
16 Designs, materials, weights and performance ratings are approximate and subject to
change without notice. Visit armstronginternational.com for up-to-date information.
Start-Up Procedures and Operation
The HumidiClean™ humidifier converts ordinary tap water or purified water to steam for distribution to raise the relative
humidity level. The demand for humidity is sensed by a humidistat or sensor which sends a control signal to the HumidiClean™.
TheHumidiClean™isconnectedtothepowersupply(208,220/240,380/400,480or600Vac)throughaseparatecircuit
breakersuppliedbythecustomer.Whenpowerisinitiallysuppliedtotheunitfromthecircuitbreaker,theLCDwilldisplay
“ARMSTRONGHC6000”.The“POWER”LEDwillcomeonandtheunit’sfillvalvesolenoidisenergizedtoallowwatertoenter
thetankatarateof1.2L/min(.31GPM)(HC-6500/6700fillrateis3.735L/min(1GPM)).Note:Whenunitisturnedonthe
drain valve will energize for 6 sec. or until water level drops below the high water probe. If water level in tank is above the low
water level switch, assuming the air proving switch is close, the high limit humidity switch is closed, the heating elements will
be activated.
The water fill solenoid continues to be activated until the water level in the tank has energized the high water switch. Note: If fill
or drain valves are not energized when power is first applied, check LCD for diagnostic code. See DIAGNOSTICS section. The
heating elements will remain on to preheat the water inside the tank until the temperature of water has reached the aquastat set
point. During this preheat cycle the amperage draw of the tank can be checked with a clamp on amp meter. The amperage draw
on all high voltage wires connected to the main power supply terminal block should correspond to the value on the nameplate.
If aquastat has been disabled, the humidifier will go into a 3 minute warm-up once the water hits the low water probe.
After the heat-up time, the HumidiClean™ will continue to produce steam based on the demand signal, read from the humidistat
orcalculatedbyreadingtherelativehumidityandsetpoint.Ifthedemandsignaldropsbelow2%orthehighlimit/sailswitch
circuitopens,thecontactor(s)willopenandtheunitwillidle.Note:Ifthehumidifiershutsoffduetolowhumidistatdemand,
ademandsignalof4%orgreaterisneededtore-initiatesteamgeneration.Ifallthesignalsareconsistentasstatedabove,
HumidiClean™ will produce steam continuously and refill the tank with water when the low water level is reached. These fill
intervals will operate based on modulating fill settings in software.
Power to the heating elements is switched on and off by the triacs in the power module to achieve a modulating output based
onthedemandsignal.Thetriacutilizesa1/2secondcycletime.Forexample,witha50%humidistatdemandsignalthetriacs
wouldbeonfor1/4secondandofffor1/4second.Ifthetriacsarefullyon,thegreen“SIGNAL”LEDonthepowermodulewill
beonconstantly.Whenthetriacsstarttomodulate(switchpowertotheheatingelementsonandoff)theLEDwillshowthe
triac on condition and will appear to flicker or blink.
As HumidiClean™ continues to produce steam, the unit will accumulate and memorize the heating element active time for the
purposeofdefiningadraincycleandservicelife(thismemoryisnotaffectedbypoweroutages).WhentheHumidiClean™
heating elements have been on for the drain frequency setting, the unit activates the drain and fill solenoids and begins draining
the tank. The tank will drain with the water being tempered from an activated water fill solenoid. The drainage from the tank
will pass the low water switch, opening the switch and shutting off power to the heating elements. The drainage from the tank
shouldnotexceed70°C(158°F)ontheHC-6100andHC-6300,or57°C(135°F)ontheHC-6500andHC-6700.Thedraincycle
is controlled by the user inputted values in the operation setup menu. Once the unit has timed out of the drain cycle and all of
the switches are still in position to generate steam, the water fill solenoid switch is activated to fill the tank and the cycle starts
over again.