Inspection and Troubleshooting
CAUTION
Do not carelessly touch the product when being used to control hot water.
The product temperature goes high, and you might get burned.
●Manually open/close the product at least once a month if it is left in inactive state for a long period after installation.
●Inspect the product according to Table 1.
●Visually inspect the product (e.g., fluid leakage) every six months. If any of the problems described in Table 2 are found,
take corresponding actions shown in the table.
If your problem is not solved by the corresponding action, please contact us.
Table 1. Inspection items and details
Inspection item Inspection interval Inspection detail
Visual inspection Semiannual Loosened lock lever
Valve and actuator damages
Fluid leakage from the gland/pipe connecting part
Operating status Semiannual Unstable open/close operation
Abnormal noise and vibration
Routine inspection Any time Abnormal noise and vibration
Unstable open/close operation
Valve hunting
Table 2. Troubleshooting
Problem Part to check
ction
Valve does not operate smoothly /
valve stops halfway /
valve does not operate at all.
Conditions of the power applied and of the input
signal applied to the actuator.
Wiring condition/disconnected wires of the actuator.
Foreign substance jammed.
Check the power supply and the controller
connected to.
Check the wiring.
Remove foreign substance by manually
opening the valve.
Fluid leaks to the outside of the valve
when the assembled actuator fully
closes the valve.
Confirm the mounting procedure referring to the
section Assembling the valve Model VY5302A
with the actuator Model MY53X0A.
Dismount and remount the actuator according
to the correct mounting procedure.
Valve hunting occurs. Secondary pressure condition.
Differential pressure condition.
Control stability.
Reset and adjust the valve inlet/outlet pressure.
Modify control parameter/PID setting of the
controller in connection to the assembled
actuator.
The auxiliary switch of the assembled
actuator does not operate.
Auxiliary switch (cam switch) condition.
Wiring condition/disconnected wires of the actuator.
Redo the cam switch setting.
Check the wiring.
Connecting part between the valve
and the actuator vibrates or produces
an abnormal noise.
Lock lever condition of the actuator.
Yoke damages.
Lock the lock lever.
Consult with our sales/service personnel.
Water flowing sound level is too high.
Consult with our sales/service personnel.
The assembled actuator in operation
produces an abnormal noise.
Consult with our sales/service personnel.
Voltage/current input signal of the
assembled actuator disagrees with the
feedback output signal.
To completely shut off the valve, valve open and close (0-100% position) operation is controlled by
10-90 % range of the actuator voltage/current input signal. Voltage/current input signal therefore
disagrees with the feedback signal, and this is not an error.