Autronica BA-45 User manual

This manual suits for next models

1

Other Autronica Control Panel manuals

Autronica BX-10M1 Service manual

Autronica

Autronica BX-10M1 Service manual

Autronica AutroSafe BS-60 Service manual

Autronica

Autronica AutroSafe BS-60 Service manual

Autronica BS-60A User manual

Autronica

Autronica BS-60A User manual

Autronica BS-100 DYFI User manual

Autronica

Autronica BS-100 DYFI User manual

Autronica BX-10 Service manual

Autronica

Autronica BX-10 Service manual

Autronica AutroSafe BS-60 User manual

Autronica

Autronica AutroSafe BS-60 User manual

Autronica BS-100 DYFI Service manual

Autronica

Autronica BS-100 DYFI Service manual

Popular Control Panel manuals by other brands

GENEVO PRiMA 6 installation manual

GENEVO

GENEVO PRiMA 6 installation manual

NAPCO X 255 - Programming instructions

NAPCO

NAPCO X 255 - Programming instructions

Next Systems UNIR1 230 instruction manual

Next Systems

Next Systems UNIR1 230 instruction manual

HORNER HE-XPW1E0 user manual

HORNER

HORNER HE-XPW1E0 user manual

DSC CLASSIC PC1555 instruction manual

DSC

DSC CLASSIC PC1555 instruction manual

Bosch Solution 2000 installation guide

Bosch

Bosch Solution 2000 installation guide

VRinsight MS Panel user manual

VRinsight

VRinsight MS Panel user manual

Zeiss SYCOP 3 Quick reference guide

Zeiss

Zeiss SYCOP 3 Quick reference guide

HULTSTEINS ECOFRIDGE DISPLAY user manual

HULTSTEINS

HULTSTEINS ECOFRIDGE DISPLAY user manual

Elkron C420 Programming manual

Elkron

Elkron C420 Programming manual

GST GST200-2 Installation and operation manual

GST

GST GST200-2 Installation and operation manual

Efka Variocontrol V810 instruction manual

Efka

Efka Variocontrol V810 instruction manual

RDZ PC-HRX user manual

RDZ

RDZ PC-HRX user manual

STG-BEIKIRCH MZ3 operation instruction

STG-BEIKIRCH

STG-BEIKIRCH MZ3 operation instruction

AMX AutoPatch CP-15 instruction manual

AMX

AMX AutoPatch CP-15 instruction manual

Cebora 208-10 instruction manual

Cebora

Cebora 208-10 instruction manual

Satel CA-6 KLED-S user manual

Satel

Satel CA-6 KLED-S user manual

Evolution IQ plus 800 installation manual

Evolution

Evolution IQ plus 800 installation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

116-P-BA45/CE, Rev.C, 2005-09-15 Protecting life, environment and property...
Features
• Control Panel for extinguishing systems with two zones
• Surface mounted or flush mounted in a wall
• Delivered as a steel cabinet with lockable front panel
• Can be used together with conventional and analogue ad-
dressable fire alarm systems
• Designed to meet EMC requirements and CE standards
• Monitored inputs and outputs
• Indicating panel with operating buttons and LED indicators
• Designed for duplicated 24V DC operating voltage
• All inputs / outputs are connected to integrated Extinguishing
Release Module BA-40
• Plug terminals for easy connection
Application / Description
BA-45 is a control panel used together with automatic fire extin-
guishing systems.
The panel consists of 2 zone units. Each zone unit controls and
monitors an extinguishing zone, which can be an area, a room, a
machine, an electrical cabinet etc. Each zone unit has 5 inputs, 4
outputs and 8 LED indicators, plus 2 inhibit buttons. The BA-45's
common functions consist of 4 inputs, 3 LED indicators and 3
operating buttons.
Several BA-45's can be used if more than two extinguishing
zones are required.
By means of a DIP-switch (S1), a delay period can be set. It is
also possible to revert the common fault output (39), plus turn off
the short circuit monitoring for all inputs.
Zone unit
Inputs
• Signal input 1 and 2, break and short circuit monitored.
• Activation of signal output 1 or 2 triggers the delay period for
release. Activation of signal output 2 before the delay period
ends activates the release output when the delay period ends.
• Manual release. 2-stage manual release function. Stage 1
activates alarm for the zone, stage 2 gives release. Break and
short circuit monitored. Two-wire connection.
• Automatic release inhibited via inhibit button on front panel or
via input for external button. The input is break and short circuit
monitored. Can also be used as "Hold" function during the
delay period.
• Inhibit button for control output for 1st alarm.
• Monitoring of pressure in extinguisher tank. Closed contacts at
normal pressure. Break and short circuit monitored.
Outputs
• Release circuit with delayed action. 22-24V DV, secured 1A.
3A current limitation in case of brief current surge (initiators).
Break and short circuit monitored.
• Control output at activation of one of the signal inputs. Transis-
tor output, 100mA. (Inhibited via front panel button).
• Extinguisher released. Potential free relay output.
• Automatic release inhibited. Transistor output, 100mA.
LED indicators
Status indicators:
• Red indicator activates at alarm on one of the signal inputs, the
delay period starts (1st alarm).
• Red indicator activates at release of extinguisher.
• Yellow indicator activates when automatic release is inhibited.
• Yellow indicator activates when control output for 1st alarm is
inhibited.
Fault indicators:
• Yellow indicator shows failure on release circuit.
• Yellow indicator activates if release pressure in extinguisher
tank is too low.
• Yellow indicator activates if there is a failure on control input 1
or 2.
• Yellow indicator shows failure on manual release circuit, circuit
for inhibit of automatic release or pressure monitoring circuit.
Operating buttons:
• Inhibit button for automatic release.
• Inhibit button for control output on 1st alarm.
Common Functions
Inputs
• 24V DC power supply, circuit 1 and circuit 2, secured.
• Silence of sounders. New alarm in other zone will reactivate
sounders.
• Reset of unit.
Outputs
• Sounder alarm output at the first incoming control signal.
Voltage output across relay, 24V DC / 0,5A, monitored and
secured. Cancelled at activation of input "Silence Sounder
Alarm". Reactivated at new alarm in new zone.
• Control output at first incoming control signal. Potential free
relay.
• Common fault output. Transistor output, 100 mA. Can be
reverted by means of DIP-switch S1.3.
• 24V DC output for common power supply to control outputs.
Monitored and secured with 0,5A.
Control Panel for Extinguishing Systems BA-45
BA-45 – Control Panel for Extinguishing Systems
Autronica Fire and Security AS
Fire and Security, Trondheim, Norway. Phone: + 47 73 58 25 00, fax: + 47 73 58 25 01
Oil & Gas, Stavanger, Norway. Phone: + 47 51 84 09 00, fax: + 47 51 84 09 99
Visit Autronica Fire and Security’s Web site: www.autronicafire.com
1st. Alarm
Extinguishant released
Autom. release
inhibited
Ext. output
inhibited
Fault release output
Low tank pressure
Fault control inputs
Fault man./aut./
pressure circuit
ZONE 2
1st. Alarm
Extinguishant released
Autom. release
inhibited
Ext. output
inhibited
Fault release output
Low tank pressure
Fault control inputs
Fault man./aut./
pressure circuit
ZONE 1
Fault power supply
Control Panel for
Extinguishing Systems
COMMON
Reset
Fault alarm output
Power
Silence sounders
Lamptest
BA-45
1st. Alarm
Extinguishant released
Autom. release
inhibited
Ext. output
inhibited
Fault release output
Low tank pressure
Fault control inputs
Fault man./aut./
pressure circuit
ZONE 2
1st. Alarm
Extinguishant released
Autom. release
inhibited
Ext. output
inhibited
Fault release output
Low tank pressure
Fault control inputs
Fault man./aut./
pressure circuit
ZONE 1
Fault power supply
Control Panel for
Extinguishing Systems
COMMON
Reset
Fault alarm output
Power
Silence sounders
Lamptest
BA-45
LED indicators (continued)
• Yellow indicator for power supply failure. Activated in case of
power failure on one of the power circuits and communication
failure between the front panel and the integrated Extinguish-
ing Release Module BA-40.
• Green indicator for operating power. Indicates that one of the
two power inputs is supplied with power.
• Yellow indicator for failure on sounder alarm output.
Operating Buttons
• Silence Alarm, Reset and Lamptest.
DIP-switch S1
DIP-switch S1 is mounted on the integrated Extinguishing Re-
lease Module BA-40 on the left uppermost side. Note that the
switch is shown as if the unit is hold in upright position.
Delay period for release of extinguisher after activation of
one of the control inputs. Settings on S1.1 and S1.2.
(Factory settings: 60 seconds)
OFF ON
1
2
3
4
OFF ON
1
2
3
4
OFF ON
1
2
3
4
OFF ON
1
2
3
4
0 seconds 30 seconds 60 seconds 180 seconds
Status common fault signal (output 39) / Settings on S1.3.
(Factory settings: Normal)
OFF ON
1
2
3
4
OFF ON
1
2
3
4
Normal
Gives 0-volt control at failure. Reverted
Breaks 0-volt control at failure.
Status for monitoring signal input/ Settings S1.4
(Factory settings: OFF)
OFF ON
1
2
3
4
OFF ON
1
2
3
4
Break and short circuit
monitored. Break monitored only.
Technical Specifications
Connections / Indicators on the integrated
Extinguishing Release Module BA-40
Front panel, Indicators and Switches
Dimensions (AutroSafe) HxWxD = 350x350x194 mm
Dimensions (conventional
systems) HxWxD = 350x350x84 mm
Weight 5,5 kg
Material Steel cabinet, ABS/PC-cast
front
Power consumption (normal)
1 zone
2 zones
70 mA
80 mA
Power consumption (alarm)
1 zone
2 zones
1,5A
3A
Ambient temperature -5 til + 40 °C
Power supply Duplicated 24VDC/1,5A
Release effect
(at 24V DC) 25W continuous.
70W<1 seconds
Protection class IE529/IP30
S1.3. S1.3
S1.4 S1.4
Indicators
Connectors
S1.1 Release Delay
S1.2 Release Delay
S1.3 Fault inv.
S1.4 Monitoring
Connec-