4
AB-7057
Specications
For weight, refer to the table shown in the section Dimensions.
zValve specications
Item Specication
Model Two-way valve with anged-end connection (raised face ange), proportional control
Body pressure rating PN16 (Max. working pressure: 1.6 MPa)
End connection PN16 anged-end (equivalent to ISO 7005-2: 1988)
Size, Cv, Close-o rating
Note:
Close-o ratings of the actuator in
combination are shown on the right.
Practical close-o rating required for the
valve controlling 175 °C steam is 0.8 MPa.
Model number Nominal size Cv Close-o ratings
VY51_ _J0011 DN15 (1/2”) 1.0 1.0 MPa
VY51_ _J0012 DN15 (1/2”) 2.5 1.0 MPa
VY51_ _J0013 DN15 (1/2”) 6.0 1.0 MPa
VY51_ _J0014 DN15 (1/2”) 1.6 1.0 MPa
VY51_ _J0015 DN15 (1/2”) 4.0 1.0 MPa
VY51_ _J0021 DN25 (1”) 10 1.0 MPa
VY51_ _J0022 DN25 (1”) 16 1.0 MPa
VY51_ _J0041 DN40 (11/2”) 25 1.0 MPa
VY51_ _J0042 DN40 (11/2”) 40 1.0 MPa
VY51_ _J0051 DN50 (2”) 65 1.0 MPa
VY51_ _J0061 DN65 (21/2”) 95 1.0 MPa
VY51_ _J0081 DN80 (3”) 125 0.7 MPa
Materials Body Gray cast iron (GG-20)
Plug, stem Stainless steel
Seat ring Heat-resistant PTFE
Gland packing Inorganic ber
Gasket Non-asbestos joint sheet
Applicable uid Chilled/hot water, high temperature water, steam,
brine (ethylene glycol solutions, 50 % max.)
Allowable uid temperature 0 °C to 175 °C (Non-freezing)
Flow characteristic Equal percentage
Rangeability 100 : 1
Seat leakage 0.01 % of rated Cv value (0.0006 Cv or less for DN15 model)
Paint Gray
Actuator to be combined Integrated with the valve
zActuator specications
Item Specication
Power supply 24 V AC ± 15 %, 50 Hz/60 Hz
Power consumption Nominal 135 Ω feedback potentiometer type (Model VY511_J): 7 VA
Nominal 135 Ω resistance input type (Model VY512_J),
4-20 mA DC input type (Model VY513_J), 2-10 V DC input type (Model VY514_J),
0-10 V DC input type (Model VY515_J): 8 VA
Timing 63 ± 5 sec (50 Hz) / 53 ± 5 sec (60 Hz)
Control signal input - Nominal 135 Ω feedback potentiometer
(Total resistance: Nominal 135 Ω, Max. applied voltage: 5 V DC)
- Nominal 135 Ω resistance input
- 4 mA DC to 20 mA DC input (Input impedance: 100 Ω)
* Input impedance uctuates depending on temperature and other environmental conditions.
Therefore, a controller with 200 Ω or higher allowable load resistance is recommended.
- 2 V DC to 10 V DC input (Input impedance: 150 kΩ or higher)
* A controller with 100 kΩ or lower allowable load resistance is recommended.
- 0 V DC to 10 V DC input (Input impedance: 150 kΩ or higher)
* A controller with 100 kΩ or lower allowable load resistance is recommended.
Feedback signal output
(only with 4-20 mA DC input, 2-10 V DC input,
0-10 V DC input types)
Range: 2 V DC (0 % position) to 10 V DC (100 % position)
Allowable load resistance: 10 kΩ or higher (Max. output current: 1mA)
Materials Case Cast aluminum alloy
Top cover, terminal cover Polycarbonate resin (Color: gray)
Yoke Steel plate
Surface nishing Case None
Yoke Electro-galvanized (Bright chromate nish)
Valve position indication Pointer located at the bottom of the actuator shows the position by pointing at the value of
the scale (0: close to 100: open) on front, rear, and bottom sides.
Manual operation Available. Refer to the section Manually opening/closing the ACTIVAL.
Wires connection M3.5 screw terminal connection
Enclosure rating IEC IP54 (dust-proof and splash-proof)
Insulation resistance Between terminal and case: 5 MΩ or higher at 500 V DC
Dielectric strength Between terminal and case: 500 V AC/min with 5 mA or less leakage current