ARAG bravo 350 Series Installation and operating instructions

BRAVO 350 SERIES COMPUTER
MULTI-ROW SPRAYER
DIRECT CONNECTION
4673514XXX
4673515XXX
4673516XXX
4673517XXX
Software rel. 1.1.x
INSTALLATION, USE AND MAINTENANCE

2
• LEGEND OF SYMBOLS
=Generic danger
=Warning
This manual is an integral part of the equipment to which it refers and must accompany the equipment in case of sale or change of ownership. Keep it
for any future reference; ARAG reserves the right to modify product specifications and instructions at any moment and without notice.
LEGEND OF SYMBOLS

3
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
• Legend of symbols ................................................................. 2
• Manual foreword and use ...................................................... 4
• Manual use modes.................................................................. 4
• LIMITATIONS ........................................................................... 4
• Responsibility ......................................................................... 4
1 Risks and protections before assembly............................... 4
2 Intended use............................................................................ 4
3 Precautions ............................................................................. 4
4 Package content ..................................................................... 5
5 System recommended composition ..................................... 5
5.1 Monitor position.................................................................6
5.2 Bracket fixing ....................................................................6
5.3 Control unit position ..........................................................6
5.4 Hydraulic unit positioning..................................................6
6 Wiring connections................................................................. 7
6.1 General precautions for a correct harness position ..........7
6.2 Power supply connection..................................................7
6.3 Connection of multicore connector ...................................8
6.4 Control unit valve connection............................................8
6.5 Hydraulic valve connection ...............................................9
6.6 Connection of sensors and available functions...............10
6.7 Power supply connection................................................10
7 Setting.................................................................................... 11
7.1 Tests and checks before setting......................................11
7.2 Computer switching on/off ..............................................11
7.3 Use of keys for setting ....................................................12
8 Advanced setup .................................................................... 14
8.1 Sections configuration.....................................................16
8.2 Coverage ........................................................................16
8.3 Valves configuration........................................................17
8.4 Flowmeter .......................................................................18
8.5 Pressure sensor..............................................................18
8.6 Flowrate calculation sensor ............................................18
8.7 Tank level........................................................................19
8.7.1 Tank level - Manual Mode ............................................... 19
8.7.2 Tank level - Level sensor mode....................................... 19
8.7.3 Tank level - Filling flowmeter mode ................................. 20
8.8 Revolutions counter ........................................................21
8.9 Foam marker...................................................................21
8.10 External device ...............................................................21
8.11 Access level....................................................................22
8.12 Setup check after Advanced setup end ..........................23
9 User setting ........................................................................... 24
9.1 Job selection...................................................................26
9.2 Current Job data .............................................................26
9.3 Jobs setup.......................................................................26
9.4 Booms setup...................................................................27
9.5 Nozzles setup .................................................................27
9.6 Working parameters........................................................28
9.6.1 Task Controller TC........................................................... 28
9.6.2 Nozzles wear check......................................................... 28
9.6.3 Min. spraying speed ........................................................ 28
9.6.4 Regulation lock type ........................................................ 28
9.7 Rate controller.................................................................28
9.8 Tank ................................................................................29
9.9 Speed..............................................................................30
9.9.1 Source - Wheel sensor.................................................... 31
9.9.2 Source - GPS .................................................................. 31
9.10 Flowrate correction factor ...............................................32
9.11 Press. sensor zero value ................................................32
9.12 Totalizers.........................................................................32
9.13 Test .................................................................................33
9.13.1 Speed simulation............................................................. 33
9.13.2 Signal test........................................................................ 33
9.13.3 Battery voltage................................................................. 33
9.13.4 Display............................................................................. 33
9.13.5 Keyboard & Switches ...................................................... 34
9.13.6 GPS data......................................................................... 34
9.13.7 Monitor hardware version - Monitor software version...... 34
9.14 User preferences ............................................................35
9.14.1 Sound alarm .................................................................... 35
9.14.2 Sound keyboard .............................................................. 35
9.14.3 Date & Time..................................................................... 35
9.14.4 Display contrast............................................................... 35
9.14.5 Filling calculation ............................................................. 35
9.14.6 Data display..................................................................... 35
9.15 Data logger .....................................................................36
9.16 Ext. device log.................................................................36
9.17 Load/save setup..............................................................37
9.17.1 Load configuration from USB .......................................... 37
9.17.2 Save configuration to USB .............................................. 37
9.17.3 Restore factory ................................................................ 37
10 Use ......................................................................................... 38
10.1 Controls on computer......................................................38
10.2 Control, selection or modification keys (1 - 2 Fig. 78).....38
10.3 Switches to operate valves in the control unit (3 Fig. 78)38
10.4 Switches to use the hydraulic functions (4 Fig. 78).........38
10.5 Display ............................................................................39
10.6 Treatment preliminary settings........................................39
10.7 Application rate regulation ..............................................40
10.7.1 Automatic operation......................................................... 40
10.7.2 Manual operation (DEFAULT) ......................................... 40
10.7.3 Automatic closure of main and section valves
(via Bravo 400S / Delta 80) ............................................. 40
11 Maintenance / diagnostics / repairs .................................... 41
11.1 Cleaning rules.................................................................41
11.2 Operation errors..............................................................41
11.3 Troubleshooting ..............................................................42
12 Accessories........................................................................... 42
12.1 Pendrive..........................................................................42
13 Technical data ....................................................................... 43
13.1 Computer technical data ................................................43
13.2 Pin-out of Bravo 350 .......................................................43
14 Guarantee terms ................................................................... 45
15 End-of-life disposal .............................................................. 45
CONTENTS

4
• MANUAL FOREWORD AND USE
This manual provides instructions to assemble, connect and set the computers of the BRAVO 350 family.
Any other information is provided in specific sheets to be used exclusively by the installer, containing specific information of each computer model.
• MANUAL USE MODES
The section of this manual dedicated to the installation contains information for installers. For this reason we have used technical terms
without providing explanations which would be necessary for end users only.
THE INSTALLATION MUST BE CARRIED OUT BY AUTHORIZED AND SKILLED PERSONNEL ONLY. THE MANUFACTURER IS
NOT RESPONSIBLE FOR ANY OPERATION SPECIFIED IN THIS MANUAL CARRIED OUT BY UNAUTHORIZED OR UNSKILLED
PERSONNEL.
• LIMITATIONS
The descriptions of the assembly phases refer to a "general" computer, so specific models will not be mentioned, unless a certain installation procedure
concerns exclusively one computer type.
• RESPONSIBILITY
The installer must carry out workmanlike installations and ensure to the end user the perfect operation of the whole system both with ARAG
components only and other brands' components.
ARAG always recommends using its components to install control systems.
The installer will be held responsible for any malfunction if he decides to use other brands' components even without actually changing the system
parts or harness.
The compatibility check with components and accessories of other manufacturers shall be carried out by the installer.
If the computer or the ARAG components installed together with other brands' components get damaged because of what stated above, no direct
or indirect warranty will be provided.
1 RISKS AND PROTECTIONS BEFORE ASSEMBLY
All installation works must be done with battery disconnected, using suitable tools and any individual protection equipment
deemed necessary.
Use ONLY clean water for treatment tests and simulations: using chemicals during simulated treatment runs can seriously
injure persons in the vicinity.
2 INTENDED USE
The device you have purchased is a computer which, when connected to a valve or suitable control unit, makes it possible to control all phases of
treatment in agricultural applications directly from the cabin of the farming machine it is installed in.
This device is designed to work on agricultural machinery for spraying and crop spraying applications.
The equipment is designed and manufactured in compliance with UNI EN ISO 14982 standard (Forestry and farming machines -
Electromagnetic compatibility - Test methods and acceptance criteria), harmonized with EMC - 2014/30/EU Directive.
3 PRECAUTIONS
• Do not aim water jets at the equipment.
• Do not use solvents or fuel to clean the case outer surface.
• Do not clean equipment with direct water jets.
• Comply with the specified power voltage (12 VDC).
• In case of voltaic arc welding, remove connectors from BRAVO 350 and disconnect the power cables.
• Only use ARAG genuine spare parts and accessories.
• Bravo 350 can control hydraulic valves to open/close the multi-row sprayer booms.
THE COMPUTER DOES NOT FEATURE EMERGENCY STOP DEVICES: THE MACHINE MANUFACTURER
MUST PROVIDE ALL NECESSARY SAFETY DEVICES FOR THE HYDRAULIC VALVE CONTROL.
IT IS THE MANUFACTURER’S RESPONSIBILITY TO ENSURE THAT THE MACHINE IS SAFE TO USE,
ALSO BY MEANS OF ACOUSTIC AND/OR VISUAL SIGNALING DEVICES.
FOREWORD

5
INSTALLATION
4 PACKAGE CONTENT
1
7
2
3
4a
5a*
6
45*
1
2
3 Power supply connector
4 Connection cable for:
4a Seals for control unit valve connectors
5*Hydraulic unit harness
5a* Seals for hydraulic unit valve connectors
6 Safety covers for control unit valve connectors
(no. 3 for 4-way version ONLY)
(no. 2 for 5-way version ONLY)
(no. 1 for 6-way version ONLY)
7 Fixing kit
* ONLY for versions with hydraulic functions
Sensors, control units and accessories must be ordered separately
(Ref. ARAG general catalog).
5 SYSTEM RECOMMENDED COMPOSITION
T
S
R
M
X
6 m
3 m
12 m
3
2
2
G
F
P
4
5
6
1
Legend:
1 Bravo 350 with direct connection
2 Power cable for Bravo 350
3Connection cable for:
4Control unit (GPcontrol valve)
5Connection cable for hydraulic valves (if available on the system)
6Hydraulic control unit (if available on the system, not supplied with the kit to be purchased separately)
Sensors:
X RPM sensor
T Filling flowmeter or Level sensor
S Speed sensor
R Foam marker
M Pressure sensor
F Flowmeter

6
INSTALLATION
5.1 Monitor position
Bravo 350 must be placed in the control cabin of the farming machine. Observe the following precautions:
- Do NOT install the monitor in areas where it would be subjected to excessive vibrations or shocks, to prevent any damage or
accidental use of the control keys;
- Install the device in a visible position within easy reach by hand; bear in mind that the monitor should not obstruct the
operator’s freedom of movement or block his view.
Consider all necessary connections of the computer (chap. 5), the cable length, and make sure there is enough space for
connectors and cables.
An identification symbol is located next to each connector to indicate its function. For any reference to the system configuration
read chap. 5.
268 86
242
186.4
Ø 6.5
40
222
2
1
3
4 5*
No. Monitor connection points
1Monitor power supply
2Auxiliary connections
3USB
4Control units and sensors
5* Hydraulic unit
* ONLY for versions with hydraulic functions
5.2 Bracket fixing
The monitor must be mounted after
having fixed the bracket at the desired
location (the previous paragraph
shows the bracket drilling template).
The bracket must be slid out of the
monitor seat (A, Fig. 4) and fixed using
the supplied screws (B).
Make sure the bracket is securely
mounted, fit the monitor on it, and push
it until it locks in place (C).
5.3 Control unit position
The control unit must be fixed with the special brackets supplied and fitted to the unit, positioning it as shown in the manual provided with the assembly.
MAKE SURE TO FOLLOW ALL THE SAFETY INSTRUCTIONS GIVEN IN THE CONTROL UNIT’S MANUAL.
5.4 Hydraulic unit positioning
The hydraulic unit shall be secured to the machine, making sure it is well protected against the elements and the fluid sprayed by the machine.
ARAG IS NOT LIABLE FOR ANY DAMAGE RESULTING FROM INSTALLATION BY UNSKILLED
PERSONNEL. ANY SYSTEM DAMAGE CAUSED BY A WRONG INSTALLATION AND/OR CONNECTION AUTOMATICALLY
VOIDS THE WARRANTY.
WARNING! DO NOT CONNECT HYDRAULIC UNITS OTHER THAN THE SPECIFIED ONES (SEE ARAG GENERAL CATALOG).
ARAG SHALL NOT BE LIABLE FOR DAMAGE TO THE PRODUCT, MALFUNCTIONS AND RISKS OF ANY KIND
CAUSED BY THEM WHEN THE MODULE IS CONNECTED TO NON-ORIGINAL UNITS OR UNITS NOT SUPPLIED BY ARAG.

7
INSTALLATION
6 WIRING CONNECTIONS
CAUTION:
To avoid short circuits, do not connect the power cables to battery before the installation is completed.
Before powering up the computer, make sure the tractor battery voltage is as specified (12 VDC).
• Use only the cables provided with the ARAG computers.
• Take care not to break, pull, tear or cut the cables.
• Use of unsuitable cables not provided by ARAG automatically voids the warranty.
• ARAG is not liable for any damage to the equipment, persons or animals caused by failure to observe the above instructions.
Use ONLY the cables and accessories indicated in the catalog, having technical features suitable for the use to be made
of them.
6.1 General precautions for a correct harness position
• Securing the cables:
- secure the harness so that it does not interfere
with moving parts;
- route the harnesses so that they cannot be
damaged or broken by machine movements or
twisting.
• Routing the cables to protect against water
infiltrations:
- the cable branches must ALWAYS be facing
down (Fig. 5).
• Fitting the cables to the connection points:
- do not force the connectors by pushing too hard
or bending them: the contacts may be damaged
and computer operation may be compromised.
6.2 Power supply connection
Connect the multicore connector to the monitor,
check it is correctly connected, and turn the ring
nut clockwise until connector blocking.

8
INSTALLATION
6.3 Connection of multicore connector
Connect the multicore connector to the monitor (connections 4and 5, “Fig. 3" on page 6); check it is correctly connected, and turn the ring nut
clockwise until connector blocking.
6.4 Control unit valve connection
• Use ARAG valves: use of unsuitable valves not provided by ARAG automatically voids the warranty.
ARAG is not liable for damage to the equipment, people, animals or property caused by failure to observe the above instructions.
• All valve connectors must be provided with seals before being connected (Fig. 9).
• Make sure the seals are correctly fitted to avoid water infiltration when using the control unit.
Section
2
Section
3
Section
4
Section
1
Valve 1 Valve 3Valve 2 Valve 4
Section
5
Valve 5
Connector 1 shall control the valve, which in turn is connected to the boom section 1, and so on with the other valves.
Connect “connector 1” to “valve 1”, and then the other connectors with increasing numbers from left to right: the boom section 1 is the furthest
from the machine on the left, looking at the machine from the rear side (Fig. 9).
Fix the connectors to the relevant valves according to
the indicated initials.
• Remove the protective cap (1) from the valve.
• Place the seal (2) onto the connector (3), and push
the connector fully on (4): be careful not to bend the
contacts upon insertion on the valve.
• Tighten the screw (5) fully home.
• CONTROL UNIT
LABEL CONNECTION
GMain valve
PControl valve
• SECTION VALVE UNIT
LABEL CONNECTION
1Section valve no.1
2Section valve no.2
3Section valve no.3
4Section valve no.4
5Section valve no.5
6Section valve no.6
In case there are more monitor switches than section valves, connect the cables as indicated in the table below.
WITH SWITCHES 5 AND 7 WITH SWITCHES 4 AND 6
No. of section valves Switches to be used
Cables to be
connected
to the valves
No. of section valves Switches to be used
Cables to be
connected
to the valves
22 - 4 1 - 2 21 - 2 1 - 2
32 - 3 - 4 1 - 2 - 3 31 - 2 - 3 1 - 2 - 3
41 - 2 - 4 - 5 1 - 2 - 3 - 4 41 - 2 - 3 - 4 1 - 2 - 3 - 4
51 - 2 - 3 - 4 - 5 1 - 2 - 3 - 4 - 5 51 - 2 - 3 - 4 - 5 1 - 2 - 3 - 4 - 5
61 - 2 - 3 - 4 - 5 - 6 1 - 2 - 3 - 4 - 5 - 6 61 - 2 - 3 - 4 - 5 - 6 1 - 2 - 3 - 4 - 5 - 6
71 - 2 - 3 - 4 - 5 - 6 - 7 1 - 2 - 3 - 4 - 5 - 6 - 7

9
INSTALLATION
6.5 Hydraulic valve connection
Bravo 350 can control up to 7 hydraulic functions through double action valves.
Fix the connectors to the relevant valves according to the initials indicated in your assembly general diagram (“5
System recommended composition" on page 5).
• Position seal (1) onto connector (2), then connect the latter pressing it fully home (3):
during this operation, take special care not to bend valve electric contacts.
• Insert screw inside connector, and screw it (4) until it is tightened.
The function of each switch on the hydraulic function control panel is described below.
• Connect the connector marked with "DD" to the pilot valve, and then the other connectors, as specified on the table:
CONTROL MOVEMENT CONNECTOR
Section movement
1 - 2 - 3 - 4
Opening 1 ÷ 4 A
Closing 1 ÷ 4 C
Boom height
Opening AA
Closing AC
Boom lock
Opening BA
Closing BC
Boom leveling
Opening CA
Closing CC

10
INSTALLATION
6.6 Connection of sensors and available functions
Harness cables are marked with a symbol denoting their functions: please see the table for correct harness connection.
Use ARAG sensors: use of unsuitable sensors not provided by ARAG automatically voids the warranty.
ARAG is not liable for damage to the equipment, persons or animals caused by failure to observe the above instructions.
ARAG sensors feature the Tyco Superseal®
connector. Insert connector fully home, until
hearing a click of the retaining tab.
The single products are supplied with the sensor
connecting instructions.
LABEL CONNECTION
FFlowmeter
SSpeed sensor
MPressure sensor
TFilling flowmeter or Level sensor
RFoam marker
XRPM sensor
6.7 Power supply connection
The package includes the power connector (component 3, Fig. 1) to be connected to the farming machine battery;
Fig. 15 shows the drilling template of the power connector.
Connect the power connector to the battery wires using two 6-mm faston connectors, as indicated in Fig. 13 and Fig. 14.
Use the cable provided with the package (component 2, Fig. 1) to connect the computer to the power supply.
CAUTION:
To avoid short circuits, do not connect the power cables to battery before the installation is completed.
Before powering up the computer and control unit, make sure the battery voltage is as specified (12 Vdc).
BRAVO 350 is supplied directly by the farming machine battery (12 Vdc): ALWAYS switch on the computer through the monitor, and then
remember to switch it off using the specific key on the control panel.
If BRAVO 350 remains on for a long time with machine off, the tractor battery could run flat: in case of prolonged breaks of the
machine with engine off, make sure the computer is off, too.
The power source must be connected as indicated in Fig. 16: the computer must be directly connected to the farming machine battery. DO
NOT connect the computer to key-operated switch (15/54).
Bravo 350 with direct connection: 10 A
CAUTION:
• The power circuit shall ALWAYS be protected by a fuse like the
ones for automotive applications: 10 Amperes.
• All cables connected to the battery shall have a minimum
cross-section of 2.5 sq. mm.
To avoid short-circuits, connect the power cable connector only
after completing installation.
• Use cables with suitable terminals ensuring correct connection
of all wires.

11
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
7 SETTING
7.1 Tests and checks before setting
Before computer setting, check:
• that all components are correctly installed (control unit and sensors);
• the correct connection to the power source;
• the component connection (main control unit and sensors).
Failure to correctly connect system components or to use specified components might damage the device or its components.
7.2 Computer switching on/off
• Ordinary switching on
28.00m
Software version Job screen
Keep key ESC).
• Switching on to activate the advanced setup
+Advanced Setup
>
Language : ...
: Metric
: ...
: ...
: ...
: ...
Unit of measurement
Flowmeter
Sections configuration
Coverage
Valves configuration
Contemporaneously press the key sequence until switching on the Bravo. Release key ESC keeping pressed the arrow keys until the display
shows the menu Advanced setup ().
• Switching off
WAIT: saving data
Keep key ESC pressed until the display shows the message WAIT: saving data.
Release the key and wait for the saving process to complete (); after a few seconds the computer turns off.
During switching off do NOT press any other key and do NOT disconnect the power supply until BRAVO 350 turns off.
WARNING: ALWAYS use the special key to switch off the computer; otherwise ALL data concerning the spraying and the
programming will be lost.
SETTING

12
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
7.3 Use of keys for setting
Advanced Setup
>
Language : ...
: Metric
: ...
: ...
: ...
: ...
Unit of measurement
Flowmeter
Sections configuration
Coverage
>
Valves configuration
1
2a
2b
1 Use cursor
>
to select the menu you want to
access: move it using the "arrow" keys until
selecting the option you are looking for (Fig.
).
2 Confirm the selection with OK.
DATA SELECTION
3a 4a
Language
>
English
Italiano
2a, ).
3a Press the arrow keys one after the other to select another item; the display will show the selected item.
4a Confirm with OK.
Item quick scrolling: keep one of the arrow keys pressed.
Exit without confirming the change: press ESC.
ACCESS TO A SUBMENU
3b 4b
Advanced Setup
>
Language : ...
: Metric
: ...
Unit of measurement
Ultrasonic configuration
...” (2b, ).
3b Press the arrow keys in succession to move across the menu items. The cursor
>
will move on the selected one.
4b Press OK to access the submenu.
Item quick scrolling: keep one of the arrow keys pressed.
Exit without confirming the change: press ESC.
SETTING

13
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
SETTING
ENABLE / DISABLE
Constant
Disabled
(F4 to enable)
5
Some submenu items require enabling before configuration.
Within the submenu, press the F4 key when the symbol is displayed.
Depending on the current status (enabled/disabled), pressing the key allows switching between the two statuses.
5Press OK to confirm.
Exit without confirming the change: press ESC.
ENTERING A NUMERICAL VALUE
76 8
Constant
RANGE: 00001 <=> 10000 pls/l
00600
6Press the arrow keys to move through numerical value digits.
7Press the arrow keys in succession to change the value.
To reset the data press CRL.
8Press OK to confirm the data.
Quick increase/decrease of the value: keep one of the arrow keys pressed.
Exit without confirming the change: press ESC.

14
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
8 ADVANCED SETUP
This operation must be done once only, upon installation.
ACCESS TO ADVANCED SETUP (WITH COMPUTER OFF)
• Release the key ESC by keeping the arrow keys pressed until the menu is displayed
+Advanced Setup
>
Language : ...
: MetricUnit of measurement
For a correct use of the keys during setting, refer to Par.
7.3.
Menu Default Min Max Other values that can be set / Notes
Language English --- ---
Italiano - English - Español - Português - Français -
ニホン
Unit of measurement Metric (l/h, km/h, bar) --- --- US (GPA, mil/h, PSI)
Par. 8.1 Sections configuration
Sections number
Par. 8.2 Coverage
Section 1 ÷ Section 7 --- --- ---
Section
Par. 8.3 Valves configuration
Master --- ---
Pressure regulator --- ---
Section --- ---
Automatic switch-off No (P mode) --- --- Yes (M mode)
Par. 8.4 Flowmeter
Type --- --- See “Tab. A" on page
Min. flowrate alarm
Disabled
Max. flowrate alarm
Disabled
Constant
---
Par. 8.5 Pressure sensor
Type Disabled --- ---
Maximum pressure ---
Item active only if a sensor is selected
Par. 8.6 Flowrate calculation sensor Flowmeter --- --- Pressure - Both
Par. 8.7 Tank level
Par. 8.7.1 Mode --- --- --- SELECTED MODE: MANUAL
Capacity
---
Minimum level alarm
---
Par. 8.7.2 Mode --- --- --- SELECTED MODE: LEVEL SENSOR
Capacity
--- --- ---
Minimum level alarm
---
Calibration ... --- --- See
page
Zero calibration --- --- ---
Load/Save calibr. ... --- --- ---
Recovered liq. count Disabled --- --- Enabled
Par. 8.7.3 Mode --- --- --- SELECTED MODE: FILLING FLOWMETER
Capacity
---
Minimum level alarm
---
Type --- --- See “Tab. C" on page
Constant
---
Minimum flowrate
--- --- See “Tab. C" on page
Maximum flowrate
--- --- See “Tab. C" on page
ADVANCED SETUP

15
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
ADVANCED SETUP
Par. 8.8 Revolutions counter
Constant Disabled ---
Minimum speed alarm Disabled Items only visible if the constant is activated
Maximum speed alarm Disabled
Par. 8.9 Foam Marker Manual --- --- Semi-autom. - Automatic
Par. 8.10 External device None --- ---
Par. 8.11 Access level Technician --- --- Operator - Manager - ARAGTech

16
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
8.1 Sections configuration
Sections configuration
>
Sections number : 7
8.2 Coverage
Set the row coverage for each boom section.
Coverage (7.00 Rows)
Section 6
Section 7
: 1.00 Rows
: 1.00 Rows
: 1.00 RowsSection 1
: 1.00 RowsSection 2
: 1.00 Rows
: 1.00 Rows
: 1.00 Rows
Section 3
Section 4
Section 5
Fig. 24
Set the width of each section:
Bravo 350 adds up the entered values and shows the total width.
Application systems:
Section Valve
1
Section Valve
2
Coverage (2.00 Rows)
: 1.00 RowsSection 1
: 1.00 RowsSection 2
- Section valve 1 sprays on one complete row (1.00 Rows).
- Section valve 2 sprays on one complete row (1.00 Rows).
Section Valve
1
Section Valve
2
Section Valve
3
Coverage (1.50 Rows)
: 0.50 RowsSection 1
: 1.00 Rows
: 0.50 Rows
Section 2
Section 3
- Section valve 1 sprays on one complete row (1.00 Rows).
- Section valve 2 sprays only on one row side (0.50
Rows).
ADVANCED SETUP

17
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
ADVANCED SETUP
8.3 Valves configuration
Set the type of valves installed on the system and the relevant data.
>
Master: indicate the type of installed main control valve.
2 ways: drain valve
3 ways: main valve
None
>
Pressure regulator: indicate the type of installed control valve.
2 ways 3 ways
>
Section: indicate the type of installed motorized section valves.
2 ways: valves without metered by-passes
3 ways: valves with metered by-passes
>
Automatic switch-off
Indicate the section valve operation mode. especially if the section
automatic switch-off is active when the main control valve is closed.
Yes (M mode)
No (P mode)
It is compulsory to set the M mode (option Yes) when None main
valve is present in the system.
• "M" operation mode (option Yes):
The section valves are closed or opened by acting on the main switch, provided that the switch relating to section valves is properly positioned:
- if the switches of sections are set to OFF (lever down), sections will not be controlled by acting on the main switch.
- If one or more section valve switches are set to ON (lever up), opening or closing the main switch opens or closes the section valves as well.
• "P" operation mode (option No):
The section valves are controlled independently.
Main switch control functions do not affect section valve opening or closing.

18
8.4 Flowmeter
Set the installed flowmeter and the relevant data. Tab. A contains the values that will be automatically set by selecting the flowmeter code.
Nevertheless these data can be modified.
>
Type: indicate the type of installed flowmeter (Tab. A).
>
Min. flowrate alarm
>
Max. flowrate alarm
The flowrate alarms (minimum or maximum) activate when, during the spraying, the flowmeter rate does not respect the set limits.
For the procedure to be followed in case of alarms, please refer to Par. 11.2 Operation errors.
>
Constant: indicate the constant of the installed flowmeter.
ORION FLOWMETERS
TYPE
METRIC UNITS OF MEASUREMENT - METR.
l/100 m US UNIT OF MEASUREMENT
The default values can be
modified.
Constant
(pls/l)
Min. flowrate
(l/min)
Max. flowrate
(l/min)
Constant
(pls/gal)
GPM min.
flowrate
GPM max.
flowrate
Orion 4621xA0xxxx
6000 0.5 10.0 22710 0.13 2.64
Orion 4621xA1xxxx
3000 1.0 20.0 11355 0.26 5.28
Orion 4621xA2xxxx
1200 2.5 50.0 4542 0.66 13.21
Orion 4621xA3xxxx
600 5.0 100.0 2271 1.32 26.42
Orion 462xxA4xxxx
300 10.0 200.0 1136 2.64 52.83
Orion 4622xA5xxxx
150 20.0 400.0 568 5.28 105.67
Orion 4622xA6xxxx
100 30.0 600.0 378 7.93 158.50
Orion 4622xA7xxxx
75 40.0 800.0 284 10.57 211.34
WOLF FLOWMETERS
TYPE
METRIC UNITS OF MEASUREMENT - METR.
l/100 m US UNIT OF MEASUREMENT
The default values can be
modified.
Constant
(pls/l)
Min. flowrate
(l/min)
Max. flowrate
(l/min)
Constant
(pls/gal)
GPM min.
flowrate
GPM max.
flowrate
Wolf 462x2xxx 1015 2.5 50.0 3842 0.66 13.21
Wolf 462x3xxx 625 5.0 100.0 2366 1.32 26.42
Wolf 462x4xxx 250 10.0 200.0 946 2.64 52.83
Wolf 462x5xxx 132 20.0 400.0 500 5.28 105.67
Wolf 462x7xxx 60 40.0 800.0 227 10.57 211.34
Tab. A Other... 625 10.0 200.0 2366 2.64 52.83
8.5 Pressure sensor
The pressure sensor is used to detect the pressure in the system and, depending on the case, for various other functions.
• Flowmeter enabled (Par. 8.6 Flowrate calculation sensor > Both):
flowmeter limits. When the flowmeter operates outside the limits the measured pressure is used to calculate the spray rate.
• Flowmeter disabled (Par. 8.6 Flowrate calculation sensor > Pressure):the pressure sensor is always used to calculate the
application rate.
Set the type of installed pressure sensor and the relevant full scale.
>
Type: indicate the type of installed sensor (available models indicated in Tab. B).
>
Maximum pressure
Indicate the full scale of the pressure sensor installed on the system.
When the option Disabled (Default) is active, the item Maximum pressure is no longer displayed.
The table below indicates the values that are automatically set selecting the sensor code:
ARAG PRESSURE SENSOR
TYPE Max pressure
The default values can
NOT be modified.
bar PSI
ARAG 466113.200 20.0 290
ARAG 466113.500 50.0 725
Tab. B Other... 50.0 725
8.6 Flowrate calculation sensor
Flowrate calculation sensor
>
Flowmeter
Set the type of sensor to be used to calculate the flowrate:
>
Flowmeter
The Flowmeter is the only sensor used to read the flowrate.
>
Pressure
The Pressure sensor is the only sensor used to read the flowrate.
Set nozzles par.
>
Both
Within the working limits, the computer uses the flowmeter, otherwise it uses the
pressure sensor (ONLY if properly configured).
ADVANCED SETUP

19
8.7 Tank level
First of all configure the submenu Mode and the selected option data.
The tank filling will be managed in different ways according to the preset mode.
Possible options:
>
Manual:
>
Level Sensor:
>
Filling flowmeter:
8.7.1 Tank level - Manual Mode
Tank level
>
Mode
: Manual
: 2000 l
Capacity
: 150 l
Minimum level alarm
>
Capacity: indicate the rated capacity.
>
Minimum level alarm: indicate the range value.
The tank alarm activates when during the spraying the tank level falls below the
set value ().
8.7.2 Tank level - Level sensor mode
The level sensor installed in the system allows displaying the tank level in real time ().
This mode operates correctly ONLY if the level sensor has been calibrated, or if the calibration of a similar tank has been loaded
from USB pendrive.
Tank level
>
Mode : Level Sensor
: 1000 l
Capacity
: 150 l
Minimum level alarm
: ...
: 4,000 mA
: ...
: Enabled
Calibration
Zero calibration
Load/Save calibr.
Recovered liq. count
>
Capacity: the computer displays the tank capacity calculated after the
calibration.
>
Minimum level alarm: indicate the range value.
The tank alarm activates when during the spraying the tank level falls below the
set value ().
>
Calibration: enters the calibration procedure of the level sensor.
The level sensor calibration is ONLY possible if the system is provided with a flowmeter.
Before starting the procedure carry out the following operations:
1 9 4
1Make sure the main switch is in position OFF
(Fig. 31).
2Fill the tank with clean water WITHOUT ADDING
CHEMICAL SUBSTANCES. The tank must be full.
Visually check the reached level.
3 Man.Reg.). Otherwise activate it by pressing AUTO (Par.
).
4 ) pressed upwards, being careful not to exceed the maximum flowrate of the
selected flowmeter.
5 Switch the computer off and on again in advanced setup mode ().
Rated tank capacity
Min: 1 l - Max:
10000 l
l
02000
6 Enter the Tank level menu, activate the Level sensor mode()
and select the Calibration item.
): enter the
value.
Calibration
>
Sprayed quantity : 13 l
: 20 l/min
Flowrate
: 7,000 mA
Measured current
: 001/200
Measured points
Press OK to start calibration
7 Immediately afterwards the computer passes to the calibration start screen
(): the message Press OK to start calibration blinks on the
display.
8 Press OK: calibration starts.
The message Enable spraying command! blinks on the display.
9 Start the spraying system: open, in succession, all section valves and the main
control (, switches in position ON).
10 The display will show in real time the quantity of sprayed water and the calibration status. The message CALIBRATION: [OK] to save/
[ESC] to exit blinks on the display.
In order to close the calibration curve the value of the level sensor must be between 3.0 mA and 5mA; press OK to manually stop the
calibration (and save it) or press ESC to stop without saving it.
Calibration
>
Sprayed quantity : 1990 l
: 0 l/min
Flowrate
: 4,000 mA
Measured current
: 180/200
Measured points
COMPLETED: [OK] to save and quit
11 If the calibration has not been manually ended, when the flowrate value
reaches zero (
finishes the procedure and displays the message COMPLETED: OK to save
and quit.
Press OK: the calibration is complete.
After having completed the calibration and checked the sensor correct operation, we recommend to memorize the calibration on
USB pendrive. CONTINUES
ADVANCED SETUP

20
Par. 7.3
Fast data reset Scroll menu items or Increase/
decrease data
Confirm menu access or
data change
Exit menu or data
change
>
Zero calibration: it accesses the "zero" calibration of the level sensor.
The level sensor zero must be calibrated when:
- the presence of fluid inside the tank is displayed, even when it is empty.
- a calibration curve already made with the same tank by means of another Arag computer is loaded. The tank must be empty.
Press OK to reset the sensor residual signal.
>
Load/Save calibr.: the level sensor calibration can be loaded or saved on USB pendrive to reconfigure the device if necessary, solve
After having completed the calibration and checked the sensor correct operation, we recommend to memorize the calibration on USB
pendrive.
Before carrying out any operation, insert the USB pendrive in the relevant slot.
>
Load tank profile from USB: select this option and press OK.
The confirmation message Successfully completed! (TANK.TKL) is displayed once the configuration process is completed. Press
ESC.
>
Save tank profile to USB: select this option and press OK.
The confirmation message Successfully completed! (TANK.TKL) is displayed once the saving process is completed. Press ESC.
>
Recovered liq. count:
During spraying it is possible to recover part of the sprayed product to reduce costs, pollute less and evaluate the quality of the spraying.
This menu is only visible when the level sensor is active.
This function is disabled by default, but enabling it will enable the computer to count the liquid recovered during spraying, which will be the
difference between the sprayed fluid and the fluid applied to the plant.
.
8.7.3 Tank level - Filling flowmeter mode
Tank level
>
Mode : Filling flowmeter
: 2000 l
Capacity
: 150 l
Minimum level alarm
: Orion 462XXA4XXXX
: 300 pls/l
: 10.0 l/min
Type
Constant
Minimum flowrate
The filling flowmeter installed in the system allows displaying the tank filling data in real
time.
>
Capacity: indicate the rated capacity.
>
Minimum level alarm: indicate the range value.
>
Type: indicate the filling flowmeter installed and the relevant data.
Tab. C contains the values that will be automatically set by selecting the flowmeter code.
Nevertheless the constant can be modified.
>
Constant: indicate the constant of the installed filling flowmeter.
ORION FLOWMETERS
TYPE
METRIC UNITS OF MEASUREMENT - METR.
l/100 m US UNIT OF MEASUREMENT
The default values can be
modified.
Constant
(pls/l)
Min. flowrate
(l/min)
Max. flowrate
(l/min)
Constant
(pls/gal)
GPM min.
flowrate
GPM max.
flowrate
Orion 462xxA4xxxx
300 10.0 200.0 1136 2.64 52.83
Orion 4622xA5xxxx
150 20.0 400.0 568 5.28 105.67
Orion 4622xA6xxxx
100 30.0 600.0 378 7.93 158.50
Orion 4622xA7xxxx
75 40.0 800.0 284 10.57 211.34
WOLF FLOWMETERS
TYPE
METRIC UNITS OF MEASUREMENT - METR.
l/100 m US UNIT OF MEASUREMENT
The default values can be
modified.
Constant
(pls/l)
Min. flowrate
(l/min)
Max. flowrate
(l/min)
Constant
(pls/gal)
GPM min.
flowrate
GPM max.
flowrate
Wolf 462x4xxx
250 10.0 200.0 946 2.64 52.83
Wolf 462x5xxx
132 20.0 400.0 500 5.28 105.67
Wolf 462x7xxx
60 40.0 800.0 227 10.57 211.34
Other... 625 10.0 200.0 2366 2.64 52.83
Tab. C
CONTINUES
ADVANCED SETUP
Other manuals for bravo 350 Series
1
Table of contents
Popular Control System manuals by other brands

Spraying Systems
Spraying Systems TeeJet 845 user manual

HIK VISION
HIK VISION DS-K3B411SX Series quick start guide

Aqua Control
Aqua Control SL3 Deluxe Wi-Fi manual

sky vision
sky vision Linx 300 Preinstallation manual

ImmersionRC
ImmersionRC EzUHF Series Overview & Operating Instructions

HIK VISION
HIK VISION DS-K3B220X Series user manual