
Bit input
Address
offset
Address
offset
Bit output
Bit input
Bit output
[Data Configuration]
*n = Bit address number assigned to this unit
*1
This can be used on the master unit having the status detail area. For details, refer to the manual for the master unit.
LED indicators
LED name
*2 This indication appears when the use of the single unit simplied replacement function fails.
*3 If ID duplication is detected when the master unit executes automatic address recognition,
this indication appears.
*4 This indication appears when transmission signal and power supply are normally
connected, and the unit is set to the factory-set address.
LINK
(Green)
ALM
(Red)
Flashing
Lit
Unlit
Flashing
Lit
Lit
Unlit
Unlit
Display status
Alternate ashing
Model mismatching error*2
Description
I/O power supply drop
No ALM available
Transmission signal received
Slave unit voltage drop
Model mismatching error*2
Transmission signal error
Model mismatching error*2
ID duplicated*3or ID unregistered*4
No transmission signal (disconnection and
reverse connection of DP and DN lines included)
[Monitor Display]
Status
details
Status detail area of the master unit
b0: Slave unit voltage drop (DP-DN-side voltage drop)
b5: I/O power supply drop (24V-0V-side voltage drop)
■Status details
The contents of an alarm detected with this unit can be checked with the “status detail area*1”
on the master unit.
A bit corresponding to the status detail area turns ON depending on the contents of the alarm.
I/O
(Orange)
LINK
ALM
LINK
ALM
LINK
ALM
ON
OFF
LINK
ALM

-BL296*B08F*4A20 11/16-
<LINK does not ash>
Remedy
Check the connection of this unit.
Check conditions of the master unit
and slave unit.
Disconnect this unit once, and then reconnect it.
[Troubleshooting]
Things to be checked
Remedy
Things to be checked
Remedy
Things to be checked
Remedy
Things to be checked
Remedy
Things to be checked
1) If LINK on the master unit is ashing and LINK on the slave unit is lit, it is possible that the master
unit has a fault or power supply (24V-0V) is directly connected to the DP-DN pins of the slave unit.
*
If LINK is lit while ALM is ashing, it means a failure in single unit simplied replacement.
2) If LINK on the master unit is ashing and LINK on the slave unit is unlit, it is possible that the power
(24V DC) is not supplied to the master unit, there is a disconnection on the transmission line (DP,
DN), or the slave unit has been damaged.
3) If LINK on the master unit is not ashing, check the power supply to the master unit. Also, since there
is a possibility that some system error has occurred, refer to the user’s manual of the master unit.
4) A slave unit incompatible with Ver.1.1 cannot be used in connection to the AnyWireASLINK system
for word transmission. Check the setting of the master unit, and lot No. of the slave unit.
<ALM is lit>
<ALM is ashing>
<LINK and ALM ashes alternately>
<LINK is lit and ALM is ashing: Model mismatching error (Failure in single unit simplied replacement)>
Check the connection of I/O terminals
on the slave unit.
Adjust the voltage of external power supply connected to the I/O side of the slave unit so that it falls
within the rating (21.6 to 27.6V).
In addition, ensure that there is no contact between and erroneous wiring of transmission lines.
Adjust the voltage of external power supply to the master unit so that it will be in the range from 21.6 to
27.6V. (Recommended voltage is 26.4V.) Check the total length.
Review the total length and wire diameter of transmission line so that the load will not exceed the current
limit supplied by the transmission line and adjust the connected load. (In the case of the wire size of
1.25mm2and total length of 50m or less, the current supplied by the transmission line is 2A.)
*
If ALM is ashing while LINK is lit, it means a failure in single unit simplied replacement.
Check if the replacement slave unit is of the same type as that of the slave unit before the replacement.
Check if the function version for the replacement slave unit is older than that of the slave unit before the
replacement.
*
If the function version of the replacement slave unit is older, the single unit simplied replacement function does not
work.
The address of the slave unit is either unregistered or duplicated.
Take the following actions.
*
The slave unit cannot be used with the factory-set address.
1) Set an address correctly.
2) Check if there is a slave unit on which the indicator lamps are ashing in the same manner and reset
the addresses so that they are not duplicated.
Check the address of the slave unit.
Check the address of the slave unit.
Check the model of the slave unit.
Check the lot No. of the slave unit.
Check the connection of the slave
unit.
Check the voltage (24V DC) of
external power supply to the master
unit.
Check if the address of the replacement slave unit is the same as the address before shipment (a bit
address of 511).
*
If the address of the replacement slave unit is not the same as the address before shipment, the single unit simplied
replacement function does not work.
Defective connections and the like may have caused single unit simplied replacement to fail.
Remove the slave unit after replacement, and make connections again.
*
When two or more replacement slave units are simultaneously connected, the single unit simplied replacement
function does not work.

-BL296*B08F*4A20 12/16-
6.8k
24V (1)
IN (4)
OUT (4)
0V (3)
6.8k
24V (1)
24V
OUT
0V
IN (4)
24V (1)
24V
0V
OUT (4)
IN
0V (3)
24V (1)
0V (3)
0V (3)
BL296SB-08F-4A-20
BL296XB-08F-4A-20 (Input)
BL296PB-08F-4A-20
BL296XB-08F-4A-20 (Output)
<Circuit conditions>
DN (Black)
DP (Red)
24V (Green)
0V (White)
DN (Black)
DP (Red)
24V (Green)
0V (White)
4-wire (isolated) ASLINK terminal
(Power supply of the AnyWire system)
Load driven by
an external power supply
4-wire (isolated) ASLINK terminal
(Power supply of the AnyWire system)
Load driven by
an external power supply
[Configuration and Electrical Characteristics of the Input and Output Circuits]
<Circuit conditions>
Rated input voltage:
Max. switching current:
ON current:
OFF current:
ON voltage:
OFF voltage:
Allowable current at 24V:
24V DC
3.5mA
2.2mA or more
1mA or less
16V or more (24V-IN)
8V or less (24V-IN)
1A max. (24V-0V)
(per terminal)
Withstand voltage:
Max. ON current:
30V DC
100mA
DN (Black)
DP (Red)
24V (Green)
0V (White)
To connect
inductive load, use
a surge killer.
If output is turned
ON with the 24V
and OUT terminals
short-circuited,
the output device
will be damaged.
To connect loads (e.g. I/O ports) that
are controlled with a power supply
other than the one used for the
AnyWireASLINK system, always use a
4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
[E.g.]
Use the device by connecting the 0V
lines together.
DN (Black)
DP (Red)
24V (Green)
0V (White)
Load
4-wire (isolated) NPN input
Switch, sensor, etc.
(2-wire type)
To connect loads (e.g. I/O ports) that
are controlled with a power supply
other than the one used for the
AnyWireASLINK system, always use a
4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
[E.g.]
Use the device by connecting the 0V
lines together.
CAUTION
4-wire (isolated) NPN output
CAUTION
Internal circuit
Internal circuit
Internal circuit
Control circuit
Internal circuit
Control circuit

-BL296*B08F*4A20 13/16-
6.8k
6.8k
24V
OUT
0V
24V
0V
IN
<Circuit conditions>
DN (Black)
DP (Red)
24V (Green)
0V (White)
DN (Black)
DP (Red)
24V (Green)
0V (White)
4-wire (isolated) ASLINK terminal
(Power supply of the AnyWire system)
Load driven by
an external power supply
4-wire (isolated) ASLINK terminal
(Power supply of the AnyWire system)
Load driven by
an external power supply
<Circuit conditions>
Rated input voltage:
Max. switching current:
ON current:
OFF current:
ON voltage:
OFF voltage:
Allowable current at 24V:
24V DC
3.5mA
2.2mA or more
1mA or less
16V or more (IN-0V)
8V or less (IN-0V)
1A max. (24V-0V)
(per terminal)
Withstand voltage:
Max. ON current:
30V DC
100mA
DN (Black)
DP (Red)
24V (Green)
0V (White)
To connect
inductive load, use
a surge killer.
If output is turned
ON with the OUT
and 0V terminals
short-circuited,
the output device
will be damaged.
To connect loads (e.g. I/O ports) that
are controlled with a power supply
other than the one used for the
AnyWireASLINK system, always use a
4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
[E.g.]
Use the device by connecting the 0V
lines together.
DN (Black)
DP (Red)
24V (Green)
0V (White)
4-wire (isolated) PNP input
BL296SB-08FS-4A-20
BL296XB-08FS-4A-20 (Input)
Switch, sensor, etc.
(2-wire type)
To connect loads (e.g. I/O ports) that
are controlled with a power supply
other than the one used for the
AnyWireASLINK system, always use a
4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
[E.g.]
Use the device by connecting the 0V
lines together.
4-wire (isolated) PNP output
BL296PB-08FS-4A-20
BL296XB-08FS-4A-20 (Output)
Internal circuit
Internal circuit
Control circuit
Load
Internal circuit
Internal circuit
Control circuit
24V (1)
IN (4)
0V (3)
24V (1)
IN (4)
0V (3)
OUT (4)
24V (1)
24V (1)
0V (3)
0V (3)
OUT (4)
CAUTION
CAUTION

-BL296*B08F*4A20 14/16-
I/O side*5
(24V-0V)
BL296SB-08F-4A-20
BL296XB-08F-4A-20
BL296PB-08F-4A-20
BL296SB-08FS-4A-20
BL296XB-08FS-4A-20
BL296PB-08FS-4A-20
BL296SB-08F-4A-20
BL296XB-08F-4A-20
BL296PB-08F-4A-20
BL296SB-08FS-4A-20
BL296XB-08FS-4A-20
BL296PB-08FS-4A-20
■Individual specications
Number of
occupied
points
Current
consumption
Detection
function
Slave unit voltage drop (DP-DN voltage drop)
I/O power supply drop (24V-0V voltage drop)
Weight
Response time*4
41g
1ms max.
[Specifications]
Service power supply voltage
Transmission method
Synchronization method
Transmission procedure
Connection mode
Number of
connection points
*3
Number of connection units
RAS function
24V DC +15% to -10% (21.6 to 27.6V DC)
with a ripple of 0.5Vp-p or less
DC power supply superimposed
total frame/cyclic method
Frame/bit synchronization method
AnyWireASLINK protocol
Bus type (Multi-drop method, T-branch
method, Tree branch method)
Number of bit points:
512 points max.
(Input: 256 bits, Output: 256 bits)
Number of word points:
1024 words max.
(Input: 512 words, Output: 512 words)
Up to 128 units
Detection of transmission line disconnection,
transmission line short-circuit, transmission
power supply drop, and
duplicated/unregistered ID
■Transmission specications
*4Indicates the internal processing time of this unit. The maximum transmission delay time
is dened as “this time + bit transmission cycle time × 2.”
*5Current consumption for input is a value assumed when all IN-0V pins (NPN) or 24V-IN
pins (PNP) are short-circuited. To connect a 3-wire type sensor, add a total current
consumption of the sensor.
Current consumption for output is a value assumed when all points are turned ON. Add a
total current consumption of load being connected.
*1 Do not use or store AnyWireASLINK devices in an environment where the pressure exceeds
the atmospheric pressure at an altitude of 0 meters. Doing so may result in malfunction.
*2“Pollution level” is an index that indicates the degree of occurrence of conductive
substances in the environment where the device is used.
Pollution level 2 means the occurrence of only pollution by non-conductive substances.
In such an environment, however, electrical conduction could occur due to accidental
condensation.
NPN bit input: 8 points
NPN bit input: 4 points/
bit output: 4 points
NPN bit output: 8 points
PNP bit input: 8 points
PNP bit input: 4 points/
bit output: 4 points
PNP bit output: 8 points
Transmission
side
(DP-DN)
*3 The number differs depending on the master unit. Be sure to refer to the manual of the
master unit for the number.
Operating ambient
temperature/humidity
Storing ambient
temperature/humidity
Vibration resistance
Shock resistance
Atmosphere
Operating altitude*1
Pollution level*2
0 – +55°C, 10 – 90%RH No condensation
-25 – +75°C, 10 – 90%RH No condensation
Based on JIS B 3502 and IEC 61131-2
Based on JIS B 3502 and IEC 61131-2
No corrosive gas
0 – 2000m
2 or less
■General specications
6.0mA
6.0mA
6.0mA
6.0mA
6.0mA
6.0mA
40.0mA
26.0mA
10.0mA
40.0mA
26.0mA
10.0mA

-BL296*B08F*4A20 15/16-
47.8
10.7
47.8
10.7
10.5 64 56
19.7521.05
40.8
35
19.75
40.8
35
19.75
23
30
24.2
21 3
37.1
26.3
21.6
15.8
100
10 10
4.5
9
9
5.5
111
(200)
(25)
2
2
7
7
5.2 5664
6.95
[Outside Dimensions] Unit: mm
■ADP-T96 (dedicated DIN rail mounting adaptor) *
Optionally available
UL style 20276
4-wire × AWG23 φ4.6, gray
Black: DN
Red: DP
White: 0V
Green: 24V
■These dimensions are common to all models.
3.5 × 4.5 φ3.5
*
This figure shows an example of BL296SB-08F-4A-20.

Printed in Japan 2020 UMA-20145AB-EN
-BL296*B08F*4A20 16/16-
Anywire Corporation
Headquarters :1 Babazusho, Nagaokakyo-shi, Kyoto 617-8550 JAPAN
:Contact by website http://www.anywire.jp
[Address]
This manual suits for next models
6
Table of contents
Other Anywire Touch Terminal manuals

Anywire
Anywire B281-B-02U-CC20 Series User manual

Anywire
Anywire ASLINKAMP L-A1AW Series User manual

Anywire
Anywire BL287SB-02F-CC20 User manual

Anywire
Anywire ASLINK BL296 B-08F V50 Series User manual

Anywire
Anywire Bitty Series User manual

Anywire
Anywire ASLINK BL296SB-04F-4A-20 User manual

Anywire
Anywire AnyWireASLINK BL296PB-16F-4A-20 User manual

Anywire
Anywire BL296 B-16F Series User manual