
Ascon Tecnologic - X35- - OPERATING INSTRUCTIONS - PAG. 12
ture control. In this mode the defrost duration is by d.de
time-out. During defrost the dF output behaves as an
heating action temperature control with Set Point = d.tE,
the differential fixed to 1°C and refers to the temperature
measured by the evaporator probe (EP). In this mode,
if the evaporator probe is not enabled or in error, the de-
frost action behaves as with EL selection (therefore the
dF output during defrost must always remain activated).
HG With hot gas in centralized systems: with this mode it
is necessary to configure 3 outputs to control Liquid
solenoid valve (ot output), Hot gas solenoid valve
(dF output) and Suction solenoid valve (Au output with
configuration Fo = 3). During defrost, only the dF output
is activated, while before and after defrost the valves per-
form a sequence of timed operations described below.
5.8.1 Starting automatic defrosts
The automatic control of defrost occours:
–Defrost at defined times – “Real Time Clock Defrost” (when
peresent and enabled the RTC);
–By interval times (regular or dynamic);
–By Evaporator temperature;
–By continuous compressor running time.
In order to avoid unnecessary defrosts when the evapora-
tor temperature is high, the d.tS parameter allows to set the
temperature related to the evaporator probe (probe config-
ured as EP) under which defrosts are possible.
If the temperature measured by the EP probe is higher than
that at parameter d.tS the defrosts are inhibited.
Defrosting at defined times – “Real Time Clock Defrosts”
The choice d.dC = cL disables the defrost at specified inter-
vals (parameters d.di and d.Sd) and enables the Real Time
Clock Defrosts programmed through parameters c.01, c.02,
c.03, c.04, c.05, c.06, c.07, c.08, c.09, c.10, c.11, c.12, c.13
and, c.14. In this mode the instrument can therefore man-
age up to a maximum of 14 daily defrost events (14 x 7 = 98
weekly defrosts with d.8).
In any case, the events can be programmed as desired even
daily according to the following settings:
d. 1 = Monday ÷ d. 7 = Sunday;
d. 8 Every day;
d. 9 Monday, Tuesday, Wednesday, Thursday, Friday;
d.10
Monday, Tuesday, Wednesday, Thursday, Friday, Saturday;
d.11 Saturday and Sunday;
d.oF No day (event disabled).
These options allow to manage the start of defrosts at differ-
ent hours for weekdays and holidays according to user needs.
For further detailed information and programming examples,
see the “Programmable events” paragraph.
Note: Remember that for “Real Time Clock Defrosts” the
user must set d.dC = cL and the internal clock must be
present and enabled.
Defrost by regular interval time
As an alternative to programmable timed defrosts, the instru-
ment allows the execution of interval defrosts.
Through parameter d.dC it is possible to establish the count-
ing methods of the defrosting interval d.di:
rt Intervals with counting of the total functioning time. The
d.di interval is counted as the total time the instrument
is powered ON. This mode the one currently used in the
refrigerators systems;
ct Intervals with counting of the compressor function-
ing time (ot output switched ON). The d.di interval is
counted as the sum of the operating times of the control
output (ot output activated). This mode is typically used
in the positive temperature refrigerator systems with
defrost by compressor stop.
cS
Defrost at all compressor stops. The instrument carries
out a defrost cycle at each compressor stop (i.e. at each
deactivation of the ot output) or however at d.di defrost in-
terval end. If d.di = oF the defrost happens only when the
compressor stops. This mode is used only on particular
refrigerator systems in which the maximum evaporator effi-
ciency conditions at each compressor cycle are requested.
To enable the automatic defrost at intervals, after setting
d.dC parameter as desired (rt, ct or cS), with parameter d.di
select the time interval between the end of a defrost and the
beginning of the next.
The time that the instrument must wait to perform the first
defrost after power ON can be set with parameter d.Sd.
d.Sd allows to perform the first defrost to a different interval
from d.di time.
To force the instrument to perform a defrost cycle at each
power ON (as long as the conditions set with parameters d.tS
and d.tE are satisfied) set parameter d.Sd = oF.
This allows the evaporator to be permanently defrost, even
when frequent interruptions to power supply occur that may
cause the cancellation of the various defrosting cycles.
If instead it is desired that all the defrosts are performed at
the same interval time, set d.Sd = d.di.
Setting d.di = oF the Automatic defrost function by interval is
totally disabled (including the first, regardless to the time set
at the d.sd parameter).
Dynamic Defrost Intervals System
Note: For this function is necessary to use the evaporator probe.
Program d.dC = rt, ct or cS and set d.dd = any value to en-
able the Dynamic Defrost Intervals System mode.
If d.dd = 0the defrost intervals are those set and the Dynam-
ic Defrost Intervals System mode is disabled.
This mode allows to dynamically reduce the defrost interval
counting (d.di or d.Sd if is the first defrost), anticipating, when
necessary, the defrost execution, all based on an algorithm
that detects a drop in the refrigerator thermal exchange perfor-
mance.
The dynamic defrost algorithm allows to highlight the
heat exchange reductions by evaluating the current tempera-
ture difference between the 2 probes (Pr1 and EP) and the
same difference stored in proximity of the control Set Point
temperature.
The advantage of the Dynamic Defrost Interval is the possi-
bility to program a defrost interval time longer than normal.
In this way, when necessary, the instrument has the possibil-
ity to anticipate/posticipate the defrost cycle from the pro-
grammed time.
If the system results correctly set, it is possible to avoid
many unnecessary defrost cycles (and therefore obtain a
consistent energy saving) that may occur with normal opera-
tion when, to ensure more system efficiency, the defrosts
interval is programmed with a time that is often too short.
With parameter d.dd - Defrost interval percentage reduc-
tion - is possible to establish the percentage of reduction of
the remaining time to start next defrost when the conditions
for the reduction happen.
If parameter d.dd = 100%, at first increasing (> 1°) of the
D
T