ENDA ERPA Series User manual

ERPA1-E-10052019
1. / 4
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N
ENVIRONMENTAL CONDITIONS
Ambient/storage temperature
Relative humidity
Pollution degree
Overvoltage category
Altitude
Protection
OUTPUT
INPUT
GENERAL
ERPA1-240-F
40
180 - 280
150
400
1,6
5
880
50 - 60
>0,75
160
0/4-20mA, 0/1-5V DC, 0/2-10V DC or ~ 10k potentiometer. (Device may be damaged at 12V DC and above voltages).
≥ ≥0,2mA (for mA input), 0,08V (for V input).
≤ ≤0,18mA (for mA input), 0,075V (for V input).
15ms.
≤ ≥100 (for mA input), 10k (for V input).Ω
Protection feature for reverse connection is available.
ERPA1-xxx-F-xx
90-250V AC, 50/60Hz.
W46 x H110 x D117mm (for ERPA1-x40-F and ERPA1-550-F) , W79 x H120 x D132mm (for ERPA1-570-F).
Approx. 450g (for ERPA1-x40-F and ERPA1-550-F) , Approx. 550g (for ERPA1-570-F) (boxed).
2500 Vrms between I/O terminals for 1 min.
For power line 16mm² cable (with 25mm² cable terminal) cable, for signal line can be connected 4mm² cable.
Max. 1,2Nm.
EN 60947-4-3
Rail mountable (EN60715,TH35 or G-32).
Self extinguishing plastics (According to EN 60695-11-10 V-O).
Fan is controlled with thermostat and works at temperatures over 50°C.
ERPA1-440-F
40
180 - 480
110
290
1,8
8
610
50 - 60
>0,75
200
ERPA1-550-F
50
180
270
10
720
300
180 - 500
1,8
50 - 60
>0,75
3A, 250V AC, NO or NC can be selected by program.
ERPA1-570-F
70
400
600
15
4000
400
Order Code
Load Current, AC51/25ºC (Arms)
Load Voltage (Vrms)
Overload Current t=1s/25°C (Arms)
Non rep. Surge current/25°C (Arms)
On-state Voltage Drop (Vrms)
Leakage Current (mArms)
I²t for Fusing t=10ms (A²s)
Frequency (Hz)
Power Factor (Cos )Φ
Minimum Operating Current (mArms)
Alarm Output
Input Signal
Transmission Signal
Drop-out Signal
Turn-on Time
Dynamic Input Impedance
Protection
Order code
Power supply
Dimensions
Weight
Isolation Voltage
Connection
Terminal screw torque
Product standard
Mounting
Enclosure material
Fa n (Optional)
ORDER CODE
Thank you for choosing eries power regulators.ENDA ERPA1 S
ERP A 1 - 5 50 - F - V - RS
ENDA ERPA Series Power Regulators1
Product Basic Code
ERPRail Mounted
Fan (*)
Fan F
Communication (*)
RS485 ModBus RS
Blank (N/A) or
Load Voltage
AC A
Number of Pole
1Single pole
Load Current
40A AC 40
50A AC 50
70A AC 70
Load Voltage
180 - 280V AC 2
180 - 480V AC 4
180 - 500V AC 5
Please rea this document carefully before using this product. The guarantee will be invalidated if the device is damaged by
not following instructions detailed in the manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
- A A40 -50 -70AAC oad current.L
- V V280 -480 -500V AC oad voltage.L
-0/4-20mA, 0/1-5V DC, 0/2-10V DC or 1kΩ ~ 10kΩ otentiometer input.P
-4 Digits LED display.
-Phase angel or zero-cross controlled.
-Soft Start or Kick Start feature.
-Overheat alarm output.
-Varistor protection for peak voltages.
-RS485 ModBus ommunication feature (Optional).C
CE arked according to European Norms.M-
Optional features should
be specified at order.
Do not use the device in locations subject to corrosive and flammable gases.
While cleaning the device, solvents (thinner, , acid etc.) or corrosive materials must not be used.gasoline
90% Relative humidity for temperatures up to 20 % °C, decreasing linearly to 50% at 40°C. (Shouldn't be condensation).
-25... +60 °C / -30... +100 °C (Shouldn't be icing and condensation in ambient.)
2
II
Max. 1000m.
IP20 According to EN60529
█
Vibration Control (*)
Vibration Control V
Blank (N/A) or
█
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N 2. / 4
ENDA
ERPA1
POWER
REGULATOR
SET
16mm
111mm 126mm
1
2
46mm 46mm
79mm
72mm
6mm 6mm
1
2
ENDA
ERPA1
POWER
REGULATOR
SET
1 2
345
10 9
8
76
1 2
345
10 9
8
76
DIMENSIONS
- To remove the device from panel ;
Pull up the device in direction 1
- To mount the device from panel ;
Pull up the device in direction 2
- To remove the device from panel ;
Pull up the device in direction 1
- To mount the device from panel ;
Pull up the device in direction 2
APPLICATIONS
ERPA1-240-F ERPA1-440-F-RS
ERPA1-240-F , ERPA1-440-F , ERPA1-550-F ERPA1-570-F
While assembling, there must be at
least 25mm clearance between the
devices.
Load
Alarm
Out Alarm
Out
Supply
90-250VAC Supply
90-250VAC
0/4-20mA
or
0-10V
- +
0/4-20mA
or
0-10V
- +
1k to 10kΩ Ω 1k to 10kΩ Ω
Potentiometer Potentiometer
180-280VAC
A
B
COM
{
Rs485
ModBus
ENDA
ERPA1
POWER
REGULATOR
SET
A
B
COM
Rs485
ModBus
ENDA
ERPA1
POWER
REGULATOR
SET
L
N
Load
180-480VAC L2
L1
ERPA1
POWER
REGULATOR
LOAD
40A
180-480VAC
MADE IN TURKEY SN : 140335045
ENDA
INDUSTRIALELECTRONICS
ERPA1-440-F-RS
POWER REGULATOR
ALARM
OUT
8 6804 0 7 714063
A
B
COM
Rs485
ModBus
A
B
COM
SUPPLY
90-250VAC
50/60Hz
7VA
1k to 10kΩ Ω
0-10V
0/4-20mA
+
_
~
L1
L2
SUPPLY
90-250VAC
50/60Hz
7VA
MADE IN TURKEY SN : 140335044
ENDA
INDUSTRIAL ELECTRONICS
ERPA1-240-F
POWER REGULATOR
ERPA1
POWER
REGULATOR
ALARM
OUT
1k to 10kΩ Ω
0-10V
0/4-20mA
+
8 6804 0 7 713981
_
~
LOAD
40A
180-280VAC
N
L
1 2
345
10 9
8
76
1 2
345
10 9
8
76
ERPA1-E-10052019
3. / 4
SET SET
SET
Running
Mode
a. 3.0
o. 30
diSp. curr.=
Output as
Current.
diSp. out=
Output as
Percentage.
SET
Communication Mode
Or ; if pressed and than keys, access to menu headers are entered. By pressing and than keys are pressed together, information is saved and returns to
Run Mode.
In "Running Mode", by held down to and then pressed to key, "Programming Mode" is entered. If no key is pressed during in "Programming Mode" for 20 seconds,
adjusted parameter(s) (if any) is stored and returned to the "Running Mode".
SET
++
If key is pressed in Run Mode for seconds, Run Mode is entered.“ ning ” “manual ning ” Manual output value flashes and3
desired value keyscan be selected by using navigation . By pressing the key, value is set and “Running Mode” is
entered.
SET
SET
SET
SET
Manual Running Mode
m. 50 m. 51 m. 50
*
SET
t0 r t 0r
Device starts in
“Running Mode"
every power-up.
PARAMETER TABLE
inp. 4 20
Parameter Options
/ [units] Description
0 20
conf. Configuration menu
0 10
1 5
2 10
0 5
pot.
manu.
4-20mA
0-20mA
0-10V
1-5V
2-10V
0-5V
Potentiometer input.
Manual Run Mode.
disp. out
curr.
Output as Percentage in Run Mode.
Output as Current in Run Mode.
c.typ. phaS.
croS.
Control with phase angle.
Control with Zero-cross.
St.ti.
Soft
ic.St.
Output is energized with soft start.
Output is energized with kick start.
al.ou. no.
nc.
Alarm relay normally open.
Alarm relay normally closed.
Err.c. auto
Stop
Returns to Run Mode when error disappeares.
Remains in Eror Mode when error disappeares.
out.c. Output Control Menu
ou.hi. Takes a value between and .ou.lo. 100
ou.lo. Takes a value between and .0 . ou.hi
cu.hi. Takes a value between and load current.0
Start duration (0 - 200).
ou.of. Takes a value between and .-50. 50
[Ampere]
[Second]
[%]
[%]
[%]
conn. Communication Menu (*)
d.adr. Takes a value between and .1. 247
baud 1200 2400 4800 9600 9200, , , and values are selectable.1
5ECU Security Menu
a.con. Configuration menu invisible.
Configuration menu can be changed.
Only configuration menu visible.
a.out. Output control menu invisible.
Output control menu can be changed.
Only Output control menu visible.
Communication menu invisible.
Communication can be changed.
Only communication menu visible.
(*) This menu is only available on ModBus featured devices.
(**) Takes 40, 50 or 70 values for according to device models.
Input selection.
Programming Mode
inp.
Control type
selection.
c.typ.
Start type
selection.
st.ty.
Display selection
in “Running Mode”
disp.
st.ti.
Alarm relay
selection.
Data menu security
parameter.
A.out..
Communication menu
security parameter.
A.cnn.
A.con. Control menu security
parameter.
codE. Security menu access
code is 124.
baud
d.adr.
Max. acceptable
value for output.
Min. acceptable
value for output.
ou.hi.
ou.lo. Modbus speed.
Modbus address.
Start duration.
ou.of.
If parameter is set as , only when key is pressed, If parameter is set as , whenErr.c stop Err.c auto
key is pressed or when the error disappeared, it returns to Run Mode. When return to the operating mode,
if overheating continues device passes to the error Mode.
Output offset value.
Err.c. Quit method
from error status.
conf.
al.ou.
out.c. conn.
SET
SET
sECU. St.ty.
nonE
p.yES
p.no
nonE
p.yES
p.no
a.cnn. nonE
p.yES
p.no
Default
values
out
phaS.
Soft
4
no.
auto
p.yES
p.yES
p.yES
100
0
If key is held down while the device is powered up, message willd.PAr
appears on display and factory settings will be restored.
0
1
9600
If held down key, the selected parameter will flash and can be adjusted to desired value with the keys.
Parameter Adjustment Method
If keys are pressed for 0.4 seconds then the parameter is changed faster.
SET
SET
SET SET SET SET
cu.hi.
+ + + +
(**)
0 10
(If = ) disP. curr.
Max. current value for
connected load
in selectioncurr. ERPA does not measures the load current. It indicates
the calculated current value for according to the entered
cu.hi. parameter.
Psc
Err.1
When the device overheats, appears on display and enters to error mode and alarm relay triggers.Err.1
Error Messages
Psc
Err.2
If input values are selected as 4-20 or 0-20 and if above current flows, Err.2 appears on display and enters
to error mode and alarm relay triggers.
Psc
Err.3
*
If input value is selected as and if master device not response for 15 seconds,m.bus Err.3 appears on display
and enters to error mode and alarm relay triggers.
m.bus. Modbus input
m.sft. Output is energized with soft start according to manual output value.
m.ic.S. Output is energized with kick start according to manual output value.
If key is pressed in Run Mode for seconds, Mode is entered.“ ning ” “Communication ” By pressing the key, “Running3
Mode” is entered. " " sign, point the communication status. During data received from Modbus, " " blinks at the left side of "0 0
r 0 t" and during data transmitted from Modbus, " " blinks at the right of the " ".
ModBus Connection Diagram 120 Ohm
Master Slave - 1 Up to 127 Slave devices
can be controlled.
Slave - 2 Slave
127
-
A
B
-
A
B
-
A
B
120 Ohm Terminating resistors should be added
-
A
B
E-mail : info@suran-elektronik.de
Internet : www.suran-elektronik.de
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
SURAN Industrieelektronik
Dettinger Str. 9 / D-72160 Horb a.N 4. / 4
Holding Register
addresses
Decimal (Hex) Data
type Data content Parameter
Name Read / Write
permission
inp.
disp.
st.ti.
ou.hi.
ou.lo.
cu.hi.
ou.of.
A.con.
A.out.
A.cnn.
d.adr.
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
R / W
Input selection (0: 4-20mA, 1: 0-20mA, 2: 0-10V, 3: 1-5V, 4: 2-10V,
5: 0-5V, 6: potentiometer, 7: manual, 8: Modbus).
Display selection on Running Mode (0: output as percent,
1: output as current, 2: set manually in percent output).
Kick-Soft start duration (adjustable between 0 and 200 seconds).
Max. acceptable value for output. Acceptable between and .( )ou.lo. 100
Modbus device address (adjustable between 0 and 247).
Max. output current. (Acceptable value between 0 and load current).
Output offset value. (Adjustable between -50 and 50).
Security parameter for configuration menu (0: Menu invisible,
1: Menu programmable 2: Only configuration menu visible).
Output parameter for configuration menu (0:Menu invisible,
1: Menu programmable 2: Only configuration menu visible).
Communication parameter for configuration menu (0: Menu invisible,
1: Menu programmable 2: Only configuration menu visible).
Modbus input (adjustable between and ).ou.lo. ou.hi.
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
Byte
0012d (000Ch)
0011d (000Bh)
0010d (000Ah)
0009d (0009h)
0008d (0008h)
0007d (0007h)
0006d (0006h)
0005d (0005h)
0004d (0004h)
0003d (0003h)
0002d (0002h)
0001d (0001h)
0000d (0000h)
1.1 Memory Map for Holding Registers
1.2 Memory Map for Coils
Coil addresses
Input register address
Data
Type Data content Parameter
Name
c.typ.
a.lou.
--
Err.c.
R / W
Only Readable
R / W
R / W
Control selection type (0: Phase angel, 1: Zero-cross)
Min. acceptable value for output. (acceptable between and ).0ou.hi.
Output value as percent
Alarm relay selection (0: NO, 1: NC)
Alarm control management (0: Returns to Run Mode when error
disappeares., 1: Remains in Eror Mode when error disappeares.)
Bit
Byte
Bit
Bit
(0000)h
(0000)h
(0001)h
(0002)h
1.3 Memory Map for Input Registers
--
Byte
ENDA ERPA1 MODBUS PROTOCOL ADDRESS MAP
Read / Write
permission
Data content Parameter
Name Read / Write
permission
Only Readable
Current value as percent
Output rate %20 Output rate %20
Output rate %50 Output rate %50
Output rate %80 Output rate %80
It is a proportional control method used in inductive and variable resistive loads
(cosØ <1). The disadvantage of this method is that it causes high electrical noise. It is a control method used in capacitive and variable resistive loads (cosØ =1).
The advantage of this method is that it does not causes high electrical noise.
With Phase Angle Control With Zero-Crossing Control
Start Method
t : Start time ( )St.ti.
Output
Ratio
Max. 100 Max. 100
0 0
t tSecond
Soft Start Kick Start
Output Ratio : Manually set or changed
by the input signal is
output as a percentage.
Out
%
Control Method
Out
%
Output
Ratio
Second
Output Ratio : Manually set or changed
by the input signal is
output as a percentage.
t : Start time ( )St.ti.
baud R / W
Modbus baud rate (0: 1200, 1: 2400, 2: 4800, 3: 9600, 4: 19200)
Byte
00 d (000 h)13 D
st.ty. R / W
Start type selection. ( 0 : Soft Start according to input signal. 1 : Kick Start according to
input signal. 2 : Soft Start according to manual output. 3 : Kick Start according to manual output ).
Note : Modbus default Parity and Data Bits settings can not be changed. (Parity : None. Data Bits : 8)
Data
Type

This manual suits for next models

6

Other ENDA Controllers manuals

ENDA EDT2423A User manual

ENDA

ENDA EDT2423A User manual

ENDA EUC942 User manual

ENDA

ENDA EUC942 User manual

ENDA ELC-186RT User manual

ENDA

ENDA ELC-186RT User manual

ENDA ELC-286RT User manual

ENDA

ENDA ELC-286RT User manual

ENDA EUP1122 User manual

ENDA

ENDA EUP1122 User manual

ENDA EU4430 User manual

ENDA

ENDA EU4430 User manual

ENDA ET4420 User manual

ENDA

ENDA ET4420 User manual

ENDA ETC4420 User manual

ENDA

ENDA ETC4420 User manual

ENDA EDT3011 Series User manual

ENDA

ENDA EDT3011 Series User manual

ENDA ETC 4420 User manual

ENDA

ENDA ETC 4420 User manual

ENDA ET2412 User manual

ENDA

ENDA ET2412 User manual

Popular Controllers manuals by other brands

ELPRO ERRTS ALERT2 Configuration manual

ELPRO

ELPRO ERRTS ALERT2 Configuration manual

Johnson Controls M9203-AG-2 Series installation guide

Johnson Controls

Johnson Controls M9203-AG-2 Series installation guide

F&F STR-1 quick start guide

F&F

F&F STR-1 quick start guide

Kamoer KICC2 quick start guide

Kamoer

Kamoer KICC2 quick start guide

Hubbell Electric Fire Pump Controllers LXi 2100 Specifications

Hubbell

Hubbell Electric Fire Pump Controllers LXi 2100 Specifications

Deger MLD Control Energy Converter S1 Assembly instructions

Deger

Deger MLD Control Energy Converter S1 Assembly instructions

Consort CRXSL-01 Installation and user guide

Consort

Consort CRXSL-01 Installation and user guide

Toro EVOLUTION Series quick start guide

Toro

Toro EVOLUTION Series quick start guide

Sven VR-L600 user manual

Sven

Sven VR-L600 user manual

New Digital VIN6038-NYCTA user manual

New Digital

New Digital VIN6038-NYCTA user manual

RIESE SAFE 4 eco Original Operating Instruction

RIESE

RIESE SAFE 4 eco Original Operating Instruction

Critical Environment Technologies FCS-M Series Operation manual

Critical Environment Technologies

Critical Environment Technologies FCS-M Series Operation manual

Slide Kamera AION IQ user manual

Slide Kamera

Slide Kamera AION IQ user manual

Northern PTZKBD3 user manual

Northern

Northern PTZKBD3 user manual

Audiophony PA WP8 user guide

Audiophony PA

Audiophony PA WP8 user guide

VPro LAX Series instruction manual

VPro

VPro LAX Series instruction manual

Emerson KEYSTONE FIGURE 738 Repair and maintenance instructions

Emerson

Emerson KEYSTONE FIGURE 738 Repair and maintenance instructions

Samson TROVIS 5757-7 Mounting and operating instructions

Samson

Samson TROVIS 5757-7 Mounting and operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.