Inspection and Maintenance
CAUTION
•Avoid touching the installed ACTIVAL (valve body, yoke, joint). When being used to control hot water, it reaches
high temperature and may cause burn injury.
•Inspect the ACTIVAL according to Table 1.
•Manually open/close the ACTIVAL at least once a month if it is left in inactive state for a long period.
•Visually inspect the fluid leakage of the valve and the actuator operations every six months. If any of the problems
described in Table 2 are found, take corresponding actions shown in the table.
If your problem is not solved by the corresponding action, please contact Azbil Corporation near you.
Table 1. Inspection items and details
Inspection item Inspection interval Inspection detail
Visual inspection Semiannual •Fluid leakage from the gland and the flange face
•Loosened bolts
•Valve and actuator damages
Operating status Semiannual •Unstable open/close operation
•Abnormal noise and vibration
Routine inspection Any time •Fluid leakage to the outside
•Abnormal noise and vibration
•Unstable open/close operation
•Valve hunting
Table 2. Troubleshooting
Problem Part to check Action
Fluid leaks from the flange face. Loosened flange bolts
Gasket on the flange face
Misaligned piping
Tighten the flange bolts.
Replace the gasket.
Redo piping.
Fluid leaks from the gland. ⎯Consult with our sales personnel.
Fluid leaks from the bonnet. Loosened bolts Tighten the bolts.
Valve does not operate smoothly /
valve stops halfway /
valve does not operate at all.
Conditions of the power applied and of the input
signal applied
Loosened terminals
Wiring conditions / disconnected wires
Check the power supply and the controller
connected to.
Tighten the terminals.
Check the wiring.
Fluid leaks to the outside of the valve
when the ACTIVAL is in fully closed
position.
Actuator pointer not pointing to fully closed position Fully close the ACTIVAL.
The valve vibrates or produces an
abnormal noise.
Primary pressure condition
Differential pressure condition
Adjust the mounting position and change the
installation location.
The auxiliary switch does not actuate. Auxiliary switch (cam switch) condition
Loosened terminals
Wiring condition / disconnected wires
Redo the cam switch setting.
Tighten the terminals.
Check the wiring.
The auxiliary potentiometer does not
operate.
Condition of resistance
Loosened terminals
Wiring condition / disconnected wires
Check the resistance value (1 kΩ).
Tighten the terminals.
Check the wiring.
Valve hunting occurs. Secondary pressure condition
Differential pressure condition
Control stability
Adjust the mounting position and change
installation location.
Connect the control parameters setting for
controller.
Input signal disagrees with the feedback
output signal.
To completely shut off the valve, valve open and close (0-100% position) operation is controlled by
10-90 % range of actuator voltage/current input signal. Input signal therefore disagrees with the
feedback signal, and this is not an error.