Ascon tecnologic KR1E User manual

WINE CONTROLLER
78 x 35 mm
Model KR1E
Quick Guide •ISTR_Q_KR1E_E_05_--
viale Indipendenza 56, 27029 - Vigevano (PV) - ITALY
Tel.: +39 0381 698 71, Fax: +39 0381 698 730
internet site: www.ascontecnologic.com
E-mail: [email protected]
ube
DECLARATION OF CONFORMITY AND
MANUAL RETRIEVAL
KR1E is a panel mounting, Class II instrument designed to comply
with European directives. All information about the controller use
can be found in the Engineering Manual:
ISTR_M_KUBEM-R1E_E_0x_-- (“x” is the revision).
The Declaration of Conformity and the manual of the controller
can be downloaded (free of charge) from the web-site:
www.ascontecnologic.com
Once connected to the web-site, search: KR1E
then click on KR1E.
In the lower part of the product page (in any language) is present
the download area with links to the documents available for the
controller (in the available languages).
Warning!
- Whenever a failure or a malfunction of the device may cause
dangerous situations for persons, things or animals, please
remember that the plant must be equipped with additional
devices which will guarantee safety.
-
We warrant that the products will be free from defects in material and
workmanship for 18 months from the date of delivery. Products
and components that are subject to wear due to conditions of
use, service life and misuse are not covered by this warranty.
Disposal
The appliance (or the product) must be disposed
of separately in compliance with the local
standards in force on waste disposal.
DISPLAY AND KEYS
KR1E
Access to:
- Operator Commands
- Parameters
- Configuration
Access to:
- Setpoint adjustment
- Operator additional info
Increase the displayed value
or selects the next parameter
in the list
Decrease the displayed value
or selects the previous
parameter in the list
Exits from Operator mode/
Parameter setting/
Configuration mode
Programmable key: runs the
programmed function (Autotune,
Auto/Man, Timer, etc.)
Access to:
- Setpoint adjustment
Operator Mode Control Mode
Confirm and go to
Next parameter
These 2 keys, pressed in sequence, allow to toggle
between MANual and AUTO modes.
+
Mesure
(Unités Phys.)
Set Point(auto mode)
Output Value(manual mode)
Param. value or
State/Function (Editing mode)
Output LEDs
Manual mode
Alarm active
Unit (°C/°F)
Autotune in progress
(flashing)
MODEL CODE
The Hardware resources are identified by the following Model Code.
KR1E A B C D E F G H
Model:
Supply voltage: 100... 240 Vac/
18... 28 Vac/
20... 30 Vdc
ELECTRICAL CONNECTIONS
RS485
DI1
OP3 OP2
NO NOCC
CN
ONF
Pt100
Pt1000/NTC/PTC
OP4
(note)
DI2
(note)
Ananogue Input
12 Vdc
(note)
12 Vdc
(note)
PV
PV
4... 20 A
3 wire transmitter
2 wire
transmitter
OP1
TERMINALS
Note: Terminal 4 can be programmed as:
- Digital Input (DI2) connecting a free of voltage contact between terminals 4 and 11;
- 0... 12 V SSR Drive Output (OP4) connecting the load between terminals 4 and 11;
- 12 Vdc (20 mA) transmitter power supply connecting the 2 wire transmitter between terminals 4 and 1;
for 3 wire transmitter connect terminal 4 to transmitter power supply input and terminal 1 and 2 to transmitter signal output.
mA
L
Pin:
q
1.4 mm (0.055 in.) max.
Stripped wire: L 5.5 mm (0.21 in.)
Neutral Line
Power supply
MOUNTING
DIMENSIONS
Overall dimensions (L x H x D): 78 x 35 x 69.5 mm
(3.07 x 1.37 x 2.73 in.)
Panel Cut-out (L x H): 71+0.6 x 29+0.6 mm
(2.79+0.023 x 1.14+0.023 in.)
Attention
The controller can be installed using 2 different types of brackets.
Follow the sequence 1, 2a, 3a for the screw bracket (collar
bracket for IP65), the sequence 1, 2b, 3b for the “butterfly”
brackets (2 pieces).
2a
2a
3b
3b
1
3a
3a
1
2b
2b
KR1E KR1EKR1E
Press for 2 seconds
the key
PARAMETERS SETTING
CONTROLLER DISPLAY
Increases the displayed value
Confirm value and pass to the next parameter
Decreases the displayed value
Parameter setting
To exit the parameters configuration procedure, press
for 3 seconds or wait for the end of the delay
(about 10 seconds)
The KR1E-xDRRRDxx controller is pre-configured (default
configuration) for wine applications where there is the
need to cool or reheat in thermostatic mode (on/off with
hysteresis) a tank with a PT100 probe in mono relay
output (Heat and Cool on OP1).
Heat mode
The controller action type can be identified by the color of the upper display (measurement):
Red: Heat mode only
Green: Cool mode only
Orange:The controller responds to temperature changes and selects the appropriate control mode
by operating the appropriate control output and displaying the setpoint to be reached.
The numbered red LEDs indicate, when lighted, the active (on) state of the corresponding relay output.
Cool mode Automatic Heat/Cool
selection
2 s
KR1E
KR1E
KR1E
KR1E
Line KR1E
Power Supply A
24Vac (-25... +12%) or 24Vdc (-15... +25%) L
100... 240 Vac (-15... +10%) H
Input + Ditigal input1 B
PT100, PT1000, mA + Digital Input 1 D
PTC, NTC, mA + Digital Input 1 P
Output OP1 (control output) C
Relay (1 SPST NO, 4 A/250 Vac) R
Output OP2 (control output) D
None -
Relay SPST NO 2 A/250 Vac (resistive load) R
Output OP3 (alarm output) E
None -
Relay SPST NO 2 A/250 Vac (resistive load) selectable if Output 1 is present
R
Output OP4 (configurable) F
Digital I/O (see the Electrical Connections paragraph for details) D
Serial Communications G
TTL Modbus -
RS485 Modbus S
Terminal Type H
Standard (screw type non removable terminal blocks) -
With plug-in screw type terminal blocks E
With plug-in clamp type terminal blocks M
With plug-in terminal blocks (fixed part only) N
Model Code example: KR1E-LDRRRD-E
KR1E controller for Wine applications
- Power supply: 24Vac/dc,
- Inputs: PT1000 or 4... 20 mA;
- Digital Input 1,
- 3 Relay Outputs (OP1: Alarm, OP2: Cold, OP3 Alarm),
- Confiigurable OP4: Digital Input 2 or Transmitter power supply,
- TTL Port,
- Removable screw type terminals.
Parameters List (PASS: 30)
Group Param. Description
Value range or selection list
Default User
selection Note
inp
node Control mode selection 1 Heat or Cool on OP1 only,
2 Heat (OP1) or Cool (OP2),
3 Heat (OP1) and Cool (OP2), 1
When only 1 output is
present, the controller
does not display the
node parameter.
It is fixed on “Mode 1”
sEns Measurement input type Pt1 Pt100
Pt10 Pt1000
4.20 4… 20 mA Pt1
dp Decimal point position 0... 2 0
diF1 Digital input 1 function Stby Mode Standby (transition)
Stby2 Mode Standby (status)
HC.tr Chaud <-> Froid (transition)
HC.St Chaud <-> Froid (status)
nonE
diF2 Digital input 2 function nonE
di.a Digital Inputs Action 0... 3 0 See the manual for
details
Pan usrb Key function
Stby Standby Mode
1H2C Heat <-> Cool toggle
HC.Sb Heat <-> Cool and
Auto <-> Standby
Auto
If HC.Sb: a 1 s pressure
toggles between
Heat <-> Cool mode.
A 5 s pressure puts the
controller in standby
ser
Add Modbus address of the controller 1... 254 1 Modbus RTU slave
Protocol
bAud Modbus transmission speed 1200, 2400, 9600 baud,
19.2, 38.4 kbaud 9600
Several successive pressures on the key allow the various groups of parameters to be scrolled.
A long pressure on the key allows to exit the Configuration mode and return to the Operator mode
Parameters List (PASS: 20)
Param. Description
Value range or selection list
Default User
selection Note
OPEr Operative mode selection reg Auto,
stdy Standby reg stdy: Control action stopped
reg: Control action running
SP Set point 1 -1999... +9999 (Engineering Unit) 0
SP2 Set point 2 -1999... +9999 (Engineering Unit) 0
HstH Heat Hysteresis 0... 9999 (Engineering Unit) 1
HstC Cool Hysteresis 0... 9999 (Engineering Unit) 1
AL1 Alarm 1 threshold (Low) AL1L... AL1H 0
AL2 Alarm 2 threshold (High) AL2L... AL2H 80
dP Decimal point position 0... 2 0
SPLL Setpoint Low Limit From 0 to the SPHL value 0
SPHL Setpoint High Limit From the value of SPLL to 1999 90
FiL Digital filter on the measured value 0 oFF
0.1... 20.0 s 1.0
HAL1 Alarm 1 Hysteresis 0...9999 (Engineering Unit) 1
HAL2 Alarm 2 Hysteresis 0...9999 (Engineering Unit) 1
Al.o Adjust Low Offset -300…+300 (Engineering Unit) 0
Note: Several successive pressures on the key allow to scroll the available Control parameters.
m Pressing no keys for 5 s, the controller automatically exits PASS20 menu and returns to the standard display and the current measurement.
KR1E KR1E KR1E
Operative Set Point Modified Set Point
Press the key (3 s) or
wait for the 10s time out to
store the new Set Point
and return to Normal Mode
CONTROLLER OPERATION
or
The Setpoint temperature setting is made pressing for a long time on the arrow keys / , small changes are made
with short pressures on the arrow keys / or by pressing the key when the display shows SP.
Chenge the value with the arrow keys
/ , then validate the valueby pressing .
1 s
KR1E KR1E
KR1E KR1E
KR1E KR1E KR1E
In 30, the navigation between the different groups is
carried out by means of the key . To access the
parameters of the selected group, press the key and
modify the value using the / keys. A brief pressure
on the key is used to exit the group, a long one to exit
the configuration menu.
The change of the control direction between heating and
cooling is done by pressing the key for at least 1 s.
The new mode is pointed out changing the main display
when this button is released.
Note: Active if USrb = 1H2C
Not active in Mode 3
(Automatic Heat ↔ Cool toggle)
Heat ↔ Cool mode
Control Mode Selection (PASS: 30)
Cool ModeHeat Mode
Heat or Cool with 1 relay Heat or Cool with 2 relays
Heat on OUT1
Cool on OUT2
Heat or Cool with 2 relays
Heat on OUT1
Cool on OUT2
 When only output 1
is present, the node
parameter is not
displayed and the
Control Mode is
forced to 1
KR1E KR1E
KR1E
Press the key or wait
for the timeout to store the
new Setpoints and return
to Operator Mode
Separate Heating (SP) and Cooling (SP2) Setpoints
Heat
Setpoint change Cool
Setpoint change
2 s
KR1E
KR1E KR1E KR1E
KR1E KR1E KR1E
2 s
Limits of the Setpoint values
Setting the lower limit of
the desired Setpoint
Validate the lower limit of
the desired Setpoint
Exit the setting mode
Setting the higher limit
of the desired Setpoint
Validate the higher limit
of the desired Setpoint
Exit the setting mode
Heat output
Hysteresis in °C Cool output
Hysteresis in °C
Setting the Hysteresis of Heat and Cool control outputs
KR1E
KR1E
KR1E
KR1E
2 s 2 s
Standby mode activation
at input state transition
The 1st contact closure
switches the controller
to Standby.
The 2nd one reactivates
the Automatic.
Standby mode activation
at input state change
The close contact switches
the controller to Standby.
The open contact
reactivates the Automatic.
Control mode selection
at input state transition
Each contact closure
reverses the control
mode and the
associated setpoint.
Control mode selection
at input state change
With the contact open
the controller is in HEAT
mode with SP.
With the contact close
the controller is in COOL
mode with SP2.
KR1E
KR1E KR1E
KR1E
KR1E KR1E KR1E KR1E
DI1/DI2 Digital Input functions (pass = 30)
2 s
ou dif2 ou dif2 ou dif2 ou dif2
KR1E
KR1E
KR1E
KR1E
Setting the temperature alarm thresholds
2 s 2 s
Low alarm
threshold in °C High alarm
threshold in °C
KR1E
KR1E
KR1E
KR1E
2 s 2 s
Hysteresis of the
Low Alarm in °C Hysteresis of the
High Alarm in °C
Setting the hysteresis of temperature alarms
KR1E KR1E
KR1E
2 s
KR1E
KR1E KR1E
USrb Functions of the key (pAss 30)
Standby mode activation
The 1st pressure switches
the controller to Standby.
The 2nd one reactivates
the Automatic.
Heat ↔ Cool selection
Heat with SP
or
Cool with SP2
(without Standby mode).
Heat or Cool or Standby
The short pressures change
the action Heat ↔ Cool.
The long pressures switch
the control Auto ↔ Standby.
To access the selected group
settings press the key
.
With PASS = 30, the navigation
between the different groups is
carried out by means of the key
.
To changhe the value press
the keys /
. A short
pressure on the key
allows to exit the group; a
long pressure allows to exit
the configuration menu.
It is possible to reset the controller to factory parameters (default parameters).
To load the default parameter values, press the
key for about 2 to display
PASS, set the PASS value to -481 and confirm with the key
.
The device restarts in its initial configuration with the default settings shown in
the table at page 1.
RESET THE CONTROLLER TO FACTORY PARAMETERS
2 s
KR1E

Other manuals for KR1E

1

This manual suits for next models

2

Other Ascon tecnologic Controllers manuals

Ascon tecnologic X35 User manual

Ascon tecnologic

Ascon tecnologic X35 User manual

Ascon tecnologic Y39W User manual

Ascon tecnologic

Ascon tecnologic Y39W User manual

Ascon tecnologic TLK 33 User manual

Ascon tecnologic

Ascon tecnologic TLK 33 User manual

Ascon tecnologic K32 Installation and operation manual

Ascon tecnologic

Ascon tecnologic K32 Installation and operation manual

Ascon tecnologic X34 User manual

Ascon tecnologic

Ascon tecnologic X34 User manual

Ascon tecnologic KX6 Series Installation and operation manual

Ascon tecnologic

Ascon tecnologic KX6 Series Installation and operation manual

Ascon tecnologic TLZ35 User manual

Ascon tecnologic

Ascon tecnologic TLZ35 User manual

Ascon tecnologic KM1E Installation and operation manual

Ascon tecnologic

Ascon tecnologic KM1E Installation and operation manual

Ascon tecnologic XS Series User manual

Ascon tecnologic

Ascon tecnologic XS Series User manual

Ascon tecnologic TLK41 User manual

Ascon tecnologic

Ascon tecnologic TLK41 User manual

Ascon tecnologic TLY25 User manual

Ascon tecnologic

Ascon tecnologic TLY25 User manual

Ascon tecnologic KM2 Installation and operation manual

Ascon tecnologic

Ascon tecnologic KM2 Installation and operation manual

Ascon tecnologic E30 User manual

Ascon tecnologic

Ascon tecnologic E30 User manual

Ascon tecnologic TLY26 User manual

Ascon tecnologic

Ascon tecnologic TLY26 User manual

Ascon tecnologic K 5P Series Installation and operation manual

Ascon tecnologic

Ascon tecnologic K 5P Series Installation and operation manual

Ascon tecnologic Y39SE User manual

Ascon tecnologic

Ascon tecnologic Y39SE User manual

Ascon tecnologic K32L Installation and operation manual

Ascon tecnologic

Ascon tecnologic K32L Installation and operation manual

Ascon tecnologic M81 User manual

Ascon tecnologic

Ascon tecnologic M81 User manual

Ascon tecnologic TLB 55 User manual

Ascon tecnologic

Ascon tecnologic TLB 55 User manual

Ascon tecnologic X5 Series User manual

Ascon tecnologic

Ascon tecnologic X5 Series User manual

Ascon tecnologic KM5P Series Installation and operation manual

Ascon tecnologic

Ascon tecnologic KM5P Series Installation and operation manual

Ascon tecnologic KR1E User manual

Ascon tecnologic

Ascon tecnologic KR1E User manual

Ascon tecnologic KX5P Installation and operation manual

Ascon tecnologic

Ascon tecnologic KX5P Installation and operation manual

Ascon tecnologic K48 Installation and operation manual

Ascon tecnologic

Ascon tecnologic K48 Installation and operation manual

Popular Controllers manuals by other brands

Signature Control Systems Galaxy-RT Solar Series quick start guide

Signature Control Systems

Signature Control Systems Galaxy-RT Solar Series quick start guide

BOSSCO DN 15 manual

BOSSCO

BOSSCO DN 15 manual

Show Tec showdesigner 512 user manual

Show Tec

Show Tec showdesigner 512 user manual

Phase Technologies ES Series quick start guide

Phase Technologies

Phase Technologies ES Series quick start guide

Heath Zenith SL-5408-GR-A - Heathco user guide

Heath Zenith

Heath Zenith SL-5408-GR-A - Heathco user guide

Alpic Air XK76 owner's manual

Alpic Air

Alpic Air XK76 owner's manual

KEBCO COMBIVERT F5 instruction manual

KEBCO

KEBCO COMBIVERT F5 instruction manual

Astral Pool HALO LITE4 installation manual

Astral Pool

Astral Pool HALO LITE4 installation manual

Elmo Bassoon installation guide

Elmo

Elmo Bassoon installation guide

AutomationDirect CLICK Series manual

AutomationDirect

AutomationDirect CLICK Series manual

EQ3 Homematic HM-LC-Sw4-DR Installation and operating manual

EQ3

EQ3 Homematic HM-LC-Sw4-DR Installation and operating manual

red lion T48 manual

red lion

red lion T48 manual

Sofar solar 4-12KTL-X Quick installation guide

Sofar solar

Sofar solar 4-12KTL-X Quick installation guide

Plast-O-Matic CAFE Series Installation, operation & maintenance instructions

Plast-O-Matic

Plast-O-Matic CAFE Series Installation, operation & maintenance instructions

Aqua Medic T Controller HC Operation manual

Aqua Medic

Aqua Medic T Controller HC Operation manual

Delta AS Series Operation manual

Delta

Delta AS Series Operation manual

Timeguard TRT039N Installation & operating instructions

Timeguard

Timeguard TRT039N Installation & operating instructions

Electronics SP44 manual

Electronics

Electronics SP44 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.