Ascon Tecnologic - TLZ35 - OPERATING INSTRUCTIONS - PAG. 2
1.2 Front panel description
TLZ 35
-12.8.
DefOutAL
1
2
5
6
7
4
3
8
1 : Used for setting the Set point and for programming
the function parameters
2 : Used for decreasing the values to be set and for
selecting the parameters.
3 / : Used for increasing the value to be set, for select-
ing the parameters and for activating manual defrosting.
4 : It can be programmed via the parameter USrb to
turning ON and OFF (stand-by) the device. In hidden
parameter programming mode it is used to modify the
visibility of the parameters (see paragraph 2.4).
5 LED SET: Indicates the input in programming mode and
the programming level of the parameters. It also serves
to indicate the Stand-by status.
6 LED Out: Indicates the compressor output (or the
temperature control device) status: on (ON), off (OFF) or
inhibited (flashing).
7 LED DEF/ : Indicates defrosting in progress (ON) or
dripping (flashing).
8 LED AL: Indicates the alarm status (ON), off (OFF) and
silenced (flashing)
2. PROGRAMMING
2.1 Programming of the set point
Press the key then release it, the display will show SP
alternated with the Set Point value. To change it press the
key to increase the value or to decrease it.
These keys increase or decrease the value one digit at a
time, but if the button is pressed for more than one sec-
ond the value increase or decreases rapidly, and after two
seconds pressed, the speed increases even more to all the
desired valued to be reached rapidly.
Exiting the Set mode is achieved by pressing the key or
automatically if no key is pressed for 15 seconds. After that
time the display returns to the normal function mode.
2.2 Parameters programming
To access the instrument function parameters, press the
key and keep it pressed for about 5 seconds, after which
the LED SET lights up and the display shows the code that
identifies the first parameter.
Using the and keys, the desired parameter can be se-
lected and pressing the key, the display alternately shows
the parameter code and its setting that can be changed with
the and keys.
Once the desired value has been set, press the key again:
the new value will be stored and the display returns to show
only the code of the selected parameter.
Pressing the and keys is now possible to another pa-
rameter and change it as described.
To exit the programming mode, press no keys for about 20
seconds, or keep the or key pressed until the instru-
ment exits the programming mode.
2.3 Parameter protection using a password
The instrument has a parameter protection function using a
password that can be personalised through the PASS parameter.
To protect the parameters, set the desired password number
in the parameter PASS.
When the protection is active, press the key to access the
parameters and keep it pressed for about 5 seconds, after
which the LED SET starts flashing and the display shows 0.
At this point, using the and keys, set the password
number programmed and press the key .
If the password is correct, the display shows the code that
identifies the first parameter and it will be possible to pro-
gram the instrument in the same ways described in the previ-
ous section.
Protection using a password can be disabled by setting the
parameter PASS = OFF.
2.4 Parameters programming levels
The instrument has two parameter programming levels.
The first level (visible parameters) is accessed according
to the procedure described above (with or without password
request) while the second level (hidden parameters) can be
accessed according to the following procedure:
–Remove the power supply to the instrument, press the key
and, keeping it pressed, power ON again the instrument;
–After about 5 s the LED SET lights up, the display shows
the code that identifies the first parameter and will be
possible to set the instrument parameters using the same
programming procedure previously described.
–Once the parameter has been selected, if the SET LED is
ON, it can be programmed even on the first (visible) level.
–If SET is OFF, the parameter can only be programmed on
the hidden level (active now).
–To change the visibility of the parameter, press the key:
the SET LED changes its status indicating the accessibility
level of the parameter (ON = visible; OFF = hidden).
The access procedure to hidden parameters is useful if the
password set has been forgotten because allows to access
the PASS parameter and check or change it.
2.5 ON/Stand-by Function
The instrument, once powered up, can assume 2 different
conditions:
ON Means that the controller uses the control functions.
STAND-BY
Means that the controller does not use any control
function and the display is turned off except for the
green LED SET.
In case of power failure, the system always sets itself in the
condition it was in before the black-out.
The ON/Stand-by function can be selected using the key
if the parameter USrb = 1(see paragraph 5.7).