ASLINKTERMINAL
[ASLINK Small Integrated 16-Point Terminal]
AnyWireASLINK System Products Guide
BL296□B-16F□-4A-20
The Products Guide describes individual products. Refer to the Guide as necessary.
■Function List  
-BL296*B16F*4A20 1/11-
Connection targets
I/O
short
circuit
SpecicationsModel
I/O
disconnection
ASLINKTERMINAL
four-wire
(isolated) cable
type
NPN 16-point input/16-point output
PNP 16-point input/16-point output
NPN 8-point input/8-point output (hybrid)
PNP 8-point input/8-point output (hybrid)
Universal sensors
and switches,
universal output
devices
Small-
sized
Sensing
level
reduction
I/O
power supply
reduction
Slave unit
voltage
reduction
[Warranty]
[Notes on Safety]
Precautions that must be observed in order to use this system safely are indicated as shown below.
You must observe these precautions.
WARNING CAUTION
A WARNING indicates a potentially hazardous
situation which, if not handled correctly, could
result in death or serious injury.
ACAUTION indicates a potentially hazardous situation
which, if not handled correctly, may result in personal
injury or property damage.
WARNING
○System Safety
○Always turn off the power before attempting to mount or replace.
This system is intended for general industrial applications. It does not have functions for supporting applications requiring higher
levels of safety such as safety-related devices or accident prevention systems. The product must not be used for these purposes.
○
Prolonged continuous ow of a rated load current or higher or a transit current due to load short-circuit, etc., in the hybrid unit including
the output unit and the output circuit may result in smoking or ring. An external safety device such as a fuse must be installed.
○Use the AnyWireASLINK within the range of the specications and conditions shown below.
○System power supply
○Separately route high-voltage and power cables
○Connectors and terminals
○Do not impose any external loads on the units. Doing so may cause a failure.
○Do not disconnect or reconnect between the transmission line and slave units. A malfunction may occur.
Use a stable, 24V DC power supply. Use of an unstable power supply may cause problems with the system.
Although the AnyWireASLINK has a high noise margin, keep the transmission line and I/O cables away from high-voltage and
power cables.
*
Pay careful attention to the length and installation of cable wiring to ensure that connectors and cables are neither overloaded nor disconnected.
* Make sure to prevent any metal objects from getting inside the connectors or the terminal blocks.
* Short-circuits caused by metal objects or mis-wiring are likely to damage the device.
CAUTION
■Warranty period
The warranty on the delivered Product shall continue to be effective for one (1) year after the delivery thereof to a location as
designated by the original owner.
■Scope of warranty
Should a defect occur in any part of the Product during the foregoing warranty period when it is used normally in acordance with
the specications described in this User's Manual, the Company shall replace or repair the defect free of charge, except when it
arises as a result of:
[1] Misuse or abuse of the Product by the owner;
[2] Fault caused by other than the delivered Product;
[3] The unauthorized modication or repair of the Product by any person other than the Company's personnel;
[4] Any unusual force of nature, disaster or other cause beyond the Company's control.
The term "warranty," as used herein, refers to the warranty applicable to the delivered product alone. The Company shall not be
liable for consequential or incidental damages resulting from any malfunction.
■Repair at cost
After the expiration of the warranty period, the owner shall be responsible for all costs and expenses incurred for the trouble-
shooting and repair of the Product. Even during the warranty term, the Company shall repair any defects arising from causes
other than within the scope of the warranty as specied above, at the owner's cost.
■Notes on use ⇒
To set any address, an “Address writer ARW-04 (Ver. 04-1.01 or higher), ARW-03 (Ver. 2.10 or higher)”
is required. Please prepare it separately.
[Type]
BL296SB-16F-4A-20
BL296PB-16F-4A-20
BL296XB-16F-4A-20
NPN input
NPN output
NPN input/NPN output
BL296SB-16FS-4A-20
BL296PB-16FS-4A-20
BL296XB-16FS-4A-20
PNP input
PNP output
PNP input/PNP output
○
×○○ ××
Functions
-BL296*B16F*4A20 2/11-
AnyWireASLINK
master
24V DC*1
Black: DN
Red: DP
Red: DP Black: DN
Black: DN
Red: DP
BT0
Red: DP Black: DN
Two points
Two points
Two points
Two points
16 points
16 points
ASLINK lter
■Connection example based on
a four-wire (isolated) terminal
Supply current on the transmission line (DP/DN)
Total length 50m or less
Size of
the transmission
line (DP/DN)
1.25mm2
0.75mm2
0.5mm2
MAX 2A
MAX 1.2A
■
Relationship between the size and length of
the transmission line and the supply current (Table 1)
MAX 0.5A
MAX 0.3A
Total length 100m to 200m
MAX 1A
MAX 0.6A
MAX 0.8A MAX 0.2AMAX 0.4A
Total length 50m to 100m
[Connection Example]
CAUTION
- Refer to Table 1 so that the size and length of the
transmission line and the allowable supply current lie within
an appropriate range.
- Connect the same symbols (DP/DN) correctly between the
AnyWireASLINK master and each device.
- The branching length or branch number has no limitation.
- Include the length of the cable provided with the terminal in
the “total line length.”
- Connect the terminator “BT0 (polar)” to the DP/DN terminal
farthest from AnyWireASLINK master.
If the load consumption current
is large, a four-wire (isolated)
terminal can be selected.
This terminal can correspond
to I/O of the controller with an
external power supply.
[Installation Location]
-Location where the unit is not subject to vibration or shock
-Location where the unit is not directly exposed to dust
-Location where the main body is not directly exposed to conductors
such as waste metal and sputter
-Location where humidity is not condensed
-Location where the atmosphere is free of corrosive gas, ammable gas
and sulfur
-Location where the unit is removed from high-voltage or high-current
cables
-Location where the unit is removed from cables and controllers that
generate servo, inverter or other high-frequency noise.
The branching
has no limitation.
Black: DN
Red: DP
Black:
DN
Red: DP
AnyWireASLINK terminator
One terminator should be connected to the DP/DN terminal farthest
from the AnyWireASLINK master.
Connect it correctly so as not to set the wrong polarity.
Black: DN Red: DP
Two points
Two points
Two points
Two points
Two points
24V DC*1
General-purpose
power supply lter
4P link connector is
convenient for
branching.
Dedicated at cable
1.25mm2(four-wire)
The sum of the
portions of DP/DN is
the total line length.
General-purpose power supply lter
* When complying with the
UL Standard, make sure to
use a 24V DC stabilized
power supply of “NEC
Class 2 Output.”
* Make sure to use a 24V DC
stabilized power supply for
the power supply to be
connected.
The AnyWireASLINK can employ a two-wire or four-wire terminal selectively depending on the load current.
This Products Guide describes a four-wire (isolated) terminal.
In the case of hybridization, refer to the Two-Wire (Non-Isolated) Terminal Products Guide separately.
If the load current is small, using a two-wire (non-isolated) terminal allows for achieving simplied wiring without local power supply.
In the case of prioritizing the sites of concentrated loads and/or the number of connections, hybridization with a four-wire (isolated) terminal,
which supports local power supply, is also possible.
Make sure to use a four-wire (isolated) terminal in the case of input and load driving using an external power supply.
[How to connect AnyWireASLINK]
-BL296*B16F*4A20 3/11-
■AnyWire Type: ANF-01 Connection example
■Filter allowable power current
DP
DN
24V
0V
POWER IN SLAVE
LG
24V
0V L
N
FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
ANF-01
24V DC stabilized
power supply
General-purpose power
supply lter
(Use it if necessary.)
24V
0V L
N
FG
~
24V DC stabilized
power supply
4-wire
terminal
4-wire
terminal
2-wire
terminal
If any of the side-by-side lines of DP, DN, 24V and 0V exceeds the total length of 50m
24V
0V
24V
0V
PE
24V DC stabilized
power supply
ANF-01
ANF-01
DP
DN
24V
0V
LG
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
DP
DN
DP
DN
24V
0V
4-wire
terminal
2-wire
terminal
4-wire
terminal
2-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
4-wire
terminal
DP
DN
24V
0V
24V
0V
L
N
FG
24V
0V
24V
0V
PE 24V
0V
24V
0V
PE
DP
DN
24V
0V
DP
DN
24V
0V
A
B
①Power supply to the entire system
②Local power supply/branching
AnyWireASLINK master
AnyWireASLINK master
POWER IN SLAVE
POWER IN SLAVE
General-purpose power
supply lter
(Use it if necessary.)
~
General-purpose power
supply lter
(Use it if necessary.)
Insert the “ASLINK lter [Type ANF-01]” regardless of installation method and distance when complying with CE Standard.
If any of the side-by-side lines of DP, DN, 24V and 0V exceeds the total length of 50m in a power supply system to be supplied, serially connect
the “ASLINK lter [Type ANF-01]” or “lter of COSEL Co., Ltd. [Type EAC-06-472]” to 24V and 0V in the starting position of the side-by-side lines.
This will improve noise resistance, reduce the impact of crosstalk by transmission signals and stabilize the signals.
In any case of power supply to the entire system from the master driving power supply or power supply from the local power supply, insert a lter.
[Precautions for use with 4-Wire (Insulated) Terminal]
ASLINK lter ANF-01 MAX 5A/24V DC
Filter of COSEL Co., Ltd. EAC-06-472 MAX 6A/24V DC
Model Type
Allowable power current
If any of the
side-by-side lines of DP,
DN, 24V and 0V
exceeds the total length
of 50m
If (A+B) of the side-by-side lines of DP,
DN, 24V and 0V exceeds the total length
of 50m
-BL296*B16F*4A20 4/11-
DP
DN
24V
0V
LINELOAD
LG
24V
0V L
N
FG
~
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
24V DC stabilized
power supply
24V
0V L
N
FG
~
24V DC stabilized
power supply
2-wire
terminal
4-wire
terminal
4-wire
terminal
If any of the side-by-side lines of DP, DN, 24V and 0V exceeds the total length of 50m
■COSEL Co., Ltd. Type: EAC-06-472 Connection example
24V
0V
24V
0V
PE
DP
DN
24V
0V
LG
DP
DN
24V
0V
DP
DN
DP
DN
24V
0V
DP
DN
BT0
2-wire
terminal
DP
DN
2-wire
terminal
4-wire
terminal
DP
DN
24V
0V
4-wire
terminal
DP
DN
24V
0V
4-wire
terminal
4-wire
terminal
24V
0V
24V
0V
PE 24V
0V
24V
0V
PE
DP
DN
24V
0V
DP
DN
24V
0V
4-wire
terminal
4-wire
terminal
A
B
①Power supply to the entire system
②Local power supply/branching
LINELOAD
LINELOAD
AnyWireASLINK master
AnyWireASLINK master
EAC-06-472
EAC-06-472
EAC-06-472
When using this lter, please be careful of the positions of LOAD and LINE.
General-purpose
power supply lter
(Use it if necessary.)
General-purpose
power supply lter
(Use it if necessary.)
24V DC
stabilized
power supply
24V
0V
L
N
FG
~
General-purpose power
supply lter
(Use it if necessary.)
When using this lter, please be careful of the positions of LOAD and LINE.
If (A+B) of the side-by-side lines of DP, DN,
24V and 0V exceeds the total length of 50m
If any of the
side-by-side lines of DP,
DN, 24V and 0V
exceeds the total length
of 50m
-BL296*B16F*4A20 5/11-
[Address Number Setting]
-BL296*B16F*4A20 5/11-
1. Address number writing
1:24V
3:0V
BL296SB-16F~
1:24V
4:OUT
BL296PB-16F~
1:24V
3:0V
1:24V
3:0V
1:24V
3:0V
BL296SB-16FS~
1:24V
4:OUT
BL296XB-16F~1:24V
3:0V
1:24V
3:0V
BL296PB-16FS~
3:0V
4:OUT
3:0V
4:OUT
BL296XB-16FS~
Make sure that no short circuit
occurs in the lines above.
Otherwise, a malfunction may occur.
Setting port
(R/W)
Fig. 2
(Output side)
(Output side)
- The address number to be set to the terminal is for correspondence to the input/output memory map of the controller.
This address number is the assigned rst position in the AnyWire input/output transmission frame (0 to 255). In the terminal, 16 points
(input or output) or 8 points (input/output mixed) are occupied after this number. In the case of input/output mixed type, the address
numbers for both input and output are the same.
- The address number can be set by one point.Set the address numbers so that the area occupied by the terminal does not exceed the
maximum transfer points.
- Use a dedicated address writer ARW-04 (Ver.04 to 1.01 or higher) or ARW-03 (Ver. 2.10 or higher) to write the address to be set in the terminal.
As for how to operate address writers ARW-04 (Ver.04 to 1.01 or higher) and ARW-03 (Ver. 2.10 or higher), refer to the product manual of the
address writer.
(The port cannot
be seen from the
surface.)
The state in which the installation dedicated
DIN rail adapter is mounted and fixed in the
same direction as the DIN rail.
The state in which the installation dedicated
DIN rail adapter is mounted and fixed in the
same direction as the DIN rail.
■ADP-W96 (Installation dedicated DIN rail adapter)
[Installation Method]
10.50
47.60
10.50
47.60
41.80
41.90
53.80
41.80
41.90
53.80
A
A
B
B
Cross-section view A-A
Cross-section view A-A
①Connect the AnyWireASLINK master and power supply to the transmission line of
 BL296□B-16F□-4A-20 to supply transmission signals and 24V DC.
②Operate the address writer to write address numbers with the address writer directed at the setting
 port of the main body (Fig. 2).
 (Hold the light receiving and emitting part as close as possible to the setting port.)
③In the case of writing in WRITE mode, reset the power supply of BL296□B-16F□-4A-20.
■How to set
Address numbers settable with BL296□B-16F□-4A-20: Input or output
Input/output mixed
0 to 240
0 to 248
Black: DN
Red: DP
Green:
24V White: 0V
Transmission
signal
AnyWireASLINK
master
24V DC*1
24V DC*1
*1Make sure to use a 24V
DC stabilized power
supply for the power
supply to be connected.
CAUTION
CAUTION
The factory setting of the terminal is “255,” which means no setting.
In this state, the terminal cannot perform an input/output operation.
2. Settings reading
When reading the address number which was written in the terminal, also use the address writer.
-BL296*B16F*4A20 6/11-
[Connection]
[Name of each part]
■Pin layout
Input side
1:24V
2:N.C
3:0V
4:OUT
BL296SB-16F-4A-20
BL296SB-16FS-4A-20
BL296XB-16F-4A-20
BL296XB-16FS-4A-20
Common to all models
BL296PB-16F-4A-20
BL296PB-16FS-4A-20
Black : DN
Red : DP
White : 0V
Green : 24V
*The dotted lines are internally connected.
**Pins of the same symbols are connected internally for 24V and 0V.
When collectively supplying current from 24V and 0V, the current should be 1A or less.
■Example of mounting LP connector on the edge of the transmission line
Applicable LP connector: LP-WW-10P
4 3 2 1
AB
C
Cover
Pressure weld using a dedicated
tool so that the ttings of the body
are in the holes of the cover.
After pressure welding, make
sure to check that hooks
③to ⑥are securely engaged.
The state in which the
cover is mounted
Make sure to check
that hooks ①and ②
are engaged.
① ② ⑤ ⑥
③ ④
Dedicated tool: LP-TOOL
Output side
1:24V
2:N.C
3:0V
4:IN
1:24V
2:N.C
3:0V
4:IN
1:24V
2:N.C
3:0V
4:IN
1:24V
2:N.C
3:0V
4:OUT 1:24V
2:N.C
3:0V
4:OUT
1:24V
2:N.C
3:0V
4:OUT 1:24V
2:N.C
3:0V
4:OUT
e-CON-compliant 4P socket
Black : DN
Red : DP
White : 0V
Green : 24V
Example of BL296PB-16F□-4A-20
LED display
Setting port
Transmission line
Put the lines in the grooves so that
the black line (DN) is on the hinge
side of the cover, fold A to the B
side and hook them with hook C to
x.
-BL296*B16F*4A20 7/11-
[Indication Function]
LED indication unit
IN 0
IN 1
LINK ALM
IN 2
IN 3
IN 4
IN 5
IN 6
IN 7
OUT 0
OUT 1
OUT 2
OUT 3
OUT 4
OUT 5
OUT 6
OUT 7
I/O 0
I/O 1
LINK ALM
I/O 2
I/O 3
I/O 4
I/O 5
I/O 6
I/O 7
I/O 8
I/O 9
I/O 10
I/O 11
I/O 12
I/O 13
I/O 14
I/O 15
BL296XB-16F□-4A-20 BL296SB-16F□-4A-20
BL296PB-16F□-4A-20
Indication status Detailed states
Normal
I/O voltage reduction
Slave unit voltage reduction
Transmission error
DP/DN disconnected or no power supply
Normal
Master unit detecting the unit ID (address)
redundant or not set
ON
OFF
Flashing
On
Flashing
Alternate ashing
On
Off
Off
On
Off
LINK
ALM
For information on narrowing down the cause of a trouble occurrence,
see the following section “Troubleshooting.”
Normal state: LINK ashing, ALM off, I/O ON on/OFF off
LINK
LINK
ALM
I/O
LED symbol
ALM
[Troubleshooting]
<LINK not ashing>
<ALM on>
<ALM ashing>
<LINK and ALM ashing alternately>
Check items Measures
Check items Measures
Check items Measures
Check items Measures
Check the connection status of the slave unit.
Disconnect and reconnect the slave unit.
Check if the LINK LED of the master unit ashes and take the following measures.
1) If the LINK of the master unit ashes and the LINK of the slave unit is on, the master unit may be
damaged. Please contact our helpdesk.
2) If the LINK of the master unit ashes and the LINK of the slave unit is off, the master unit may not
be powered (24V DC), the transmission line (DP/DN) may be partially disconnected, or the slave
unit may be damaged. Check if the master unit is powered and, if necessary, please contact our
helpdesk.
3) If the LINK of the master unit does not ash, check if the master unit is powered. Other system
errors may also occur. Refer to the User’s Manual of the master unit.
Adjust the power voltage of the externally supplied power that is connected to the I/O side of the
slave unit so that it is at the rated value (21.6V to 27.6V).
As for terminal wiring, check that there is no contact or incorrect wiring of each transmission line.
Adjust the voltage of the external power supply of the master unit to lie within the range from 21.6 to
27.6V (recommended voltage is 26.4V). Check the total line length.
Review the total line length and the size of the transmission line so as not to connect a load exceeding
a supply current limit on the transmission line and, if necessary, adjust the connected load (e.g. the
supply current on the transmission line is 2A if the size is 1.25mm
2
and the total length is 50m or less).
The address of the slave unit is not set (255) or address redundancy occurs. Take the following measures.
1) Change the address within the range from 0 to 254.
2) Check if there is another slave unit undergoing the same ashing and, if necessary, reset the
address so as not to be redundant.
Check the I/O side connection of the
slave unit.
Check the voltage of the external
power supply (24V DC) of the master
unit.
Check the address of the slave unit.
Check the connection status of the
master unit.
In case of an abnormal indication status, narrow down the
cause and remove the trouble based on the on/ashing status
and the left table.
The indication status will be restored automatically after the
trouble is removed.
-BL296*B16F*4A20 8/11-
[Input/Output Circuit Configuration and Electrical Properties]
6.8k
24V(1)
DN (black)
D P(Red)
Switch, sensor, etc.
(2-wire type)
IN(4)
24V(1)
OUT(4)
0V(3)
24V (Green)
0V (White)
DN (black)
D P(Red)
24V (Green)
0V (White)
DN (black)
D P(Red)
24V (Green)
0V (White)
Load
6.8k
24V(1)
24V
OUT
0V
IN(
4
)
0V(3)
4-wire (insulated) NPN input
BL296SB-16F-4A-20
4-wire (insulated) ASLINK terminal
(AnyWire series power supply)
Load by external type
power supply
[Ex.]
Use with the common value set at 0V.
BL296XB-16F-4A-20 (Input side)
4-wire (insulated) NPN output
BL296SB-16F-4A-20
BL296XB-16F-4A-20 (Output side)
Internal circuit
Internal circuit
Internal circuit
Control circuit
In the case of connecting with a load
(input/output port, etc.) controlled by a
power supply different from the power
supply used with AnyWireASLINK,
make sure to use a 4-wire (insulated)
terminal.
Otherwise a malfunction may occur.
In the case of an
inductive load, mount a
surge killer.
If the power is turned
on with the circuit
between OUT and 24V
shorted, passive
elements may be
damaged.
<Circuit conditions>
Rated input voltage : 24V DC
Maximum switching current
: 3.5mA
ON current : 2.2mA or more
OFF current : 1mA or less
ON voltage : (24V-IN) 16V or more
OFF voltage : (24V-IN) 8V or less
Allowable 24V current : (24V-0V) up to 1A
(per terminal)
<Circuit conditions>
Withstand voltage : 30V DC
Maximum ON current : 100mA
CAUTION
DN (black)
D P(Red)
24V (Green)
0V (White)
24V (1)
24V
OUT
0V
IN
(4)
4-wire (insulated) ASLINK terminal
(AnyWire series power supply)
Load by external type
power supply
[Ex.]
Use with the common value set at 0V.
Internal circuit
In the case of connecting with a load
(input/output port, etc.) controlled by a
power supply different from the power
supply used with AnyWireASLINK,
make sure to use a 4-wire (insulated)
terminal.
Otherwise a malfunction may occur.
CAUTION
Control circuit
-BL296*B16F*4A20 9/11-
6.8k
24V(1)
DN (black)
D P(Red) Switch, sensor, etc.
(2-wire type)
IN(4)
0V(3)
OUT(4)
0V(3)
24V (Green)
0V (White)
DN (black)
D P(Red)
24V (Green)
0V (White)
DN (black)
D P(Red)
24V (Green)
0V (White)
Load
6.8k
24V(1)
24V
OUT
0V
IN(4)
0V(3)
4-wire (insulated) NPN input
BL296SB-16FS-4A-20
4-wire (insulated) ASLINK terminal
(AnyWire series power supply)
Load by external type
power supply
[Ex.]
Use with the common value set at 0V.
BL296XB-16FS-4A-20 (Input side)
4-wire (insulated) NPN output
BL296SB-16FS-4A-20
BL296XB-16FS-4A-20 (Output side)
Internal circuit
Internal circuit
Internal circuit
Control circuit
In the case of connecting with a load
(input/output port, etc.) controlled by a
power supply different from the power
supply used with AnyWireASLINK,
make sure to use a 4-wire (insulated)
terminal.
Otherwise a malfunction may occur.
In the case of an
inductive load, mount a
surge killer.
If the power is turned
on with the circuit
between OUT and 24V
shorted, passive
elements will be
damaged.
<Circuit conditions>
Rated input voltage : 24V DC
Maximum switching current : 3.5mA
ON current : 2.2mA or more
OFF current : 1mA or less
ON voltage : (IN-0V) 16V or more
OFF voltage : (IN-0V) 8V or less
Allowable 24V current : (24V-0V) up to 1A
(per terminal)
<Circuit conditions>
Withstand voltage : 30V DC
Maximum ON current : 100mA
CAUTION
DN (black)
D P(Red)
24V (Green)
0V (White)
24V
IN
0V
0V
OUT(
4
)
(3)
4-wire (insulated) ASLINK terminal
(AnyWire series power supply)
Load by external type
power supply
[Ex.]
Use with the common value set at 0V.
Internal circuit
Control circuit
In the case of connecting with a load
(input/output port, etc.) controlled by a
power supply different from the power
supply used with AnyWireASLINK,
make sure to use a 4-wire (insulated)
terminal.
Otherwise a malfunction may occur.
CAUTION
-BL296*B16F*4A20 10/11-
[Specifications]
[Outside dimensions]
■ The dimensions are common to all models.
(200)
(57)
14.6
37.1
91
(21)
38.5
19.25
84.5 3.25
2-Φ3.5
24V
NC
0V
OUT
OUT
0
OUT
8
R/W
LINK ALM
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
24V
NC
0V
OUT
Unit: mm
*The figure is an example of BL296PB-16F-4A-20.
UL style 20276
4 wires × No.23AWG Ø 4.6 Gray
BL296PB-
16F-4A-20
68.715.7 6.6
4.5
Detecting transmission signal level reduction
Defecting I/O voltage reduction
BL296SB-16F-4A-20
BL296SB-16FS-4A-20
BL296XB-16F-4A-20
BL296XB-16FS-4A-20
NPN Input 16 point
PNP Input 16 point
NPN Input 8 point, Output 8 point
PNP Input 8 point, Output 8 point
BL296PB-16F-4A-20
BL296PB-16FS-4A-20
NPN Output 16 point
PNP Output 16 point
■Individual Specications■General Specications
■Transmission Specications
Number of
occupied
data items
Response time
*3
BL296SB-16F-4A-20 :60g
BL296XB-16F-4A-20 :60g
BL296PB-16F-4A-20 :60g
BL296SB-16FS-4A-20:60g
BL296XB-16FS-4A-20:60g
BL296PB-16FS-4A-20:60g
Monitoring
function
Mass
BL296SB-16F-4A-20
BL296XB-16F-4A-20
BL296PB-16F-4A-20
BL296SB-16FS-4A-20
BL296XB-16FS-4A-20
BL296PB-16FS-4A-20
Consumption
current
Transmission side
I/O side*4
8 mA
8 mA
8 mA
8 mA
8 mA
8 mA
80 mA
50 mA
80 mA
50 mA
15 mA
15 mA
Up to 1ms
Ambient temperature use
Ambient humidity use
Temperature/humidity storage
Atmosphere
Altitude use*1
Pollution level*2
Noise resistance
0 - +55℃
10 - 90%RH No condensation
-25 - +75℃
No corrosive gas
0 - 2000m
2 or less
1200Vp-p (pulse width 1μs)
(Do not preserve or use under an environment pressurized equal to
or higher than the atmospheric pressure at the altitude of 0m)
Power supply voltage use
Transmission method
Synchronization method
Transmission procedure
Connection mode
Number of connection points
Number of connection points
24V DC +15% to -10% (21.6 to 27.6V DC) with a ripple of 0.5Vp-p or less
DC power supply superimposed total frame/cyclic method
Frame/bit synchronization method
Dedicated protocol
Bus type (Multi-drop method, T-branch method, Tree branch method)
512 max. (IN: 256, OUT: 256)
Up to 128 units
*1 Do not use or store AnyWireASLINK equipment under an environment pressurized higher
than the atmospheric pressure at an altitude of 0m. Otherwise, a malfunction may occur.
*2 This is an index that shows the occurrence level of conductive substances in the
environment where the equipment is used.
In the case of pollution level 2, only non-conductive pollution occurs.
However, this is an environment where temporary conductivity can occur by accidental
condensation.
*3: The time from detection of ON or OFF to sending of a transmission
signal. This time + 2 transmission cycle times is the transmission
delay time.
*4: * The value on the input terminal is the value when all points between
IN and 0V (NPN) or between 24V and IN (PNP) are shorted.
When connecting a 3-wire sensor, add the total consumption current
of the sensor.
* The value on the output terminal is the value when all points are ON.
Add the total connected load consumption current.
* The value on the output terminal is the value when all points are ON.
Add the total connected load consumption current.
-BL296*B16F*4A20 11/11-
Printed in Japan 2016,2017 UMA-13221C-EN
Anywire Corporation
Headquarters :1 Babazusho, Nagaokakyo-shi, Kyoto 617-8550 JAPAN
:Contact by mailContact [email protected]
:Contact by website http://www.anywire.jp
[Address]

This manual suits for next models

5

Other Anywire Touch Terminal manuals

Anywire ASLINKAMP L-A1AW Series User manual

Anywire

Anywire ASLINKAMP L-A1AW Series User manual

Anywire AnyWireASLINK BL296PB-16F-4A-20 User manual

Anywire

Anywire AnyWireASLINK BL296PB-16F-4A-20 User manual

Anywire BL296 B-08F-4A-20 Series User manual

Anywire

Anywire BL296 B-08F-4A-20 Series User manual

Anywire ASLINK BL296 B-08F V50 Series User manual

Anywire

Anywire ASLINK BL296 B-08F V50 Series User manual

Anywire Bitty Series User manual

Anywire

Anywire Bitty Series User manual

Anywire ASLINK BL296SB-04F-4A-20 User manual

Anywire

Anywire ASLINK BL296SB-04F-4A-20 User manual

Anywire BL287SB-02F-CC20 User manual

Anywire

Anywire BL287SB-02F-CC20 User manual

Anywire B281-B-02U-CC20 Series User manual

Anywire

Anywire B281-B-02U-CC20 Series User manual

Popular Touch Terminal manuals by other brands

VeriFone E235 installation guide

VeriFone

VeriFone E235 installation guide

FiberHome HG6145F product manual

FiberHome

FiberHome HG6145F product manual

Ingenico AXIUM EX4000 user guide

Ingenico

Ingenico AXIUM EX4000 user guide

AT&T 7434D user guide

AT&T

AT&T 7434D user guide

RFL 9506 General description

RFL

RFL 9506 General description

SMA FP7900 user guide

SMA

SMA FP7900 user guide

Appostar GP-3460 user manual

Appostar

Appostar GP-3460 user manual

POSIFLEX XT-2614E user manual

POSIFLEX

POSIFLEX XT-2614E user manual

Keymantek K25 manual

Keymantek

Keymantek K25 manual

AXIOMTEK GOT810-316 user manual

AXIOMTEK

AXIOMTEK GOT810-316 user manual

PairGain PG-Flex FRC-753 4B manual

PairGain

PairGain PG-Flex FRC-753 4B manual

hazeltine 2000 operating manual

hazeltine

hazeltine 2000 operating manual

DLoG DLoG X 7 manual

DLoG

DLoG DLoG X 7 manual

Huawei EchoLife EG8240H5 quick start

Huawei

Huawei EchoLife EG8240H5 quick start

Casio V-REGI Series Reference manual

Casio

Casio V-REGI Series Reference manual

Datavan G-615S Quick installation guide

Datavan

Datavan G-615S Quick installation guide

Tysso POS-1000 Series user manual

Tysso

Tysso POS-1000 Series user manual

Casio IT-600 Series user guide

Casio

Casio IT-600 Series user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.