Autronica BX-10M1 Service manual

Fire Alarm Control panel
BX-10M1
Conventional fire alarm control panel with 4 zones (loops)
Protecting life, environment and property...
P-BX10M1/FE Rev. A, 050128
Operator's Handbook

COPYRIGHT
©
This publication, or parts thereof,
may not be reproduced in any form,
by any method, for any purpose.
Autronica Fire and Security AS and
its subsidiaries assume no
responsibility for any errors that may
appear in the publication, or for
damages arising from the
information in it. No information in
this publication should be regarded
as a warranty made by Autronica
Fire and Security. The information in
this publication may be updated
without notice.
Product names mentioned in this
publication may be trademarks.
They are used only for identification.

Contents
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 1
Table of Contents
1.
Introduction......................................................................3
1.1
About this manual..............................................................................3
1.2
The Product.......................................................................................3
1.3
The reader.........................................................................................4
1.4
Other reference material ...................................................................4
2.
Operating the control panel............................................6
2.1
Operating levels.................................................................................6
2.2
Operator mode/service mode operations........................................6
2.3
Keypad...............................................................................................7
2.4
Keypad functions...............................................................................7
2.4.1
Summary of the keypad configurations...................................7
2.4.2
Resetting the keypad using the C-key.....................................8
2.5
The front panel label..........................................................................8
3.
LED indicators .................................................................10
3.1
Summary...........................................................................................10
3.2
Fire alarm from detectors on a conventional detector loop...............11
4.
A fire alarm is activated (immediate action)..................12
5.
Fire alarm with 2 minutes delayed warning...................14
6.
A fault arises....................................................................16
7.
Disabling/restoring..........................................................18
7.1
Introduction........................................................................................18
7.2
Disabling/restoring from the front panel ............................................19
7.3
Disabling/restoring of zones from auxiliary switches.........................20
8.
Activating the alarm delay function................................21
8.1
Introduction........................................................................................21
8.1.1
Maritime panel BX-10M1.........................................................21
8.2
Activating from the front panel...........................................................22
9.
Testing indicator lights and internal buzzer..................24

Contents
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 2
10.
Appendix ..........................................................................26
10.1
Summary of indicators.......................................................................26
10.1.1
Main indicators........................................................................26
10.1.2
Alarm – detector zones ...........................................................26
10.1.3
Fault/disabling/testing - zones 1 - 4.........................................26
10.1.4
Fault/disabling/testing - alarm outputs ....................................27
10.1.5
Error/disabling/testing - general alarm output (BMA)..............27
10.1.6
Error/disabling/testing - general fault output (BMF) ................27
10.1.7
Immediate warning disabled ...................................................27
10.1.8
Fault in battery or battery fuse (F9).........................................27
10.1.9
Fault on power supply/charger or fuse (F8) ............................28
10.1.10
Earth fault on the control panel......................................28
10.1.11
System fault/controlled shut down of control panel.......28
10.1.12
Alarm sender activated..................................................28
10.1.13
Operator level/Service level...........................................28
10.2
BX-10M Control Panel variants.........................................................29
11.
Reader’s Comments........................................................31

Introduction
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 3
1. Introduction
1.1 About this manual
The purpose of this manual is to provide all the information necessary to
operate the BX-10M1 fire alarm control panel.
• BX-10M1 can be supplied with variants of the system program
adapted to particular markets and special functions (appendix 8).
1.2 The Product
The BX-10M1 Fire Alarm Control Panel is a conventional panel with 4
zones. The panel is supplied as:
• BX-10M1 fire alarm control panel with 4 zones (loops), including
power supply and battery.
• BX-10M1 can operate from 110VAC and 230VAC mains.
In an alarm situation, detectors and manual call-points connected to a
conventional detection loop are detected by means of increasing current
consumption. Hence, it is not possible on the control panel to identify the
detectors and manual call-points that are in alarm status. The points
(detector and manual call-points) in alarm are found by checking all
points connected to the zone in alarm and observing the points that
have active alarm LEDs (the LEDs are lit).
Manual call points and detectors can be connected to the same loop
cable (the same zone). Manual call-points in alarm are handled
differently compared to detectors in alarm. The standard manual call-
point BF-20 always gives instant alarm when operated (glass broken).
This means that manual call-points are not disabled when the zone is
disabled, and alarm outputs are not affected by the standard 2-minute
delay if a manual call-point is operated (glass broken).
If the installation requires a standard 2-minute delayed alarm output
when a manual call-point is operated, a resistor 120 ohm/0,5W must be
connected in series with the alarm switch in the manual call-point.
(Internal connection: Chapter 3.8).
Note that the manual call-point still is active (will give alarm) if the zone
is disabled.
A second alarm in a zone where the first alarm already has been
acknowledged, will not activate alarm LEDs and the internal buzzer. If
the internal buzzer only is muted after the first alarm, the second alarm
will activate it once more.

Introduction
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 4
1.3 The reader
The manual is designed for use by those designated responsible for
operating the system.
1.4 Other reference material
In addition to this manual, the BX-10M1 control panel is covered by the
following documents:
Manual Item no.
Installation Manual - BX-10M1 Fire Alarm
Control Panel P-BX-10M1/IE
Data sheet P-BX10M1/CE

Introduction
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 5

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 6
2. Operating the control panel
2.1 Operating levels
The BX-10M1 fire alarm control panel has 2 operating levels. Level 1 is
the lowest level of access and does not require a password.
The following functions are accessible within the respective operating
level:
Level Accessible functions
1
No password protection. Normal mode.
• resetting of internal audio warning device (with alarms and
faults).
• testing of indicator lamps/internal audio warning device.
2
Operator code is required. Yellow OPERATOR LEVEL light comes
on indicating that the system is in operator mode.
• cancelling/reactivating of the alarm outputs
• resetting of the control panel from alarm or error status
• disabling of functions (zones 1-4, alarm outputs, control outputs)
• disabling of immediate warning (D/N function)
The operator code for operating level 2 shall include a minimum of 3
digits.
For relevant operator codes, see sub-section. 2.4.3.
IMPORTANT:
All operator code entries are confirmed by pressing this key -
2.2 Operator mode/service mode operations
Keying the operator code + enables the operator to access the
system in operator mode The system will remain in this mode for a
predetermined time (time (the default is 5 minutes after the last key-
stroke), after which it will automatically return to normal mode unless the
operator or service code is entered one more time.
Operator code: 110 +

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 7
2.3 Keypad
The keypad comprises 15 keys and is back-lit
when the control panel records an event, or
when one of the keys is pressed.
The back-lighting will switch off automatically
about 5 minutes after the last keystroke is
made.
Any fault in the keypad connection (e.g. a
sticking key) will cause the internal audio
warning device to emit a rapid intermittent
sound.
2.4 Keypad functions
2.4.1 Summary of the keypad configurations
Keypad functions
Function
Keypad configuration
In normal status:
(no code required) In operator mode:
Operator code +
Cancel internal audio warning device
Cancel/activate alarm
Reset
R
Disabling zone 1 1 +
Disabling zone 2 2 +
Disabling zone 3 3 +
Disabling zone 4 4 +
Disabling alarm circuits (AK1 and AK2) FAD's 5 +
Disabling control outputs 6 +
Disabling alarm output (BMA) FARE 7 +
Disabling fault output (BMF) FWRE 8 +
Disabling immediate alarm (D/N function) * 9 +
Disabling of intruder alarm (not implemented) 10 +
Lamp test / audio warning device test 30 +
ENTER (accept)
Resetting the keypad
C
* Maritime version has a 2 minutes delay.
0
C
98
7
6
5
4
3
2
1
R
(always accessible)
(always accessible)

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 8
2.4.2 Resetting the keypad using the C-key
The C-key is used to reset the keypad, i.e. all keystrokes subsequent to
the last use of the key will be cancelled.
IMPORTANT:
If you are unable to access operator or service mode, the problem may
be that the control panel “remembers” a previous keystroke. In such
instances, reset the keypad (press C) and then enter the code+
Operator code
The operator code will vary from country to country. The operator code
must always be confirmed with . The yellow OPERATOR LEVEL light
will come on when the control panel is in operator mode. As long as the
indicator lamp is on there is no need to enter the operator code for each
new function.
The operator code is activated 5 minutes after the last keystroke, or is
cancelled manually by entering the code anew.
Operator code: 110 + .
2.5 The front panel label
Behind the Plexiglas door cover is a label with four fields for noting the
areas of cover of the respective zones (zones 1-4). If this information
requires changing, the Plexiglas cover can be removed and the new
information can be noted in black print on transparent tape.
Refer to the BX-10M1 Installation and Commissioning Handbook.
2:
3:
4:
R
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power.
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4 Fault outp.
.
Operator
Imm. alarm Alarm call activated
Information
Alarm
System Zone Operator
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
1:
F
ields for noting the areas of cover for the
respective zones.

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 9

ב
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 10
3. LED indicators
3.1 Summary
The panel front comprises 24 LED indicators. The individual
characteristics and response modes for these are given in subsequent
chapters concerning the various events/functions.
In addition, a detailed description of the indicator functions is provided in
the Appendix at the back of this manual.
The instant an alarm signal is activated, the LED indicators for FIRE
and FAULT will flash in time with the intermittent internal audio warning.
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
A
larms
Contr.
A
l -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4 Fault outp..
Operator
Imm. alarm
Information
Alarm
System Zone Operator
1:
2:
3:
4:
A
ccess code: xx
x
Silence int. buzzer
Silence/res. alarms
Reset
A
utronica Fire & Securit
y
System
0
C
98
7
6
5
4
3
2
1
BX-10
R
R
A
larm call activated

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 11
3.2 Fire alarm from detectors on a
conventional detector loop
The fire alarm panel cannot display if more than one detector on the
same loop is in alarm condition. This means, if the panel gives alarm on
one loop, the alarm can be activated from more then one detector. The
person in charge for the investigation of the fire, has to check all
detectors on the loop (zone), to verify the fire situation.

ב
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 12
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4 Fault outp.
.
Operator
Imm. alarm
InformationAlarm
System Zone Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
987
6
5
4
3
21
BX-10
R
R
Alarm call activated
4. A fire alarm is activated
(immediate action)
Step Necessary action Visual Warning Status Audio Warning Status
1
Follow local fire instructions
step by step. The red FIRE indicator
flashes.
The zone indicator(s) at the
bottom-left will flash red,
indicating in which detector
zone(s) the fire is registered
(zones 1 to 4).
The integrated audio warning
device and the sounders are
activated (control outputs are
activated).
2
Cancel internal buzzer by
pressing The red FIRE indicator and
zone indicator(s) continue to
flash.
The internal audio device is
switched off.
Alarms and control outputs
remain active.
3
Investigate the site of the fire
and all detectors on the
alarming loop to check if there
are more than one area in fire,
and take the necessary actions.
4
Go into operator mode: key in
operator code + The yellow operator level
indicator will come on.
Note: If the system goes out of operator mode after 5 minutes, you
must re-enter the operator code +
5
Accept the alarm by
pressing The red FIRE indicator and
zone indicator(s) light up with
steady light.
The running delay of the
sounder alarm outputs is
deactivated. Control outputs
remain active.
Note: If necessary, the sounders can be re-activated by once again
operating .
When the fire is extinguished and all necessary repair work is
implemented (smoke is exhausted, new glass replaced in the
manual call-points, etc.), the system should be returned to
normal operating mode.
One or more detectors/manual call-points send an alarm signal from a detector zone.
The red FIRE indicator light flashes.
Red flashing zone lights
indicate the activated
detector zone(s).
Internal buzzer is activated.
All alarm units linked to the panel are delayed 2 minutes.
*Continuous alarm signal
Audio/visual characteristics:
Visual: 0.5 sec. ON – 0.5 sec. OFF
Audio: Continuous signal on
BX-10M1

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 13
Step Necessary action Visual Warning Status Audio Warning Status
6
Reset the system by pressing
The red FIRE indicator and
zone indicator(s) go out.
Note: If a detector zone remains in alarm status after resetting the
system, the alarm will be activated again. In such an instance
the above steps must be repeated.
R

ב
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 14
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4 Fault outp.
.
Operator
Imm. alarm
InformationAlarm
System Zone Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
987
6
5
4
3
21
BX-10
R
R
Alarm call activated
5. Fire alarm with 2 minutes delayed
warning
The BX-10M1has according to SOLAS requirements 2 minutes delay of sounder outputs.
Step Necessary Action Visual Warning Status Audio Warning Status
1
Follow local fire instructions
step by step. The red FIRE indicator
flashes.
One of the red zone indicators
at the bottom-left will flash to
indicate in which detection
zone the fire is detected (zone
1, 2, 3 or 4).
The integrated audio warning
device with continous signal
is activated.
Note: Two-minute alarm delay starts (two minute alarm delay applies
to maritime regulation).
Immediate alarms are disabled during the delay period.
If an alarm is given from two or more detectors or detection
zones simultaneously, the alarm outputs will be activated
immediately, i.e. the alarm delay will be interrupted.
2
Silence internal buzzer by
pressing The red FIRE indicator and
zone indicator will continue to
flash.
The internal buzzer is
switched off.
3
Accept the alarm by
pressing
The flashing red indicators
change to a steady light. The
running delay time is
deactivated.
Alarm outputs are blocked for
automatic activation.
Note: If necessary, the sounders can be reactivated by once again
operating
4
Investigate the fire site of fire
and all detectors on the
alarming loop to check if there
are more than one area in fire.
(Continued on next page…..)
One or more detectors/manual call-points send an alarm signal from a detection zone in a situation where
alarm delay is activated (immediate warning disabled, see Chap. 8).
NOTE: If an alarm is activated from two or more detection zones simultaneously, the alarm
outputs and alarm transference will be activated immediately, i.e. the alarm delay will be
cancelled. The same activation will appear if a manual call point without an extra resistor
is operated in a zone. Refer to chapter 1.1.
The red FIRE indicator flashes.
Red flashing zone lights
indicate which detector
zone(s) are involved.
Visual characteristics:
0.5 sec. ON – 0.5 sec. OFF
Continuous audio signal.
All alarms linked to the
panel are delayed 2
minutes.
Continuous alarm
signal for maritime
version.

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 15
4
The next step in the procedure will depend on whether or not there really is a fire.
Step should be followed if there isn’t a fire, step if there is a fire.
4a
If there is not a fire;
go into operator mode: key in
operator code +
The yellow
operator level
indicator will
come on.
5a
Reset the system by operating The red FIRE
indicator and
zone indicator
will go out.
4b
If there really is a real fire,
implement the necessary
measures. Activate the fire
alarm and alert the fire
department by activating the
nearest manual call-point.
The red FIRE indicator and
zone indicator will continue to
flash.
All sounders will be switched
on.
General alarm output will be
activated.
Note: When the fire is extinguished and all necessary repair work is
complete (the smoke is exhausted, new glass replaced in the
manual call-points, etc.), the system may be returned to normal
operating mode again.
5b
If the Operator Mode is
switched off, re-enter the
Operator Mode again.
Go into operator mode: key in
operator code +
The yellow operator level
indicator will come on.
Note: If the system goes out of operator mode after 5minutes, you
must re-enter the operator code +
6b
Silence alarm by pressing The red FIRE indicator and
the zone indicator(s) will
come on with a steady light.
All sounders will be switched
off.
General alarm output remains
activated.
Note: If necessary, the sounders may be re-activated by pressing
again.
7b
Reset the system by pressing The red FIRE indicator and
zone indicator(s) will go out.
Note: If a detector zone remains in alarm status after resetting the
system, the alarm will be activated again. In such an instance
the above steps must be repeated.
4a
R
4b
R

A fault arises
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 16
s
ALARM
Test
Fault
Disabled
Power
Zone 1
Zone 2
Zone 3
Zone 4
Alarms
Contr.
Al -outp.
Fault/Disabled/Test
Battery
Power
Earth
Fault
Zone 1
Zone 2
Zone 3
Zone 4 Fault outp.
.
Operator
Imm. alarm
InformationAlarm
System Zone Operator
1:
2:
3:
4:
Access code: xxx
Silence int. buzzer
Silence/res. alarms
Reset
Autronica Fire & Security
System
0
C
987
6
5
4
3
21
BX-10
R
R
Alarm call activated
6. A fault arises
Step Necessary Action Visual Warning Status Audio Warning Status
1
Check the error indicators on
the panel and determine which
fault is reported.
The yellow common FAULT
indicator will flash in the
event of an error/fault. One or
more of the yellow flashing
error indicators will indicate
which type of fault has arisen.
The internal buzzer will be
activated.
2
Silence internal buzzer by
pressing The yellow common FAULT
indicator and the yellow
FAULT indicator below will
continue to flash.
The internal buzzer will
switch off.
3
Call the system administrator or
engineer and implement all
necessary repair work.
Note: A fault warning from the central unit is not possible to accept.
Flashing failure indication continue to flash until the fault is
repaired and the “reset” button is pressed.
4
Go into operator mode: key in
operator code (110) + The yellow operator level
indicator will come on.
5
Reset the system by pressing The yellow common FAULT
indicator and the yellow fault
indicator below will go out.
Note: If an error continues after resetting the system, the panel will
indicate an error again. In such an instance the above steps
must be repeated.
Note: If an alarm arises when the system is in fault status, the visual and audio signal will change to the
characteristics for fire alarm. When the alarm is reset (RESET ALARM), the visual
characteristics for fault status will resume and the buzzer will switch off.
On or more faults occur. The panel indicates which type of error(s) has arisen.
The integrated audio warning device
is activated.
The common yellow FAULT
indicator flashes in the event of
a fault.
One or more of the yellow flashing fault indicators in the
FAULT/DISABLING/TEST field will indicate which
type(s) of fault has arisen. The fault could be in:
• Loop cable (detector zone) – break, high current
consumption or short-circuit
• Sounder output – break or short-circuit
• Blown fuse for alarm/error output.
• Battery
• Power supply – charger, mains connection
• Earth fault
• System fault
R
Audio/visual characteristics:
0.5 sec. ON – 1.5 sec. OFF

Operating the control panel
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 17

Disabling/restoring
Operator's Handbook, Fire Alarm Control panel BX-10M1, P-BX10M1/FE Rev. A, 050128, Autronica Fire and Security AS
Page 18
7. Disabling/restoring
7.1 Introduction
All disabling/restoring (of zones, alarm outputs, control outputs and
alarm transmissions) can be implemented from the control panel using
the keys 1-8 followed by when the panel is in operator mode, see
Chap. 7.2.
Each of the four detector zones can also be disabled via auxiliary
disabling switches.
IMPORTANT: When a zone (detector loop) is disabled the detectors will
be disabled while manual call-points will continue to be active.
If a zone is disabled using an external switch, it will not be possible to
restore the zone from the front panel.
Table of contents
Other Autronica Control Panel manuals
Popular Control Panel manuals by other brands

Siemens
Siemens FC2005 Programming manual

SILENT KNIGHT
SILENT KNIGHT 5204 Installation and operation manual

Maple Armor
Maple Armor FW106S,FW106SC Installation and operation manual

Nortek
Nortek e Series Field guide

Beckhoff
Beckhoff CP6608 Installation and operating instructions

Ksenia
Ksenia KSI1000016.300 Quick reference guide