A4 INTRINSICALLY SAFE &
NON-INCENDIVE RATED PRESSURE
TRANSMITTER INSTRUCTION SHEET
INSTALLATION FOR FM
INTRINSICALLY SAFE CLASS 1, GROUPS A, B, C & D &
CLASS ll, GROUPS E, F & G &
CLASS lll
INSTALLATION NOTES:
Voc OR Vt ≤30VDC
Isc OR It ≤100mA
Ca≥0.053uF + Ccable
La ≥0.364uH + Lcable
1. THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION OF TWO INTRIN -
SICALLY SAFE DEVICES FM APPROVED WITH ENTITY PARAMETERS NOT SPECIFICALLY
EXAMINED IN COMBINATION AS A SYSTEM WHEN: Uo OR Voc OR V≤t Vmax, Io OR Isc OR≤
It Imax, Ca OR Co ≥Ci + Ccable, La OR ≥Lo Li +Lcable≤, Po Pi.
2. THE NONINCENDIVE FIELD WIRING CONCEPT ALLOWS INTERCONNECTION OF NONINCEND -
ING FIELD WIRING APPARATUS WITH ASSOCIATED NONINCENDIVE FIELD APPARATUS
USING ANY OF THE WIRING METHODS PERMITTED FOR NON3HAZARDOUS (UNCLASSIFIED)
LOCATIONS WHEN: Uo OR Voc OR Vt Vmax, Io OR Isc OR It Imax, Ca OR Co + Ccable, La OR
Lo Li +Lcable, Po Pi.
3. FOR DIVISION 1 INSTALLATIONS, THE CONFIGURATION OF ASSOCIATED APPARATUS SHALL
BE FM APPROVED UNDER ENTITY CONCEPT.
4. FOR DIVISION 2 INSTALLATIONS USING NONINCENDIVE FIELD WIRING CONCEPTS THE
ASSOCIATED APPARATUS SHALL BE FM APPROVED UNDER THE ENTITY CONCEPT OR
NONINCENDIVE FIELD WIRING CONCEPT.
5. FOR DIVISION 2 INSTALLATIONS THE ASSOCIATED APPARATUS IS NOT REQUIRED TO BE FM
APPROVED UNDER ENTITY CONCEPT OR NONINCENDIVE FIELD WIRING CONCEPT IF THE
A2 SERIES PRESSURE TRANSDUCER IS INSTALLED IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE (ANSI/NFPA 70) FOR DIVISION 2 WIRING METHODS EXCLUDING
NONINCENDIVE FIELD WIRING.
6. CONTROL EQUIPMENT CONNECTED TO THE ASSOCIATED APPARATUS SHALL NOT USE OR
GENERATE MORE THAN 250VRMS OR VDC.
7. DIVISION 1 INSTALLATIONS SHOULD BE IN ACCORDANCE WITH ANSI/ISA RP12.06.01,
“INSTALLATION OF INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS (CLASSIFIED)
LOCATIONS” AND THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70).
8. ASSOCIATED APPARATUS MANUFACTURERS INSTALLATION DRAWING SHALL BE FOLLOWED
WHEN INSTALLING THIS EQUIPMENT.
9. RUN SHIELDED INTERCONNECTION CABLE WITH SHIELD CONNECTED TO FM APPROVED
ASSOCIATED APPARATUS GROUND.
10. WARNING – DO NOT OPEN WHEN ENERGIZED.
11. WARNING – DO NOT DISCONNECT EQUIPMENT UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
HAZARDOUS (CLASSIFIED) AREA
CLASS I, DIVISION 1 & 2,
GROUPS A, B, C, & D;
CLASS II, DIVISION 1 & 2,
GROUPS E, F & G, CLASS III
NON-HAZARDOUS
(UNCLASSIFIED) AREA
BARRIER
BARRIER
V+
V–
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
R LOAD
250 OHM
TYP.
R LOAD
250 OHM
TYP.
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
V+
V–
+24 VDC TYP.
+
–24 VDC TYP.
–
V OUT
(1-5 V TYP.)
V OUT
(1-5 V TYP.)
INSTALLATION FOR FM
INTRINSICALLY SAFE CLASS 1, GROUPS A, B, C & D &
CLASS ll, GROUPS E, F & G &
CLASS lll
INSTALLATION NOTES:
Voc OR Vt ≤30VDC
Isc OR It ≤100mA
Ca≥0.053uF + Ccable
La ≥0.364uH + Lcable
1. THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION OF TWO INTRIN -
SICALLY SAFE DEVICES FM APPROVED WITH ENTITY PARAMETERS NOT SPECIFICALLY
EXAMINED IN COMBINATION AS A SYSTEM WHEN: Uo OR Voc OR V≤t Vmax, Io OR Isc OR≤
It Imax, Ca OR Co ≥Ci + Ccable, La OR ≥Lo Li +Lcable≤, Po Pi.
2. THE NONINCENDIVE FIELD WIRING CONCEPT ALLOWS INTERCONNECTION OF NONINCEND -
ING FIELD WIRING APPARATUS WITH ASSOCIATED NONINCENDIVE FIELD APPARATUS
USING ANY OF THE WIRING METHODS PERMITTED FOR NON3HAZARDOUS (UNCLASSIFIED)
LOCATIONS WHEN: Uo OR Voc OR Vt Vmax, Io OR Isc OR It Imax, Ca OR Co + Ccable, La OR
Lo Li +Lcable, Po Pi.
3. FOR DIVISION 1 INSTALLATIONS, THE CONFIGURATION OF ASSOCIATED APPARATUS SHALL
BE FM APPROVED UNDER ENTITY CONCEPT.
4. FOR DIVISION 2 INSTALLATIONS USING NONINCENDIVE FIELD WIRING CONCEPTS THE
ASSOCIATED APPARATUS SHALL BE FM APPROVED UNDER THE ENTITY CONCEPT OR
NONINCENDIVE FIELD WIRING CONCEPT.
5. FOR DIVISION 2 INSTALLATIONS THE ASSOCIATED APPARATUS IS NOT REQUIRED TO BE FM
APPROVED UNDER ENTITY CONCEPT OR NONINCENDIVE FIELD WIRING CONCEPT IF THE
A2 SERIES PRESSURE TRANSDUCER IS INSTALLED IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE (ANSI/NFPA 70) FOR DIVISION 2 WIRING METHODS EXCLUDING
NONINCENDIVE FIELD WIRING.
6. CONTROL EQUIPMENT CONNECTED TO THE ASSOCIATED APPARATUS SHALL NOT USE OR
GENERATE MORE THAN 250VRMS OR VDC.
7. DIVISION 1 INSTALLATIONS SHOULD BE IN ACCORDANCE WITH ANSI/ISA RP12.06.01,
“INSTALLATION OF INTRINSICALLY SAFE SYSTEMS FOR HAZARDOUS (CLASSIFIED)
LOCATIONS” AND THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70).
8. ASSOCIATED APPARATUS MANUFACTURERS INSTALLATION DRAWING SHALL BE FOLLOWED
WHEN INSTALLING THIS EQUIPMENT.
9. RUN SHIELDED INTERCONNECTION CABLE WITH SHIELD CONNECTED TO FM APPROVED
ASSOCIATED APPARATUS GROUND.
10. WARNING – DO NOT OPEN WHEN ENERGIZED.
11. WARNING – DO NOT DISCONNECT EQUIPMENT UNLESS AREA IS KNOWN TO BE
NON-HAZARDOUS.
HAZARDOUS (CLASSIFIED) AREA
CLASS I, DIVISION 1 & 2,
GROUPS A, B, C, & D;
CLASS II, DIVISION 1 & 2,
GROUPS E, F & G, CLASS III
NON-HAZARDOUS
(UNCLASSIFIED) AREA
BARRIER
BARRIER
V+
V–
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
R LOAD
250 OHM
TYP.
R LOAD
250 OHM
TYP.
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
V+
V–
+24 VDC TYP.
+
–24 VDC TYP.
–
V OUT
(1-5 V TYP.)
V OUT
(1-5 V TYP.)
4.3 FM INSTALLATION GUIDELINES
INSTALLATION NOTES≥
Voc OR Vt ≤30VDC
Isc OR It ≤100mA
Ca≥ 0.053uF + Ccable
La ≥ 0.364uH + Lcable
1. THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION
OF TWO INTRINSICALLY SAFE DEVICES FM APPROVED WITH ENTITY
PARAMETERS NOT SPECIFICALLY EXAMINED IN COMBINATION AS A
SYSTEM WHEN: Uo OR Voc OR V≤t Vmax, Io OR Isc OR≤ It Imax, Ca OR Co
≥ Ci + Ccable, La OR ≥Lo Li +Lcable≤, Po Pi.
2. THE NONINCENDIVE FIELD WIRING CONCEPT ALLOWS INTERCONNECTION
OF NONINCENDING FIELD WIRING APPARATUS WITH ASSOCIATED
NONINCENDIVE FIELD APPARATUS USING ANY OF THE WIRING METHODS
PERMITTED FOR NON3HAZARDOUS (UNCLASSIFIED) LOCATIONS WHEN: Uo
OR Voc OR Vt Vmax, Io OR Isc OR It Imax, Ca OR Co + Ccable, La OR Lo Li
+Lcable, Po Pi.
3. FOR DIVISION 1 INSTALLATIONS, THE CONFIGURATION OF ASSOCIATED
APPARATUS SHALL BE FM APPROVED UNDER ENTITY CONCEPT.
4. FOR DIVISION 2 INSTALLATIONS USING NONINCENDIVE FIELD WIRING
CONCEPTS THE ASSOCIATED APPARATUS SHALL BE FM APPROVED UNDER
THE ENTITY CONCEPT OR NONINCENDIVE FIELD WIRING CONCEPT.
INSTALLATION FOR FM
INTRINSICALLY SAFE CLASS 1, GROUPS A, B, C & D &
CLASS ll, GROUPS E, F & G &
CLASS lll
5. FOR DIVISION 2 INSTALLATIONS THE ASSOCIATED APPARATUS IS
NOT REQUIRED TO BE FM APPROVED UNDER ENTITY CONCEPT OR
NONINCENDIVE FIELD WIRING CONCEPT IF THE
A2X(4-20mA) & A4 SERIES PRESSURE TRANSDUCER IS INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70)
FOR DIVISION 2 WIRING METHODS EXCLUDING NONINCENDIVE FIELD
WIRING.
6. CONTROL EQUIPMENT CONNECTED TO THE ASSOCIATED APPARATUS
SHALL NOT USE OR GENERATE MORE THAN 250VRMS OR VDC.
7. DIVISION 1 INSTALLATIONS SHOULD BE IN ACCORDANCE WITH ANSI/
ISA RP12.06.01, ``INSTALLATION OF INTRINSICALLY SAFE SYSTEMS FOR
HAZARDOUS (CLASSIFIED) LOCATIONS’’ AND THE NATIONAL ELECTRICAL
CODE (ANSI/NFPA 70).
8. ASSOCIATED APPARATUS MANUFACTURERS INSTALLATION DRAWING
SHALL BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.
9. RUN SHIELDED INTERCONNECTION CABLE WITH SHIELD CONNECTED TO
FM APPROVED ASSOCIATED APPARATUS GROUND.
10. WARNING –DO NOT OPEN WHEN ENERGIZED.
11. WARNING –DO NOT DISCONNECT EQUIPMENT UNLESS AREA IS KNOWN
TO BE NON-HAZARDOUS.