AB-6673
15
Address Setting (Addressing)
To SAnet interface module, ACTIVAL Model VY516XJ and other Intelligent Component Series devices including ACTIVAL
PLUS and damper actuators are connected via SAnet. Set address for the terminal devices (Intelligent Component Series
devices) so that the SAnet interface module can recognize all the terminal devices connected. Follow the procedure below to
set the address. For details regarding address setting (addressing), ask our sales/service personnel.
1) Unscrew the setscrews and remove the terminal cover. See Fig. 10 for removing the terminal cover.
2) Set address. (See Table 1.) Address can be set with rotary switch, with service pin switch, or based on SAnet ID. Rotary
switch and service pin switch are provided on this product. To set the address with service pin switch or based on SAnet ID,
Data Setter or PC-MMI is required. Set the address in either way according to your availability.
Setting with rotary switch:
Turn the rotary switch using a precision Phillips screwdriver and set.
Setting with service pin switch:
1. Set the rotary switch to ‘0’.
2. Start addressing operation* of Data Setter or PC-MMI.
Then, press the service pin switch. Do not keep the
switch pressed for longer than 5 seconds.
3.
ddress is set within 5 seconds after pressing the
service pin switch.
For the addressing operation of Data Setter or PC-MMI, ask
our sales/service personnel.
Setting based on SAnet ID:
1. Set the rotary switch to ‘0’.
2. With Data Setter or PC-MMI, enter the SAnet ID (on the
product code label) and address number to set. The
product code label is attached on the side surface of the
actuator, as shown in Fig. 14.
For the addressing operation of Data Setter or PC-MMI, ask
our sales/service personnel.
3) Attach the terminal cover after setting the address.
IMPORTANT:
While the terminal cover is removed, do not touch the terminal block or allow anything to touch the terminal
block.
If the service pin switch is kept pressed for longer than 5 seconds, the mode will be switched and operation
error (data point trouble) will be occurred. In such a case, press the service pin switch again and keep it
pressed for longer than 10 seconds to go back to the normal mode.
Table 1. Basic address setting of this product and other Intelligent Component Series devices
Add. Device Sub-DO Sub-DI
1 Outdoor air damper
2 Exhaust air damper
3 Return air damper
4 Switch damper of total heat exchanger for outdoor air
5 Switch damper of total heat exchanger for exhaust air
6 Chilled/hot water valve / Chilled water valve Filter alarm
7 Hot water valve (Chilled water valve) Humidifying ON/OFF
8 Humidifying valve
D (13) Reserved
E (14) Reserved
F (15) Reserved
Notes:
For ‘chilled/hot water valve + chilled water valve’ application, set address 6 for chilled/hot water valve and 7 for chilled water valve.
Items in bold characters are the basic address to set for this product.
The above table is a basic setting example. Set address and use sub-I/O in response to system configuration, installation location, and
wiring best suitable for your application.
LED
Service pin switch
(for Data Setter/PC-MMI)
Rotary switch
Terminal block
Ground terminal
Figure 13. Terminal block, LED, setting switches
(without terminal cover)
Figure 14. SAnet ID on the product code label
SAnet ID