Autronica AutroFlame X33AF User manual

Instructions
AutroFlame X33AF
Multi-spectrum IR Flame Detector
Instructions, AutroFlame X33AF 116-P-X33AF/IGB, rev. E, 2013-08-13, Autronica Fire and Security AS
P/N 95-8625-17.1, Rev: 2/13

COPYRIGHT ©
This publication, or parts thereof, may
not be reproduced in any form, by
any method, for any purpose.
Autronica Fire and Security AS and its
subsidiaries assume no responsibility
for any errors that may appear in
the publication, or for damages
arising from the information in it. No
information in this publication should
be regarded as a warranty made
by Autronica Fire and Security. The
information in this publication may be
updated without notice.
Product names mentioned in this
publication may be trademarks. They
are used only for identification.

Table of Contents
DESCRIPTION ..............................1
Outputs ..............................1
LED.................................2
Opical Integrity (
oi
)....................2
Communication........................3
Data Logging .........................3
Integral Wiring Compartment .............3
Detector Sensitivity Levels ...............3
GENERAL APPLICATION INFORMATION .........4
Response Characteristics................4
Important Application Considerations .......4
IMPORTANT SAFETY NOTES ..................4
INSTALLATION ..............................5
Detector Positioning ....................5
Detector Orientation ....................5
Protection Against Moisture Damage .......5
Wiring Procedure ......................6
STARTUP PROCEDURE .....................13
Fire Alarm Test .......................13
TROUBLESHOOTING........................13
MAINTENANCE ............................14
Cleaning Procedure ...................14
oi
plate Removal and replacement .......14
Periodic Checkout Procedure ............15
Clock Battery ........................15
FEATURES ................................15
SPECIFICATIONS ...........................16
Accessories .........................18
REPLACEMENT PARTS ......................18
Replacement parts ....................18
DEVICE REPAIR AND RETURN................18
ORDERING INFORMATION ...................18
APPENDIX A – FM APPROVAL AND PERFORMANCE
REPORT .................................A-1
APPENDIX B – CSA APPROVAL ..............B-1
APPENDIX C – ATEX / CE APPROVAL .........C-1
APPENDIX D – IECEX APPROVAL ............D-1
APPENDIX E – EN54 APPROVALS ............E-1
APPENDIX F – OFFSHORE APPROVALS .......F-1
Type Approval .......................F-1
Type Approval .......................F-1
APPENDIX G – ADDITIONAL APPROVALS ......G-1


Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 1
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the ame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X33AF includes the Automatic Optical
Integrity (
oi®
) feature — a calibrated performance
test that is automatically performed once per
minute to verify complete detector operation
capabilities. No testing with an external test lamp
is approved or required.
DESCRIPTION
The X33AF is a multispectrum infrared (IR) ame detector.
It provides unsurpassed detection of res from light to
heavy hydrocarbon fuels combined with the highest
degree of false alarm rejection. The detector has Division
and Zone explosion-proof ratings and is suitable for use in
indoor and outdoor applications.
The X33AF contains three IR sensors with their
associated signal processing circuitry. The standard
output conguration includes re, fault and auxiliary
relays. Output options include:
– 0 to 20 mA output (in addition to the three relays)
– HART communication.
A tricolor LED on the detector faceplate indicates normal
condition and noties personnel of re alarm or fault
conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
The X33AF housing is available in copper-free aluminum
or stainless steel, with NEMA/Type 4X and IP66/IP67
rating.
OUTPUTS
Relays
The standard detector is furnished with re, fault and
auxiliary relays. All three relays are rated 5 amperes at
30 Vdc.
The Fire Alarm relay has redundant terminals and normally
open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and latching
or non-latching operation.
INSTRUCTIONS
Multispectrum IR Flame Detector
AutroFlame X33AF

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 2
The Auxiliary relay has normally open / normally closed
contacts, and is congurable for energized or de-energized
operation, and latching or non-latching operation.
0 to 20 mA Output
A 0 to 20 mA output is available as an option (in addition
to the three relays). This option provides a 0 to 20 mA dc
current output for transmitting detector status information
to other devices. The circuit can be wired in either an
isolated or non-isolated conguration and can drive a
maximum loop resistance of 500 ohms from 18 to 19.9
Vdc and 600 ohms from 20 to 30 Vdc. Table 1 indicates
the detector status conditions represented by the various
current levels. The output is calibrated at the factory, with
no need for eld calibration. A model with relays and
0-20 mA with HART is also available. Refer to Addendum
number 116-P-X33AFADDENDUM/YGB for complete
details.
NOTE
The output of the 0 to 20 mA current loop is not
monitored by the fault detection circuitry of the
X33AF. Therefore, an open circuit on the loop will
not cause the fault relay to change state or the
detector status LED to indicate a fault.The status of
the LED always follows the status of the relays.
An alarm condition will normally over-ride a fault condition,
unless the nature of the fault condition impairs the ability
of the detector to generate or maintain an alarm output,
i.e. loss of operating power.
LED
A tricolor LED on the detector faceplate indicates normal,
re alarm and fault conditions. Table 2 indicates the
condition of the LED for each status.
Table 2—Detector Status Indicator
OPICAL INTEGRITY (
oi
)
Automatic
oi
The X33AF includes the Automatic Optical Integrity
(
oi
) feature — a calibrated performance test that is
automatically performed once per minute to verify
complete detector operation capabilities.No testing with an
external test lamp is required. The detector automatically
performs the same test that a maintenance person with a
test lamp would perform — once every minute, 60 times
per hour. However, a successful Automatic
oi
test does
not produce an alarm condition.
The Protect•IR signals a fault condition when less than
half of the detection range remains. This is indicated by
the Fault output relay and is evident by the yellow color of
the LED on the face of the detector. The
oi
fault condition
is self-clearing if the optical contamination is temporary. If
the contamination is not automatically cleared and the
oi
fault remains, the detector may require cleaning or service.
See the "Troubleshooting" section for further information.
Magnetic
oi
/ Manual
oi
The detector also incorporates both Magnetic
oi
(Mag
oi
) and Manual
oi
(Man
oi
) features that provide the
same calibrated test as the Automatic
oi
, and in addition
actuates the Alarm output to verify operation for preventive
maintenance requirements. These features can be
performed at any time and eliminate the need for testing
with a non-calibrated external test lamp.
Table 1—Detector Status Conditions Indicated by Current Level
Current Level (±0.3 mA) Detector Status
0 mA Power Fault
1 mA General Fault
2 mA Oi Fault
3 mA Hi Background IR Fault
4 mA Normal Operation
20 mA Fire Alarm
Detector Status LED Indicator
Power On/Normal Operation
(no fault or re alarm) Green
Fault Yellow
Fire (Alarm) Red
Low Sensitivity One Yellow Flash
During Power-up
T- Low Sensitivity Three Yellow Flashes
During Power-up
Medium Sensitivity Two Yellow Flashes
During Power-up
Very High Sensitivity Four Yellow Flashes
During Power-up
NOTE: See "Detector Sensitivity Levels" for additional information.

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 3
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
The Mag
oi
test is performed by placing a magnet by
the marked location (Mag
oi
) on the outside of the
detector (see Figure 2). The Man
oi
test is accomplished
by connecting the
oi
lead (terminal 22) to power supply
minus via an external switch.The magnet or switch must be
held in place for a minimum of 6 seconds to complete the
test. Either of these test methods activates the calibrated
IR emitters. If the resulting signal meets the test criteria,
indicating that greater than half of the detection range
remains, the Alarm output changes state, the indicating
LED changes to red, and the 0-20 mA current output
goes to 20 mA. This condition remains until the magnet is
removed or the switch is released, regardless of whether
the relays are set for latching or non-latching operation.
If less than half of the detection range remains, no alarm
is produced and a fault is generated. The fault indication
can be reset by momentarily applying the Mag or Man
oi
switch.
NOTE
Refer to Appendix A for FM verification of the
Optical Integrity
oi
function.
COMMUNICATION
The X33AF is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 supports MODBUS protocol, with
the detector congured as a slave device.
For HART communication, connect a HART communicator
across a 250 ohm resistor in the 0-20 mA loop.
DATA LOGGING
Data logging capability is also provided. Status conditions
such as normal, power down, general and
oi
faults, pre-
alarm, re alarm, time and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active, and
again when the status changes. Data is accessible using
the RS-485 port.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected within the
integral junction box. The screw terminals accept wiring
from 14 to 24 AWG. The detector is furnished with four
conduit entries, with either 3/4 inch NPT or M25 threads.
DETECTOR SENSITIVITY LEVELS
There are four factory congured sensitivity levels
available for the X33AF Flame Detector:
Very High, Medium, Low and T-Low.
The following criteria should be considered when
choosing a sensitivity level for the intended application:
• Detector placement
• Speed of response based on fuel type and re size
(see Appendix A for response times)
• Distance between the hazard and the ame
detector
Recommended sensitivity guidelines are as follows:
Very High: Offshore, Warehousing
Medium: General Duty, Compressors
Low: Offshore, close proximity/high IR
backgrounds
T-Low: Turbine enclosures
Additional information on X33AF Flame Detector
performance results and sensitivities can be found in
Appendix A, the FM Approval and Performance Report.
Consult the factory with any questions on how to choose
the optimum sensitivity level for the intended application.

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 4
GENERAL APPLICATION
INFORMATION
RESPONSE CHARACTERISTICS
Response is dependent on the detector's sensitivity
setting, distance, type of fuel, temperature of the fuel, and
time required for the re to come to equilibrium. As with
all re tests, results must be interpreted according to an
individual application.
See Appendix A for third-party approved re test results.
Additional re test results are available from Autronica.
IMPORTANT APPLICATION CONSIDERATIONS
In applying any type of sensing device as a re detector,
it is important to know of any conditions that can prevent
the device from responding to re, and also to know
what other sources besides re can cause the device to
respond.
Welding
Arc welding should not be performed within 40 feet
(12.2 m) of the detector congured to very high sensitivity,
within 10 feet (3.0 m) at medium sensitivity, within 5
feet (1.5 m) at T-Low sensitivity, or within 5 feet (1.5 m)
at Low sensitivity. It is recommended that the system be
bypassed during welding operations in situations where
the possibility of a false alarm cannot be tolerated. Gas
welding mandates system bypass, since the gas torch is
an actual re. Arc welding rods can contain organic binder
materials in the ux that burn during the welding operation
and are detectable by the X33AF. Welding rods with clay
binders do not burn and will not be detected by the X33AF.
However, system bypass is always recommended, since
the material being welded may be contaminated with
organic substances (paint, oil, etc.) that will burn and
possibly trigger the X33AF.
Articial Lighting
The X33AF should not be located within 3 feet (0.9 m) of
articial lights. Excess heating of the detector could occur
due to heat radiating from the lights.
EMI/RFI Interference
The X33AF is resistant to interference by EMI and RFI,
and is EMC Directive compliant. It will not respond to a 5
watt walkie-talkie at distances greater than 1 foot. Do not
operate a walkie-talkie within 1 foot of the X33AF.
Non-Carbon Fires
The X33AF is a multiple spectrum IR device with detection
limited to carbonaceous fuels. It should not be used to
detect res from fuels that do not contain carbon, such as
hydrogen, sulfur, and burning metals.
IMPORTANT SAFETY NOTES
WARNING
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage.
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If
in doubt, consult the authority having jurisdiction
before wiring the system. Installation must be
done by a properly trained person.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing system tests or maintenance.
CAUTION
The multispectrum IR ame detectors are to be
installed in places where the risk of mechanical
damages is low.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 5
INSTALLATION
NOTE
The recommended lubricant for threads and
O-rings is a silicone free grease (part number
116-005003-001) available from Autronica. Under
no circumstances should a lubricant containing
silicone be used.
DETECTOR POSITIONING
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:
• Identify all high risk re ignition sources.
• Be sure that enough detectors are used to adequately
cover the hazardous area.
• Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
• Verify that all detectors in the system are properly
located and positioned so that any re hazards are
within both the Field of View (FOV) and detection
range of the detector. Autronica's Q1201C Laser
Aimer is recommended for establishing the detector's
FOV. Refer to Appendix A for specic information
regarding detector range and FOV.
• The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain. See
Figure 1. The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
• The detector must be mounted on a rigid surface in a
low vibration area.
• Dense fog, rain or ice can absorb IR radiation and
reduce the sensitivity of the detector. To ensure
optimum performance, be certain that the internal
optical heater is enabled on detectors that are used in
applications where snow, ice, and condensation are
likely to occur.
• Although IR detectors are less affected by smoke
than other detectors, the X33AF should not be placed
where rising combustion products can obscure its
vision. If smoke is expected before re, smoke or other
alternative detectors should be used in conjunction
with the X33AF. For indoor applications, if dense
smoke is expected to accumulate at the onset of a
re, mount the detector on a side wall at least a few
feet (approximately 1 meter) down from the ceiling.
• If possible, re tests should be conducted to verify
correct detector positioning and coverage.
• For ATEX installations, the X33AF detector housing
must be electrically connected to earth ground.
DETECTOR ORIENTATION
Refer to Figure 2 and ensure that the oi plate will be oriented
as shown when the X33AF is mounted and sighted. This
will ensure proper operation of the
oi
system and will also
minimize the accumulation of moisture and contaminants
between the
oi
plate and the viewing windows.
IMPORTANT
If removed, the
oi
plate must be securely
tightened to ensure proper operation of the
oi
system (40 oz./inches [28.2 N.cm] recommended).
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CORRECT
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
D1974
Figure 1—Detector Orientation Relative to Horizon
VIEWING WINDOW (3)
oiPLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
oiMAGNET
DETECTOR
STATUS INDICATOR
F2068
Figure 2—Front View of the X33AF

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 6
PROTECTION AGAINST MOISTURE DAMAGE
It is important to take proper precautions during installation
to ensure that moisture will not come in contact with the
electrical connections or components of the system. The
integrity of the system regarding moisture protection must
be maintained for proper operation and is the responsibility
of the installer.
If conduit is used, we recommend installing drains,
according to local codes, at water collection points to
automatically drain accumulated moisture.
It is also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
Conduit raceways should be inclined so that water will
ow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible, install
conduit drains above the seals to prevent the collection
of water or install a drain loop below the detector with a
conduit drain at the lowest point of the loop.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are highly
recommended to prevent water ingress in outdoor
applications. Units with M25 threads must use an IP66/
IP67 washer to prevent water ingress.
WIRING PROCEDURE
Wire Size and Type
The system should be wired according to local codes.
The wire size selected should be based on the number
of detectors connected, the supply voltage and the cable
length. Typically 16 AWG or 2,5 mm2shielded cable is
recommended. Wires should be stripped 3/8 inch (9 mm).
A minimum input voltage of 18 Vdc must be present at the
X33AF.
NOTE
Refer to “Power Consumption” in the
“Specications”section of this manual.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures 7
through 12, and Figure 15. Consult the factory if not using
shielded cable.
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.
CAUTION
Installation of the detector and wiring should be
performed only by qualied personnel.
Detector Mounting
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch (M9) bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting
arm weights (See "Specications" section). Refer to the
Q9033 Mounting Arm and Collar Attachment Manual (95-
8686) for additional mounting information. See Figure 3
for dimensions.
13.1
(33.4)
10.6
(27.0)
4.0
(10.2)
4.0
(10.2)
3.0
(7.6)
3.0
(7.6)
4X ø0.42
(1.1)
E2069
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
Figure 3—Q9033 Mounting Bracket Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 7
Relay and 0-20 mA Output Models
Follow the instructions below to install the X33AF.
1. Make eld connections following local ordinances
and guidelines in this manual.
– Figure 4 shows the wiring terminal strip located
inside the detector’s integral junction box.
– Figure 5 shows the wiring terminal identication for
the X33AF ame detector.
– Figure 6 shows an EOL resistor installed within the
integral wiring compartment of the detector (refer to
“EOL Resistors” for details).
– Figures 7 and 8 provide examples of typical
installations with a X33AF wired to a re alarm
panel.
– If the detector is equipped with a 0 to 20 mA output,
refer to Figures 9 through 12.
– Figures 13, 14 and 15 shows examples of connection
to AutroSafe/Autroprime systems.
– Figure 16 shows example of connection to BS-100
system.
2. Check all eld wiring to be sure that the proper
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the nal sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
EOL Resistors
To ensure that the insulating material of the wiring terminal
block will not be affected by the heat generated by EOL
resistors, observe the following guidelines when installing
the resistors.
1. Required EOL resistor power rating must be 5 watts
minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies
to ATEX/IEC installations only.
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3. Bend the leads and install the EOL resistor as shown
in Figure 6.
4. Maintain a 3/8 inch (10 mm) minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
NOTE
The EOL resistor can only be used within the
ameproof terminal compartment. Unused conduit
entries shall be closed with suitable blanking
elements.

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 8
Figure 4—X33AF Terminal Block
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
4-20 mA + 4-20 mA –
4-20 mA + REF 4-20 mA – REF
COM FIRE COM FIRE
N.O. FIRE N.O. FIRE
N.C. FIRE N.C. FIRE
COM FAULT COM FAULT
N.O. FAULT N.O. FAULT
24 VDC + 24 VDC +
24 VDC – 24 VDC –
24 VDC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
COM AUX
N.O. AUX
N.C. AUX
RS-485 A
RS-485 B
MAN Oi
C2061
Figure 5—X33AF Wiring Terminal Identication
3/8 INCH (10 MM) GAP MINIMUM
1112
13
141516171819
B2126
BULKHEAD
Figure 6—EOL Resistor Installation (For Ex d Wiring only)

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 9
B2107*
FIRE ALARM PANEL
X33AF DETECTOR
ALARM
24 VDC
+
–
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
E.O.L.
DEVICE4
oi TEST 3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
N.O. FIRE2
N.O. FIRE
N.C. FIRE2
N.C. FIRE
COM FAULT1
COM FAULT
N.O. FAULT1
N.O. FAULT
24 VDC + 24 VDC +
24 VDC – 24 VDC – 24 VDC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS-485 A
RS-485 B
MAN Oi
4-20 mA + 4-20 mA –
4-20 mA + REF 4-20 mA – REF
COM AUX
N.O. AUX
N.C. AUX
Figure 7—Ex d Wiring Option
B2109
FIRE ALARM PANEL
X33AF DETECTOR
ALARM
ALARM
24 VDC
+
–
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 EOL RESISTOR SUPPLIED BY PANEL.
EOL
DEVICE 4
oiTEST 3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
N.O. FIRE2
N.O. FIRE
N.C. FIRE2
N.C. FIRE
COM FAULT1
COM FAULT
N.O. FAULT1N.O. FAULT
24 VDC + 24 VDC +
24 VDC – 24 VDC – 24 VDC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS-485 A
RS-485 B
MAN Oi
4-20 mA + 4-20 mA –
4-20 mA + REF
4-20 mA – REF
COM AUX
N.O. AUX
N.C. AUX
Figure 8—Ex d e Wiring Option

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 10
24 VDC
4 TO 20 mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
E2063*
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
4-20 mA + 4-20 mA –
4-20 mA + REF 4-20 mA
–
REF
24 VDC +
24 VDC –
24 VDC +
24 VDC – 24 VDC –
29
28
27
26
25
24
23
22
21
MAN Oi
X33AF IR DETECTOR
SPARE
SPARE
RS-485 A
RS-485 B
COM AUX
N.O. AUX
N.C. AUX
COM FIRE
N.O. FIRE
N.C. FIRE
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
COM FAULT
N.O. FAULT
Figure 9—X33AF Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sourcing)
24 VDC
4 TO 20 mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
E2064*
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
29
28
27
26
25
24
23
22
21
X33AF IR DETECTOR
4-20 mA +
4-20 mA + REF
24 VDC +
24 VDC –
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
24 VDC +
24 VDC – 24 VDC –
MAN Oi
SPARE
SPARE
RS-485 A
RS-485 B
COM AUX
N.O. AUX
N.C. AUX
4-20 mA –
4-20 mA
–
REF
Figure 10—X33AF Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sinking)
24 VDC
4 TO 20 mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
E2065*
Oi TEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
29
28
27
26
25
24
23
22
21
X33AF IR DETECTOR
–+
24 VDC
4-20 mA +
4-20 mA + REF
24 VDC +
24 VDC –
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
4-20 mA –
4-20 mA
–
REF
24 VDC +
24 VDC – 24 VDC –
MAN Oi
SPARE
SPARE
RS-485 A
RS-485 B
COM AUX
N.O. AUX
N.C. AUX
Figure 11—X33AF Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing)
24 VDC
4 TO 20 mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
E2066*
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
29
28
27
26
25
24
23
22
21
X33AF IR DETECTOR
–
+
24 VDC
4-20 mA +
4-20 mA + REF
24 VDC +
24 VDC –
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
4-20 mA –
4-20 mA
–
REF
COM FIRE
N.O. FIRE
N.C. FIRE
COM FAULT
N.O. FAULT
24 VDC +
24 VDC – 24 VDC –
MAN Oi
SPARE
SPARE
RS-485 A
RS-485 B
COM AUX
N.O. AUX
N.C. AUX
Figure 12—X33AF Detector Wired for Isolated 0 to 20 mA
Current Output (Sinking)
NOTES: 1. INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE
INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 11
Figure 13 – EEx d wiring option, AutroSafe/Autroprime
C NC NO - + - +
11
10
9 8 7 6 5
2K
BN-320
1 2 3 4
+ + - -
Detector loop in +
Detector loop out +
Detector loop out -
Detector loop in -
DETECTOR, EEx d wiring
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
oi TEST 3 (Optional)
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
N.O. FIRE2
N.O. FIRE
N.C. FIRE2
N.C. FIRE
COM FAULT1
COM FAULT
N.O. FAULT1
N.O. FAULT
24V DC + 24V DC +
24V DC – 24V DC – 24V DC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS-485 A
RS-485 B
MAN Oi
4-20 mA + 4-20 mA –
4-20 mA + REF 4-20 mA – REF
COM AUX
N.O. AUX
N.C. AUX
2K
910Ω
24V DC
+
-
C NC NO - + - +
11 10 9 8 7 6 5
2K
BN-320
1 2 3 4
+ + - -
Detector loop in +
Detector loop out +
Detector loop out -
Detector loop in -
DETECTOR, EEx e wiring
WIRING NOTES:
* IN ORDER TO ACHIEVE AN EEX E INSTALLATION, THE EOL RESISTOR MUST BE MOUNTED IN THE SAFE AREA.
** TERMINALS FOR CONNECTION OF THE EOL RESISTOR ARE NOT SUPPLIED AS STANDARD WITH BN-320.
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
oiTEST 3 (Optional)
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
N.O. FIRE2
N.O. FIRE
N.C. FIRE2
N.C. FIRE
COM FAULT1
COM FAULT
N.O. FAULT1
N.O. FAULT
24V DC + 24V DC +
24V DC – 24V DC – 24V DC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS-485 A
RS-485 B
MAN Oi
4-20 mA + 4-20 mA –
4-20 mA + REF 4-20 mA – REF
COM AUX
N.O. AUX
N.C. AUX
EOL
1K5
620 OHM
*
24V DC
+
-
**
Figure 14 – EEx e wiring option, AutroSafe/Autroprime

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 12
DETECTOR, EEx e wiring, non-latching detector
WIRING NOTES:
* IN ORDER TO ACHIEVE AN EEX E INSTALLATION, THE EOL RESISTOR MUST BE MOUNTED IN THE SAFE AREA.
** TERMINALS FOR CONNECTION OF THE EOL RESISTOR ARE NOT SUPPLIED AS STANDARD WITH BN-320.
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (N.O.) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
oiTEST 3 (Optional)
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
N.O. FIRE2
N.O. FIRE
N.C. FIRE2
N.C. FIRE
COM FAULT1
COM FAULT
N.O. FAULT1
N.O. FAULT
24V DC + 24V DC +
24V DC – 24V DC – 24V DC –
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS-485 A
RS-485 B
MAN Oi
4-20 mA + 4-20 mA –
4-20 mA + REF 4-20 mA – REF
COM AUX
N.O. AUX
N.C. AUX
EOL
1K5
620 OHM
*
24V DC
+
-
**
+ + - - - +
1 2 3 4 5 6
Detector loop in +
Detector loop out +
Detector loop out -
Detector loop in -
BN-300
Figure 16 – EEx d wiring option, BS-100
Figure 15 – EEx e non latching, BN-300

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 13
STARTUP PROCEDURE
When installation of the equipment is complete, perform
the “Fire Alarm Test” below.
FIRE ALARM TEST
1. Disable any extinguishing equipment that is connected
to the system.
2. Apply input power to the system.
3. Initiate an
oi
test. (See “Magnetic
oi
/ Manual
oi
”
under Optical Integrity in the Description section of
this manual.)
4. Repeat this test for all detectors in the system. If a unit
fails the test, refer to the “Troubleshooting” section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Autronica
Q1201C Laser Aimer is recommended for this
purpose.)
6. Enable extinguishing equipment when the test is
complete.
TROUBLESHOOTING
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the eld.
1. Disable any extinguishing equipment that is connected
to the unit.
2. Inspect the viewing windows for contamination
and clean as necessary. The detector is relatively
insensitive to airborne contaminants, however, thick
deposits of ice, dirt, or oil will reduce sensitivity.
(Refer to the “Maintenance” section for complete
information regarding cleaning of the detector viewing
windows.)
3. Check input power to the unit.
4. If the re system has a logging function, check the re
panel log for output status information. See Table 3
for information regarding 0 to 20 mA output.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
high levels of background IR radiation by covering the
detector with the factory supplied cover or aluminum
foil. If the fault condition clears within 6 minutes or
less, extreme background IR is present. Re-adjust
the view of the detector away from the IR source or
relocate the detector.
If none of these actions corrects the problem, return the
detector to the factory for repair.
NOTE
It is highly recommended that a complete spare
be kept on hand for eld replacement to ensure
continuous protection.
Table 3—Current Level Output Troubleshooting Guide
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.
Current Level
(±0.3 mA) Status Action
0 mA Power Fault Check system wiring.
1 mA General Fault Cycle power1
2 mA
oi
Fault Clean windows2
3 mA Hi Background
IR Fault
Remove IR source or
aim detector away
from IR source.
4 mA Normal Operation
20 mA Fire Alarm

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 14
MAINTENANCE
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
amepaths.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the eld.
NOTE
Refer to the X33AF Safety Manual (116-P-X33AF-
SIL2/CGB) for specific requirements and
recommendations applicable to the proper
installation, operation, and maintenance of all SIL-
Certied X33AF ame detectors.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X33AF must be
kept relatively clean. Refer to the procedure below for
cleaning instructions.
CLEANING PROCEDURE
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
To clean the windows and
oi
plate, use Autronicas window
cleaner (part number 116-001680-001) and a soft cloth,
cotton swab or tissue and refer to the following procedure.
1. Disable any extinguishing equipment that is
connected to the unit.
2. Since the X33AF is less affected by contamination
than other detectors, removal of the oi plate is needed
only under extreme conditions. In addition, it is not
necessary to achieve perfect cleanliness, because
IR is not signicantly absorbed by slight lms of oil
and/or salt. If a fault condition is still indicated after
cleaning, remove and clean the oi Plate Removal and
Replacement procedure.
3. In all environments, clean all three viewing windows
and reector surfaces thoroughly. Use a cotton
swab and Autonicas window cleaning solution. Use
Isopropyl alcohol for contaminations that Autronicas
window cleaning solution can not remove.
IMPORTANT
When used in extreme environments, the reective
surface of the detector
oi
plate may eventually
deteriorate, resulting in reoccurring
oi
faults and
the need for
oi
plate replacement.
oi
PLATE REMOVAL AND REPLACEMENT
1. Disable any extinguishing equipment that is connected
to the unit.
2. Loosen the two captive screws, then grasp the
oi
plate by the visor and remove it from the detector.
See Figure 17.
3. Install the new (or cleaned)
oi
plate.
NOTE
When installing the stainless steel plate, ensure
that the gasket is present and correctly seated to
prevent moisture or contaminants from penetrating
behind the plate. To ensure even seating, tighten
both screws equally.
4. Re-calibrate the detector's
oi
system. Refer to the
Inspector Monitor manual (95-8581) for instructions
regarding
oi
plate replacement and
oi
system
recalibration.
CAUTION
Do not replace the
oi
reector plate without also
recalibrating the
oi
system.
Recalibration of the
oi
system requires the use of
the Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the
oi
replacement kit, or they can be purchased separately. See
Ordering Information for details.
LOOSEN TWO CAPTIVE SCREWS
GRASP VISOR AND
REMOVE oiPLATE
B2106
Figure 17 –
oi
plate removal

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 15
X33AF Reector Plates
X33AF models are supplied with either a black or a
stainless steel reector plate. These plates are not
interchangeable. Order the replacement that matches the
reector plate on your X33AF ame detector.
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the system using the
Mag
oi
or Man
oi
feature should be performed regularly
to ensure that the system is operating properly. Refer to
Table 1 in the X33AF Safety Manual (116-P-X33AF-SIL2/
CGB) for frequency of proof tests. To test the system,
perform the “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual.
CLOCK BATTERY
The real time clock has a backup battery that will operate
the clock with no external power for nominally 10 years.
It is recommended that the battery be replaced every
7 years. Return the device to the factory for battery
replacement if needed.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the ame detector, but the time
stamping of the data log may be affected.
FEATURES
• Long detection range to carbonaceous res.
• Unequaled false alarm rejection.
• Responds to a re in the presence of modulated
blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm.
• Microprocessor controlled heated optics for increased
resistance to moisture and ice
• Automatic, manual or magnetic optical integrity (
oi
)
testing
• Easily replaceable
oi
plate.
• Fire, fault and auxiliary relays standard
• 0 to 20 mA isolated output (optional)
• HART communication (optional)
• EDT/DMT capable
• Multiple sensitivity levels
• A tricolor LED on the detector faceplate indicates
normal condition and noties personnel of re alarm
or fault conditions
• Operates under adverse weather conditions and in
dirty environments
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of installation.
• Explosion-proof/ame-proof detector housing. Meets
FM, CSA, ATEX Directive and CE certication
requirements
• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for under 0.5
second (available when model selected)
• 5 year warranty
• RFI and EMC Directive compliant
ASSOCIATED MANUALS
List of X33AF related manuals:
TITLE FORM NUMBER
SIL 2 (Safety) 116-P-X33AF-SIL2/CGB
HART Addendum 116-P-X33AFADDENDUM/YGB,
P/N 95-8624

Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev. E, 2013-08-13, P/N 95-8625-17.1, Rev: 2/13
Autronica Fire and Security AS
Page 16
SPECIFICATIONS
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
Without heater: 4 watts at 24 Vdc nominal;
5.2 watts at 24 Vdc in alarm.
4.5 watts at 30 Vdc nominal;
6.5 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total power: 17 watts at 30 Vdc with EOL resistor
installed and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts. For HART model, refer to Addendum
116-P-X33AFADDENDUM/YGB.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready to
indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or non-latching
operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open/normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
CURRENT OUTPUT (OPTIONAL)—
0 to 20 milliampere (±0.3 mA) dc current, with a maximum
loop resistance of 500 ohms from 18 to 19.9 Vdc and 600
ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +125°C.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100% condensing
humidity for short periods of time.
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis. Unlike
conventional detectors, the X33AF provides full coverage
at a minimum of 70% of the maximum detection distance.
Perfect cone of vision for methane re detection — 100
feet (30.5 m) on and off axis on “very high” setting.
Refer to Appendix A for FM Approved cone of vision data.
RESPONSE TIME—
Typical response times are under 10 seconds. Models are
available that can respond to automotive paint gun res
in under 0.5 seconds. See Appendix A and “Automotive
Addendum” (form number 95-8534) for actual response
times.
DIMENSIONS—
See Figure 18.
10.0
(25.4)
4.8
(12.2)
4.7
(11.9)
B2067
Figure 18—X33AF Dimensions in Inches (cm)
Other manuals for AutroFlame X33AF
1
Table of contents
Other Autronica Security Sensor manuals

Autronica
Autronica AutroFlame X33AF Installation and operating instructions

Autronica
Autronica AutroFlame BG-201 User manual

Autronica
Autronica AutroFlame X98AF User manual

Autronica
Autronica AutroGuard V-430 Release Note

Autronica
Autronica BWP-143A-SS/AG User manual

Autronica
Autronica AutroSense 75 Guide

Autronica
Autronica BG-21 User manual

Autronica
Autronica BG-201 User manual

Autronica
Autronica BS-100 DYFI Guide

Autronica
Autronica AutroFlame X33AF PL User manual