H-4
TF3 Series
TF3 Series
Remote display unit [TFD]
※1: The weight includes packaging. The weight in parentheses is for unit only.
The weight is varied by model option.
※Environment resistance is rated at no freezing or condensation.
Model TFD-3 TFD-5
Power supply 3.3VDCᜡ
Power consumption Max. 1W
Display method 7 Segment LED method (red)
Communication method Serial (TTL Level), Half duplex
Communication cycle 100ms
Cable Ø2.5mm, 3m Ø2.5mm, 5m
Vibration 1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Enviorn-
ment
Ambient temp. -10 to 50℃, storage: -20 to 60℃
Ambient humi. 35 to 85%RH, storage: 35 to 85%RH
Protection structure IP67
Approval
Weight※1Approx. 77g (approx. 48g)
Specifications
Model TF31- TF33- -
Number of channels 1CH 3CH
Power sup-
ply
AC power 100-240VACᜠ50/60Hz
AC/DC power 24VACᜠ50/60Hz, 12-24VDCᜡ
Allowable voltage range 90 to 110% of rated voltage
Power
consumption
AC power Max. 8VA (100-240VACᜠ50/60Hz)
AC/DC power Max. 5VA (24VACᜠ50/60Hz), Max. 3W (12-24VDCᜡ)
Display method 7 Segment LED method (red)
Character size (W×H) 9.4×19.3mm
Input type NTC 5kΩ/10kΩ
RTD DPt100Ω
-
Sampling period 500ms
Display accuracy At room temp. (23℃±5℃): ±1℃±1 digit Out of room temp. range: ±2℃±1 digit
Control
output
Compressor (COMP) 250VACᜠ5A 1a, 16A 1c, 20A 1a
Defrost (DEF) 250VACᜠ10A 1a
Auxiliary (AUX) 250VACᜠ5A 1a
Communication output
-
RS485 communication output (Modbus RTU)
Digital input Contact input: ON max. 1㏀, OFF min. 100㏀
No contact input: ON residual voltage: max. 1V, OFF leakage current: max. 1mA, outow current: 4㎂
Control method ON/OFF control
Hysteresis 0.5 to 5.0℃, 2 to 10℉variable
Relay life
cycle
Compressor
(COMP)
5A 1a Mechanical: 5,000,000 operations, Electrical: 50,000 operations (250VAC 5A)
16A 1c Mechanical: 20,000,000 operations, Electrical: 30,000 operations (250VAC 16A)
20A 1a Mechanical: 10,000,000 operations, Electrical: 100,000 operations (250VAC 20A)
Defrost (DEF) Mechanical: 20,000,000 operations, Electrical: 100,000 operations (250VAC 10A)
Auxiliary (AUX) Mechanical: 5,000,000 operations, Electrical: 50,000 operations (250VAC 5A)
Memory retention Approx. 10 years (non-volatile memory method)
Insulation resistance Min. 100MΩ (at 500VDC megger)
Dielectric
strength
AC power 3000VAC 50/60Hz for 1 min (between all terminals and case, power and input circuit)
AC/DC power 1000VAC 50/60Hz for 1 min (between all terminals and case, power and input circuit)
Noise resistance Square-wave noise by the noise simulator (pulse width: 1㎲) ±2kV R-phase and S-phase
Vibration 1.5mm amplitude at frequency of 10 to 55Hz (for 1 min) in each X, Y, Z direction for 2 hours
Environ
ment
Ambient temperature -10 to 50℃, storage: -20 to 60℃
Ambient humidity 35 to 85%RH, storage: 35 to 85%RH
Accessories Bracket: 2, NTC sensor (5kΩ): 1
Protection structure IP65 (front case)
Approval