Model: 2852-PCD User Manual Rev: 2.1
6
2.0 INSTALLATION
NOTE: If any damage to the instrument is found, please notify an Arjay Engineering
representative as soon as possible prior to installation.
2.1 Controller Installation
Choose the mounting location in accordance with good instrument practice. Extremes of ambient
temperature and vibration should be avoided (see specifications and installation drawing).
The 2850 controller may be mounted up to one kilometer from the PMC card using a minimum 18
gauge, 2-wire SHIELDED cable.
Check the polarity of the + and - wiring between the controller and the PMC prior to powering on
the unit; + to + and - to - to avoid damage. Shield of cable should be connected to secondary
ground terminal marked as . Incoming Earth ground should be connected to primary ground
terminal marked on sub plate.
Important Note: The controller is factory set in a Failsafe mode. This means that the relays
are in an energized state during normal operation. The N.O. relay contact will be held closed and
the N.C. relay contact will be held open during a normal condition. This will allow the relay to return
to its non-energized (shelf) state during an alarm, fault or power failure condition. Wire
accordingly.
Note: Maximum Conduit size for installation size is ¾” FNPT.
2.1.1 Permanent Power Connection (AC Powered Models only)
1) Connection to the building wiring system shall be in accordance with the Canadian
Electrical Code (CEC), Part 1 in Canada, the National Electrical Code, ANSI/NFPA 70 in
the USA, or the local electrical codes of the country where the equipment is being
installed.
2) A disconnecting device is required. The disconnecting means shall disconnect all
current-carrying conductors.
3) 15A circuit breaker or equivalent fuse is required.
4) An external switch or breaker shall be in close proximity to the equipment and within
easy reach of the operator. The switch shall be marked as the disconnecting device for
the equipment and include the symbols to its “ON” and “OFF” positions using the
following symbols:
5) The wiring for AC power should be minimum 18 AWG / 300V or as required by local /
country codes.
6) After field wiring, the primary wires must be secured to the enclosure by tie-wraps to
maintain the separation from the signal wires.
7) Wiring diagram for permanent connection: See drawings at the back of this manual.
8) Use copper conductors only.