+ +1 sec: The alarm output function disable or enable select (when
power re-setting, the default setting is enable)
1-4-5 Soft start (Heater dehumidify) function
To avoid the humidity make the heater burn out. The soft start function could
output a lower current to make dehumidify action when turn on the power.
Soft start condition:
The soft start percentage ( ) and time ( ). After power turn on, ifSV>
PV;PV<120°C,manual and PID tuning function are disable, the soft start
would be executed. Set to zero for disable soft start function.
Soft start interrupt:
+ 1 sec
1-4-6 PID auto tuning function
For get the optimal PID value in some system, it is possible to execute "PID
auto tuning" function when first use or heater system changed.
After finished auto tuning, the optimal PID would be save into the instrument
Start PID auto tuning function:
(1)PV must lowerthan120°C or 180°F
(2)SV must higher than PV for 80°C or 100°F
(3)Set parameter into
PS:During PID auto tuning execution, the decimal point of PV would flash.
After instrument get the optimal PID, the decimal point turn off and
instrument recovery to auto temperature control.