installation &
operating instructions
Design Envelope 4312 and 4392 vertical in-line
twin pumping unit with ivs drive
4
1.0 introduction
This manual contains specific information regarding the safe
installation, operation and maintenance of Armstrong Design
Envelope pumps. Read this manual carefully before installing or
using the product. If clarification is needed on any point please
contact Armstrong quoting the equipment serial number.
1.1 precautions
1.1.1 uncrating
Armstrong Design Envelope 4312 and 4392 in-line pumps are
thoroughly inspected before shipment to assure they meet
with your order requirements. After removing the pump from
the crate, make sure the equipment is in good order and that
all components are received as called for on the packing list.
Any shortages or damage should be reported immediately.
Use extreme care in handling the unit, placing slings carefully
so that stress will not be imposed on the integrated controls,
pump or motor. Never place cable slings around the pump
shaft or integrated controls. The eye bolts or lifting lugs on
the motor are intended for lifting only the motor and not the
complete unit.
1.1.2 handling design envelope 4312 and
4392 units
Design Envelope 4312 and 4392 twin pumps are handled in
a similar manner to the normal twin pumping units. Extra
care is required to ensure the integrated controls do not get
damaged during lifting and installation. Remove the coupling
guards and insert lifting straps through each pump/motor
pedestal on the inner side of each coupling. As the lifting
device is engaged (Using a spacer bar if necessary) and the
straps tighten ensure no part of the strapping is touching any
part of the control or motor fan cover. Lift the pumping unit
carefully from the pallet in this manner and allow the unit to
stand upright on a flat surface and re-position the straps, if
necessary, to ensure safe and damage free transportation
into the pipe installation
1.2 mechanical installation
1.2.1 location
Locate the unit as close as practical to the liquid being
pumped, with a short, direct suction pipe. Ensure adequate
space is left above and around the unit for operation, mainte-
nance, service and inspection of parts.
If the ivs controls are supplied with integral disconnect
switches, 36ins / 1meter clearance may be required in front
of the controls to meet local electrical codes.
Electric motor driven pumps should not be located in damp
or dusty location without special protection.
1.2.2 storage
Pumps not immediately placed into service, or removed from
service and stored, must be properly prepared to prevent rust-
ing. Rotate the shaft periodically to keep rotating element free.
For long term storage, the pump must be placed in a vertical
position in a dry environment.
Internal rusting can be prevented by removing the plugs at
the top and bottom of the casing and drain or air blow out all
water to prevent rust build up or the possibility of freezing. Be
sure to reinstall the plugs when the unit is made operational.
Rustproofing or packing the casing with moisture absorb-
ing material and covering the flanges is acceptable. When
returning to service be sure to remove the drying agent from
the pump.
1.2.3 installation
The most important consideration when installing a Design
Envelope 4312 and 4392 pumping unit is to make sure the
pump is free to float with expansion and contraction of the
piping. Recommended arrangements are:
• Supported from the ceiling by pipe hangers (See fig. 1.1 on
page 5)
• Pipe supported at the ceiling, with the twin free-standing
and mounted with an Armstrong Suction Guide & Flo-Trex
valve. (See figs. 1.2 & 1.3 on page 6)
• Piping supported at ceiling with additional floor mounted
supports under Armstrong Suction Guide and Flo-Trex
Valve (See fig. 1.4 on page 6)
•
Floor mounted saddle supports (See fig. 1.5 on page 6)
• Where required, additional floor support may be obtained
as shown in fig. 1.6. Note that the pump must not be rig-
idly attached either to the plate or to the block. Leave a V"
(3mm) gap between pump and base. The piping must be
installed in such a manner that the pump is not used as a
pipe support.
design envelope 4392 design envelope 4312