manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. AUMA
  6. •
  7. Controllers
  8. •
  9. AUMA SA 25.1-UW User manual

AUMA SA 25.1-UW User manual

Control
→Parallel
Profibus DP
Profinet
Modbus RTU
Modbus TCP/IP
Foundation Fieldbus
Multi-turn actuators
SA 25.1-UW –SA 30.1-UW
SAR 25.1-UW –SAR 30.1-UW
for continuous underwater use
with actuator controls
AC 01.2 Non-Intrusive
Assembly, operation, commissioningOperation instructions
Read operation instructions first.
●Observe safety instructions.
●These operation instructions are part of the product.
●Retain operation instructions during product life.
●Pass on instructions to any subsequent user or owner of the product.
Purpose of the document:
This document contains information for installation, commissioning, operation and maintenance staff.It is intended
to support device installation and commissioning.
Reference documents:
●Manual (Operation and setting ) of actuator controls AC 01.2 Parallel
Reference documents can be downloaded from the Internet (www.auma.com) or ordered directly from AUMA
(refer to <Addresses>).
Table of contents Page
41. Safety instructions................................................................................................................. 41.1. Basic information on safety 41.2. Range of application 51.3. Warnings and notes 51.4. References and symbols
72. Identification........................................................................................................................... 72.1. Name plate 102.2. Short description
113. Transport, storage and packaging........................................................................................ 113.1. Transport 123.2. Storage 123.3. Packaging
134. Assembly................................................................................................................................ 134.1. Mounting position 134.2. Multi-turn actuator: mount to valve/gearbox 134.2.1. Output drive types B 144.2.1.1. Multi-turn actuator with output drive types B:mount to valve/gearbox 154.3. Mounting positions of local controls 154.3.1. Mounting positions: modify
165. Electrical connection............................................................................................................. 165.1. Basic information 185.2. Cable installation between actuator controls (wall bracket) and actuator 225.3. S/SH electrical connection (AUMA plug/socket connector) 235.3.1. Terminal compartment : open 245.3.2. Cable connection 255.3.3. Terminal compartment : close
266. Operation................................................................................................................................ 266.1. Motor operation 266.1.1. Local actuator operation 276.1.2. Actuator operation from remote 276.2. Menu navigation via push buttons (for settings and indications)
2
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Table of contents AC 01.2 Non-Intrusive
286.2.1. Menu layout and navigation 296.3. User level, password 296.3.1. Password entry 306.3.2. Password change 306.4. Language in the display 306.4.1. Language change
327. Indications.............................................................................................................................. 327.1. Indications during commissioning 327.2. Indications in the display 337.2.1. Feedback indications from actuator and valve 367.2.2. Status indications according to AUMA classification 367.2.3. Status indications according to NAMUR recommendation 387.3. Indication lights of local controls
398. Signals (output signals)......................................................................................................... 398.1. Status signals via output contacts (digital outputs) 398.1.1. Assignment of outputs 398.1.2. Coding the outputs 398.2. Analogue signals (analogue outputs)
409. Commissioning (basic settings)........................................................................................... 409.1. Type of seating: set 419.2. Torque switching: set 429.3. Limit switching: set 449.4. Test run 449.4.1. Direction of rotation: check 459.4.2. Limit switching: check
4610. Corrective action.................................................................................................................... 4610.1. Faults during commissioning 4610.2. Fault indications and warning indications 5010.3. Fuses 5010.3.1. Fuses within the actuator controls 5210.3.2. Motor protection (thermal monitoring)
5311. Servicing and maintenance................................................................................................... 5311.1. Preventive measures for servicing and safe operation 5311.2. Maintenance 5311.3. Disposal and recycling
5412. Technical data......................................................................................................................... 5412.1. Technical data Multi-turn actuators 5512.2. Technical data Actuator controls
6013. Spare parts............................................................................................................................. 6013.1. Multi-turn actuators SA 25.1–UW –SA 48.1–UW/SAR 25.1–UW –SAR 30.1–UW 6213.2. AC 01.2 actuator controls 6413.3. Wall bracket
6614. Certificates.............................................................................................................................. 6614.1. EU Declaration of Incorporation / Declaration of Conformity
67Index........................................................................................................................................
69Addresses...............................................................................................................................
3
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Table of contents
1. Safety instructions
1.1. Basic information on safety
Standards/directives Our products are designed and manufactured in compliance with recognised
standards and directives.This is certified in a Declaration of Incorporation and an
EU Declaration of Conformity.
The end user or the contractor must ensure that all legal requirements, directives,
guidelines, national regulations and recommendations with respect to assembly,
electrical connection, commissioning and operation are met at the place of installation.
Safetyinstructions/warn-
ings All personnel working with this device must be familiar with the safety and warning
instructions in this manual and observe the instructions given. Safety instructions
and warning signs on the device must be observed to avoid personal injury or property
damage.
Qualification of staff Assembly, electrical connection, commissioning, operation, and maintenance must
be carried out by suitably qualified personnel authorised by the end user or contractor
of the plant only.
Prior to working on this product, the staff must have thoroughly read and understood
these instructions and, furthermore, know and observe officially recognised rules
regarding occupational health and safety.
Commissioning Prior to commissioning, it is important to check that all settings meet the requirements
of the application. Incorrect settings might present a danger to the application, e.g.
cause damage to the valve or the installation.The manufacturer will not be held
liable for any consequential damage. Such risk lies entirely with the user.
Operation Prerequisites for safe and smooth operation:
●Correct transport, proper storage, mounting and installation, as well as careful
commissioning.
●Only operate the device if it is in perfect condition while observing these instruc-
tions.
●Immediately report any faults and damage and allow for corrective measures.
●Observe recognised rules for occupational health and safety.
●Observe national regulations.
●During operation,thehousing warms upandsurfacetemperatures >60°C may
occur.To prevent possible burns, we recommend checking the surface temper-
ature using an appropriate thermometer and wearing protective gloves, if re-
quired, prior to working on the device.
Protective measures The end user or the contractor are responsible for implementing required protective
measures on site, such as enclosures, barriers, or personal protective equipment
for the staff.
Maintenance To ensure safe device operation, the maintenance instructions included in this manual
must be observed.
Any device modification requires prior written consent of the manufacturer.
1.2. Range of application
AUMA multi-turn actuators are designed for the operation of industrial valves, e.g.
globe valves, gate valves, butterfly valves, and ball valves.
Other applications require explicit (written) confirmation by the manufacturer.
The following applications are not permitted, e.g.:
●Industrial trucks according to EN ISO 3691
●Lifting appliances according to EN 14502
●Passenger lifts according to DIN 15306 and 15309
●Service lifts according to EN 81-1/A1
4
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Safety instructions AC 01.2 Non-Intrusive
●Escalators
●Continuous duty
●Buried service
●Radiation exposed areas in nuclear power plants
No liability can be assumed for inappropriate or unintended use.
Observance of these operation instructions is considered as part of the device's
designated use.
Information These operation instructions are only valid for the "clockwise closing" standard
version, i.e. driven shaft turns clockwise to close the valve.
1.3. Warnings and notes
The following warnings draw special attention to safety-relevant procedures in these
operation instructions, each marked by the appropriate signal word (DANGER,
WARNING, CAUTION, NOTICE).
Indicates an imminently hazardous situation with a high level of risk. Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a medium level of risk.Failure
to observe this warning could result in death or serious injury.
Indicates a potentially hazardous situation with a low level of risk. Failure to
observe this warning may result in minor or moderate injury. May also be used
with property damage.
Potentially hazardous situation. Failure to observe this warning may result in
property damage. Is not used for personal injury.
Arrangement and typographic structure of the warnings
Type of hazard and respective source!
Potential consequence(s) in case of non-observance (option)
→Measures to avoid the danger
→Further measure(s)
Safety alert symbol warns of a potential personal injury hazard.
The signal word (here: DANGER) indicates the level of hazard.
1.4. References and symbols
The following references and symbols are used in these instructions:
Information The term Information preceding the text indicates important notes and information.
Symbol for CLOSED (valve closed)
Symbol for OPEN (valve open)
Important information before the next step.This symbol indicates what is required
for the next step or what has to be prepared or observed.
Via the menu to parameter
Describes the path within the menu to the parameter. By using the push buttons of
the local controls you may quickly find the desired parameter in the display.
5
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Safety instructions
< > Reference to other sections
Terms in brackets shown above refer to other sections of the document which provide
further information on this topic.These terms are either listed in the index, a heading
or in the table of contents and may easily be located.
6
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Safety instructions AC 01.2 Non-Intrusive
2. Identification
2.1. Name plate
Figure 1: Arrangement of name plates
[1] Actuator name plate
[2] Actuator controls name plate
[3] Motor name plate
[4] Additional plate, e.g. KKS plate (Power Plant Classification System)
Actuator name plate
Figure 2: Actuator name plate (example)
(= manufacturer logo); (= CE mark)
[1] Name of manufacturer
[2] Address of manufacturer
[3] Type designation
[4] Order number
[5] Actuator serial number
[6] Speed
[7] Torque range in direction CLOSE
[8] Torque range in direction OPEN
[9] Type of lubricant
[10] Permissible ambient temperature
[11] Can be assigned as an option upon customer request
[12] Enclosure protection
[13] Data Matrix code
7
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Identification
Actuator controls name plate
Figure 3: Actuator controls name plate
(= manufacturer logo); (= CE mark)
[1] Type designation
[2] Order number
[3] Serial number
[4] Actuator terminal plan
[5] Actuator controls terminal plan
[6] Mains voltage
[7] AUMA power class for switchgear
[8] Permissible ambient temperature
[9] Enclosure protection
[10] Control
[11] Data Matrix code
Motor name plate
Figure 4: Motor name plate (example)
(= manufacturer logo); (= CE mark)
[1] Motor type
[2] Motor article number
[3] Serial number
[4] Current type, mains voltage
[5] Rated power
[6] Rated current
[7] Type of duty
[8] Enclosure protection
[9] Motor protection (temperature protection)
[10] Insulation class
[11] Speed
[12] Power factor cos phi
[13] Mains frequency
[14] Data Matrix code
8
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Identification AC 01.2 Non-Intrusive
Descriptions referring to name plate indications
Type designation Figure 5:Type designation (example)
1. Actuator type, size and version
2. Flange size
Type, size and version
These instructions apply to the following devices types and sizes:
●Type SA = Multi-turn actuators for open-close duty
Sizes: 25.1, 30.1
Version: UW = for continuous underwater use
●Type SAR= Multi-turn actuators for modulating duty
Sizes: 25.1, 30.1
Version: UW = for continuous underwater use
●Type AC = AUMATIC actuator controls
Size and generation:01.2
Order number The product can be identified using this number and the technical data as well as
order-related data pertaining to the device can be requested.
Please always state this number for any product inquiries.
On the Internet at http://www.auma.com > Service & Support >myAUMA, we offer
a service allowing authorised users to download order-related documents such as
wiring diagramsandtechnical data (both inGerman and English), inspectioncertificate
and the operation instructions when entering the order number.
Actuator serial number Table 1:
Description of serial number (with example 0516MD12345)
MD123451605
Positions 1+2: Assembly in week = week 0505
Positions 3+4:Year of manufacture = 201616
Internal number for unambiguous product identificationMD12345
Actuator enclosure pro-
tection IP68-C15:The maximum permissible head of water is 15 m.
IP68-C60 (option): Head of water up to 60 m.
Actuator terminal plan Position 9 after TPA: Position transmitter version
I, Q = MWG (magnetic limit and torque transmitter)
AUMA power class for
switchgear The switchgear used in the actuator controls (reversing contactors/thyristors) are
classified according to AUMA power classes (e.g.A1, B1, ....).The power class
defines the max. permissible rated power (of the motor) the switchgear has been
designed for.The rated power (nominal power) of the actuator motor is indicated in
kW on the motor name plate.For the assignment of the AUMA power classes to the
nominal power of the motor types, refer to the separate electrical data sheets.
For switchgear without assignment to any power classes, the actuator controls name
plate does not indicate the power class but the max. rated power in kW.
Data Matrix code When registered as authorised user, you may use the AUMA Support App to scan
the Data Matrix code and directly access the order-related product documents without
having to enter order number or serial number.
9
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Identification
Figure 6: Link to the AUMA App:
For further Service & Support, software/apps/...refer to www.auma.com.
Control Table 2:
Control examples (indications on actuator controls name plate)
DescriptionInput signal
Control voltage 24V DC for OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
24 V DC
Control voltage 48V DC OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
48 V DC
Control voltage 60V DC OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
60 V DC
Control voltage 115V AC for OPEN - CLOSE control via digital inputs (OPEN,
STOP, CLOSE)
115 V AC
Input current for setpoint control via analogue input0/4 –20 mA
2.2. Short description
Multi-turn actuator Definition in compliance with EN 15714-2/EN ISO 5210:
A multi-turn actuator is an actuator which transmits torque to a valve for at least one
full revolution.It is capable of withstanding thrust.
AUMA multi-turn actuatorsSA25.1-UW–SA 30.1-UW/SAR 25.1-UW –SAR 30.1-UW
are driven by an electric motor. Switching off in end positions may be either by limit
or torque seating. Actuator controls are required to operate or process the actuator
signals.
Actuator controls AC 01.2 actuator controls are used to operate AUMA actuators and are supplied
ready for use. In combination with multi-turn actuators SA 25.1-UW –SA
30.1-UW/SAR 25.1-UW –SAR 30.1-UW, they are mounted separately on a wall
bracket.For high nominal motor currents of the actuator, the switchgear of the actuator
controls additionally require a control box.
The functions of actuator controls include standard valve control in OPEN-CLOSE
duty, positioning, process control, logging of operating data right through to diagnostic
functions.AC 01.2
Local controls/
AUMA CDT Operation, setting, and display can be performed directly at the actuator controls.
When set to local control, it is possible to
●operate the actuator via the local controls (push buttons and display) and perform
settings (contents of these instructions).
●read in or out data or modify and save settings via AUMA CDT software (ac-
cessory), using a computer (laptop or PC).The connection between computer
and actuator controls is wireless via Bluetooth interface (not included in these
instructions).
Non-Intrusive Non-Intrusive version (control unit: electronic):
Limit and torque setting is performed via the controls, without removal of actuator or
actuator controls covers.For this purpose, the actuator is equipped with an MWG
(magnetic limit and torque transmitter), also capable to supply analogue torque
feedback signals/torque indication and analogue position feedback signals/position
indication at the actuator controls output.
10
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Identification AC 01.2 Non-Intrusive
3. Transport, storage and packaging
3.1. Transport
For transport to place of installation, use sturdy packaging.
Hovering load!
Risk of death or serious injury.
→Do NOT stand below hovering load.
→Actuators mounted on valves: Attach ropes or hooks for the purpose of lifting
by hoist to valve and NOT to actuator.
→Actuatorsmounted togearboxes:Attach ropes or hooks forthe purposeof lifting
by hoist only to the gearbox using eyebolts and NOT to the actuator.
→Respect total weight of combination (actuator, gearbox, valve)
→Secure load against falling down, sliding or tilting.
→Perform lift trial at low height to eliminate any potential danger e.g.by tilting.
Figure 7: Example: Lifting the actuator using an eyebolt
Table 3:
Weight Multi-turn actuators SA 25.1–UW –SA 30.1–UW/SAR 25.1–UW –SAR 30.1–UW
with 3-phase AC motors
Weight2)
Motor type1)
Type designation
Actuator approx. [kg]
166AD... 90-...SA 25.1-UW/
SAR 25.1-UW 178AD... 132-...
220AD... 112-...SA 30.1-UW/
SAR 30.1-UW 290AD... 160-...
Refer to motor name plate1) Indicated weight includes AUMA NORM multi-turn actuator with 3-phase AC motor, electrical con-
nection or plug/socket connector incl.cable glands (approx.2.3 kg) as well as output drive type B1.
2)
Forother output drive types, heed additional weights.Heedweight of cablesifplug/socket connector
is linked.
11
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Transport, storage and packaging
3.2. Storage
Danger of corrosion due to inappropriate storage!
→Store in a well-ventilated, dry room.
→Protect against floor dampness by storage on a shelf or on a wooden pallet.
→Cover to protect against dust and dirt.
→Apply suitable corrosion protection agent to uncoated surfaces.
Damage on display caused by temperatures below permissible level!
→AC actuator controls MUST NOT be stored below –30 °C.
Long-term storage For long-term storage (more than 6 months), observe the following points:
1. Prior to storage:
Protect uncoated surfaces, in particular the output drive parts and mounting
surface, with long-term corrosion protection agent.
2. At an interval of approx. 6 months:
Check for corrosion.If first signs of corrosion show, apply new corrosion protec-
tion.
3.3. Packaging
Our products are protected by special packaging for transport when leaving the
factory.The packaging consists of environmentally friendly materials which can easily
be separated and recycled.We use the following packaging materials: wood,
cardboard, paper, and PE foil.For the disposal of the packaging material, we
recommend recycling and collection centres.
12
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Transport, storage and packaging AC 01.2 Non-Intrusive
4. Assembly
4.1. Mounting position
The product described in this document can be operated without restriction in any
mounting position.
4.2. Multi-turn actuator: mount to valve/gearbox
Danger of corrosion due to damage to paint finish and condensation!
→Touch up damage to paint finish after work on the device.
→After mounting, connect the device immediately to electrical mains to ensure
that heater minimises condensation.
4.2.1. Output drive types B
Application ●For rotating, non-rising valve stem
●Not capable of withstanding thrust
Design For output drive types B/B1/B2, the connection to the valve or the gearbox is made
by directly placing the multi-turn actuator solid shaft (output drive shaft) onto the
input shaft of the valve or gearbox.
For output drive types B3/B4/E, the connection is made via output drive sleeve which
is inserted into the bore of the solid shaft of the multi-turn actuator and fixed by a
retaining ring.
When exchanging the output drive sleeve, later retrofitting to a different output drive
type is possible
Figure 8: Output drive type B
[1] Multi-turn actuator flange
[2] For output drive types B/B1/B2 hollow shaft with keyway
[2]* For output drive types B3/B4/E, an output drive sleeve is fitted into the hollow
shaft
[3] Gearbox/valve shaft with parallel key
Information Spigot at valve flanges should be loose fit.
13
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Assembly
4.2.1.1. Multi-turn actuator with output drive types B: mount to valve/gearbox
Figure 9: Mounting output drive types B
[1] Multi-turn actuator
[2] Valve/gearbox
[3] Valve/gearbox shaft
1. Check if mounting flanges fit together.
2. Check if output drive of multi-turn actuator [1] matches the output drive of
valve/gearbox or valve/gearbox valve shaft [2/3].
3. Apply a small quantity of grease to the valve or gearbox shaft [3].
4. Fit multi-turn actuator [1].
Information: Ensure that the spigot fits uniformly in the recess and that the
mounting faces are in complete contact.
5. Fasten multi-turn actuator with screws according to table.
Information: We recommend applying liquid thread sealing material to the
screws to avoid contact corrosion.
6. Fasten screws crosswise to a torque according to table.
Table 4:
Tightening torques for screws
Tightening torque [Nm]Threads
Strength class
A2-808.8
200214M16
392431M20
1,4221,489M30
2,4812,594M36
14
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Assembly AC 01.2 Non-Intrusive
4.3. Mounting positions of local controls
Figure 10: Mounting positions
The mounting position of the local controls is implemented according to the order.
If, after mounting the actuator to the valve or the gearbox on site, the local controls
are in an unfavourable position, the mounting position can be changed at a later
date.Four mounting positions shifted by respectively 90° are possible (by maximum
180° into one direction).
4.3.1. Mounting positions: modify
Hazardous voltage!
Risk of electric shock.
→Disconnect device from the mains before opening.
Electrostatic discharge ESD!
Risk of damage to electronic components.
→Earth both operators and devices.
1. Loosen screws and remove the local controls.
2. Check whether O-ring is in good condition, correctly insert O-ring.
3. Turn local controls into new position and re-place.
Cable damage due to twisting or pinching!
Risk of functional failures.
→Turn local controls by a maximum of 180°.
→Carefully assemble local controls to avoid pinching the cables.
4. Fasten screws evenly crosswise.
15
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Assembly
5. Electrical connection
5.1. Basic information
Danger due to incorrect electrical connection
Failure to observe this warning can result in death, serious injury, or property damage.
→The electrical connection must be carried out exclusively by suitably qualified
personnel.
→Prior to connection, observe basic information contained in this chapter.
→After connection but prior to applying the voltage, observe the <Commissioning>
and <Test run> chapters.
Wiring diagram/terminal
plan The pertaining wiring diagram/terminal plan (in German or English) is attached to
the device in a weather-proof bag, together with these operation instructions.It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks
(supply networks) Actuator controls (actuators) are suitable for use inTN andTT networks with directly
earthed star point for mains voltage up to maximum 690V AC. Use in IT networks
for nominal voltages up to maximum 600 V AC are permissible.For IT network, a
suitable, approved insulation monitor measuring the pulse code is required.
Current type, mains
voltage, mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
actuator controls and motor name plates.Also refer to chapter <Identification>/<Name
plate>.
Figure 11: Motor name plate (example)
[1] Type of current
[2] Mains voltage
[3] Mains frequency (for 3-phase and 1-phase AC motors)
Protection and sizing on
site For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
The current values for sizing the protection can be derived from the current
consumption of the motor (refer to motor name plate) plus the current consumption
of actuator controls.
We recommend adapting the switchgear sizing to the max.current (Imax) and selecting
and setting the overcurrent protection device in compliance with the indications in
the electrical data sheet.
Table 5:
Current consumption of actuator controls
Max. current consumptionMains voltage
–30 %±10 %Permissible variation of the mains voltage
1,000 mA750 mA100 to 120 V AC
750 mA400 mA208 to 240 V AC
400 mA250 mA380 to 500 V AC
400 mA200 mA515 to 690 V AC
16
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Electrical connection AC 01.2 Non-Intrusive
Table 6:
Maximum permissible protection
max. protectionRated powerSwitchgear
(switchgear with power class)1)
16 A (gL/gG)up to 1.5 kWReversing contactor A1
32 A (gL/gG)up to 7.5 kWReversing contactor A2
63 A (gL/gG)up to 15 kWReversing contactor A3
125A (gL/gG)up to 30 kWReversing contactor A4 (in control box)
200A (gL/gG)up to 55 kWReversing contactor A5 (in control box)
315A (gL/gG)up to 75 kWReversing contactor A6 (in control box)
16 A (g/R) I²t<1,500A²sup to 1.5 kWThyristor B1
32 A (g/R) I²t<1,500A²sup to 3 kWThyristor B2
63 A (g/R) I²t<5,000A²sup to 5.5 kWThyristor B3
The AUMA power class (A1, B1, ...) is indicated on the actuator controls name plate1)
Considerthe motor starting current (IA) (referto electricaldata sheet) when selecting
the circuit breaker.We recommend tripping characteristics D or K for circuit breakers
in accordance with IEC 60947-2. For controls with thyristors, we recommend safety
fuses instead of circuit breakers.
For actuator controls equipped with a heating system and external electronics power
supply, the fuses for the heating system have to be provided by the customer (refer
to wiring diagram F4 ext.)
Table 7:
Fuse for heating system
Designation in wiring diagram = F4 ext.
230 V AC115 V ACExternal power supply
1 A T2 A TFuse
Potential of customer
connections All input signals (control inputs) must be supplied with the same potential.
All output signals (status signals) must be supplied with the same potential.
Safety standards Safety measures and safety equipment must comply with the respectively valid
national on site specifications.All externally connected devices shall comply with
the relevant safety standards for the place of installation.
Connecting cables ●We recommend using connecting cables and connecting terminals according
to rated current (IN) (refer to motor name plate or electrical data sheet).
●For device insulation, appropriate (voltage-proof) cables must be used.Specify
cables for the highest occurring rated voltage.
●Use connecting cable with appropriate minimum rated temperature.
●For connecting cables exposed to UV radiation (outdoor installation), use UV
resistant cables.
●For the connection of position transmitters, screened cables must be used.
Cable installation in ac-
cordance with EMC Signal and fieldbus cables are susceptible to interference. Motor cables are
interference sources.
●Lay cables being susceptible to interference or sources of interference at the
highest possible distance from each other.
●The interference immunity of signal and fieldbus cables increases if the cables
are laid close to the earth potential.
●If possible, avoid laying long cables and make sure that they are installed in
areas being subject to low interference.
●Avoid parallel paths with little cable distance of cables being either susceptible
to interference or interference sources.
17
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Electrical connection
5.2. Cable installation between actuator controls (wall bracket) and actuator
Figure 12: Example of cable installation for actuator controls –wall bracket
[1] Electrical connection (S/SH) of actuator controls
[2] Wall bracket
[3] Plug/socket connector for wall bracket
[4] Connecting cables (LSW 68 or LSW 69)
[5] Plug/socket connector for actuator
[6] Fixing the connecting cables (example)
[7] DS intermediate frame (option)
Wall bracket
Actuatorcontrols are alwaysmounted separatelyfrom the actuatoron a wall bracket,
outside the flooded area.
When mounting actuator controls outside the flooded area but below water level, we
recommend using the DS intermediate double sealed frame between wall bracket
and plug/socket connector.
18
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Electrical connection AC 01.2 Non-Intrusive
Version with control box
Figure 13: Example of cable installation with control box
[1] Electrical connection (SD) of actuator controls
[2] Wall bracket
[3] Plug/socket connector for wall bracket
[4a] Connecting cable between motor and control box (LS 36)
[4b] Connecting cable between actuator and wall bracket (LSW 75 or LSW 76)
[5] Plug/socket connector for actuator
[6] Fixing the connecting cables (example)
[7] DS intermediate frame (option)
For actuators with high nominal motor current (AUMA power class switchgear from
category A4), a control box is additionally required.Switchgear (reversing contactors)
will then be installed in the control box and not within the actuator controls. Control
box is mounted separately on the wall.
Danger of short-circuit!
In case of incorrect assembly, water may ingress the control box by flowing along
the cable.
→Mount control box outside the flooded area above the maximum possible water
level.
For the power supply cable, fuses have to be provided for short-circuit protection by
the customer.The fuses have to be adapted to the cross section of the cable, the
thermal overload relay in the control box, the switch contacts and the motor data
(refer to motor name plate).
19
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
AC 01.2 Non-Intrusive Electrical connection
Connecting cables
●Connecting cables must be protected against damage and securely fixed.The
plant operator or the contractor are responsible for providing the required cable
protection.
●The permissible cable length between actuator controls on wall bracket and
the actuator amounts to 100 m maximum.
●Exclusively use AUMA “LSW”cable sets as connecting cables “LSW and LS”!
Table 8:
AUMA cable sets
LSW 69 (without control box)
LSW 76 (with control box)
LS 36 (with control box)
LSW 68 (without control box)
LSW 75 (with control box)
Ready-made
Tested for leak tightness
Ready-made
Tested for leak tightness
Plug/socket con-
nector for actuator
Connector wiring to be performed by the cus-
tomer
LSW 69/76: open cable to wall bracket
LS 36: open cable to control box
Ready-madePlug/socket con-
nector for wall
bracket
●For LSW 69/76 cable sets, the plug/socket connector must be opened at wall
bracket level and the cables must be connected to the pin carrier according to
the terminal plan.Appropriate crimping pliers are required for orderly crimping.
Suitable pliers are available at AUMA (art. no. K007.979).
Figure 14: Connection example using LSW 69/76
[1] Cover for wall bracket plug/socket connector1)
[2] Pin carrier for crimp pin contacts
[3] Pin contacts (included in LSW 69/76 scope of delivery)
Table 9: Calibration pin Ø[mm]
Crimp rangeUnitsPin contacts forArt.no.
2.002.503Motor cablesZ030.022
1.600.75 –1.58Control contacts of hybrid cableZ006.161-1
0.5 –0.550.5 –0.554CAN contacts of hybrid cableZ041.602
●When connecting, make sure that the shield of both connecting cables is suffi-
ciently overlapping (approx.2 mm over the O-ring) the contact socket of the
cable gland.
1) For connection with cable set LSW 76 (in combination with wall bracket) only one cable (hybrid
cable) is available at plug/socket connector.The motor cable is then directly led from the actuator
vis LS 36 to the control box.
20
SA 25.1-UW –SA 30.1-UW / SAR 25.1-UW –SAR 30.1-UW Control unit: electronic (MWG)
Electrical connection AC 01.2 Non-Intrusive

This manual suits for next models

3

Other AUMA Controllers manuals

AUMA SA Series User manual

AUMA

AUMA SA Series User manual

AUMA SQ 05.2 User manual

AUMA

AUMA SQ 05.2 User manual

AUMA SQ 14.2 User manual

AUMA

AUMA SQ 14.2 User manual

AUMA SA 3 User manual

AUMA

AUMA SA 3 User manual

AUMA AUMATIC AC 01.2 Manual

AUMA

AUMA AUMATIC AC 01.2 Manual

AUMA Aumatic ACExC 01.1 User manual

AUMA

AUMA Aumatic ACExC 01.1 User manual

AUMA SA 07.1 - SA 30.1 User manual

AUMA

AUMA SA 07.1 - SA 30.1 User manual

AUMA SAExC 07.1 User manual

AUMA

AUMA SAExC 07.1 User manual

AUMA Aumatic AC 01.1 User manual

AUMA

AUMA Aumatic AC 01.1 User manual

AUMA SA 25.1 User manual

AUMA

AUMA SA 25.1 User manual

AUMA SQ 05.2 User manual

AUMA

AUMA SQ 05.2 User manual

AUMA AUMATIC ACExC User manual

AUMA

AUMA AUMATIC ACExC User manual

AUMA SQEx 05.2 User manual

AUMA

AUMA SQEx 05.2 User manual

AUMA SG 05.1-FA07 User manual

AUMA

AUMA SG 05.1-FA07 User manual

AUMA SQEx 05.2 User manual

AUMA

AUMA SQEx 05.2 User manual

AUMA SG 05.1-F05 User manual

AUMA

AUMA SG 05.1-F05 User manual

AUMA AMB 01.1 User manual

AUMA

AUMA AMB 01.1 User manual

AUMA SQ 05.2 User manual

AUMA

AUMA SQ 05.2 User manual

AUMA SA 07.1 User manual

AUMA

AUMA SA 07.1 User manual

AUMA SA 25.1 User manual

AUMA

AUMA SA 25.1 User manual

AUMA SGExC 05.1 User manual

AUMA

AUMA SGExC 05.1 User manual

AUMA SAEx 07.2 User manual

AUMA

AUMA SAEx 07.2 User manual

AUMA SGM 04.1 User manual

AUMA

AUMA SGM 04.1 User manual

AUMA SQEx 05.2 User manual

AUMA

AUMA SQEx 05.2 User manual

Popular Controllers manuals by other brands

ADVATEK LIGHTING PixLite E4-S Mk3 quick start guide

ADVATEK LIGHTING

ADVATEK LIGHTING PixLite E4-S Mk3 quick start guide

Nordic DELTACO SH-OW02 user manual

Nordic

Nordic DELTACO SH-OW02 user manual

MOBILUS MOTOR mob.iq [RHM] user manual

MOBILUS MOTOR

MOBILUS MOTOR mob.iq [RHM] user manual

Belimo CR24 Series manual

Belimo

Belimo CR24 Series manual

Hayward OmniPL HLBPRO4SW Operation manual

Hayward

Hayward OmniPL HLBPRO4SW Operation manual

Varian Turbo-V 70 instruction manual

Varian

Varian Turbo-V 70 instruction manual

Altera Enpirion EN63A0QI user guide

Altera

Altera Enpirion EN63A0QI user guide

Kutai electronics EA63-2.5 Operation manual

Kutai electronics

Kutai electronics EA63-2.5 Operation manual

Panasonic AFP7MC16EC user manual

Panasonic

Panasonic AFP7MC16EC user manual

Horstmann ChannelPlus H27ZXL Series 2 User operating instructions

Horstmann

Horstmann ChannelPlus H27ZXL Series 2 User operating instructions

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS... Installation and operation manual

THOMSON

THOMSON MEC 310#GENSET CONTROLLER OPTION J-CANBUS... Installation and operation manual

LinMot E1200-GP-UC installation guide

LinMot

LinMot E1200-GP-UC installation guide

Mitsubishi Electric AE-200A installation manual

Mitsubishi Electric

Mitsubishi Electric AE-200A installation manual

Emerson FB3000 Field installation guide

Emerson

Emerson FB3000 Field installation guide

Emerson Dixell XR20T operating instructions

Emerson

Emerson Dixell XR20T operating instructions

Eaton PKZM01 Series Instruction leaflet

Eaton

Eaton PKZM01 Series Instruction leaflet

PI P-843 user manual

PI

PI P-843 user manual

GEM 1242PTAZ Assembly instructions

GEM

GEM 1242PTAZ Assembly instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.